Example: quiz answers

TECHNICAL GUIDE Description R-410A ZF SERIES …

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE5167798-YTG-H-0717 TECHNICAL GUIDED escriptionASHRAE COMPLIANTYORK Predator units are convertible single packages with a common footprint cabinet and common roof curb for all through ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or Predator units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field units in all tonnage sizes are convertible between side airflow and down airflow, with corresponding economizer if economizer option is units are available in the following configurations: cooling only, cooling with electric heat, and cooling with gas heat.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 5167798-YTG-H-0717 TECHNICAL GUIDE Description ASHRAE 90.1 COMPLIANT YORK® Predator® units are convertible single packages with a

Tags:

  Guide, Technical, Descriptions, Technical guide description

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of TECHNICAL GUIDE Description R-410A ZF SERIES …

1 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE5167798-YTG-H-0717 TECHNICAL GUIDED escriptionASHRAE COMPLIANTYORK Predator units are convertible single packages with a common footprint cabinet and common roof curb for all through ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or Predator units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field units in all tonnage sizes are convertible between side airflow and down airflow, with corresponding economizer if economizer option is units are available in the following configurations: cooling only, cooling with electric heat, and cooling with gas heat.

2 Electric heaters are available as factory-installed options or field-installed units provide constant supply air volume. A variable air volume (VAV) option, which features a variable frequency drive (VFD), is available on through ton in accordance with: R-410A ZF SERIES - TON 60 HertzZF THROUGH 10 TON 5167798-YTG-H-07172 Johnson Controls Unitary ProductsTable of ContentsDescription .. 1 Table of Contents .. 2 Component Location .. 2 Nomenclature .. 3 Prior Nomenclature .. 4 Features and Benefits .. 5 GUIDE Specifications .. 11 Physical Data .. 15 Capacity Performance .. 18 Airflow Performance .. 28 Sound Performance .. 36 Electrical Data.

3 37 Typical Wiring Diagrams .. 45 Weights and Dimensions .. 61 Economizer Options .. 69 Component LocationCooling With Gas HeatRoof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from York Sunline footprint to the ZF SERIES footprints are also available (field installed accessory)Base rails w/forklift slots (three sides) and lifting holesCompressor #2 access (high- efficiency compressor) Dual stage cooling for maximum comfortSecond model nameplate inside hinged access panelTerminal block for hi-voltage connectionSmart Equipment control board w/screw connector for T-stat wiring and network connectionsDisconnect location (optional disconnect switch)Filter Access(2 or 4 filter options)Filter drier(solid core)

4 Slide-out motor and blower assembly for easy adjustment and serviceBelt-drive blower motorPower ventor motor20-guage aluminizedsteel tubular heatexchanger for longlife (stainless steeloption) Two-stage gas heating to maintain warm, comfortable temperatureIntelligent control board for safe and efficient operation Compressor #1 access (high-efficiency compressor) Toolless door latchSide entry power and control wiring knockoutsVFD Location (optional)Slide-out drain panwith 3/4 NPT,female connectionZF SERIES utilize Micro-ChannelAluminum Tube/Aluminum FinCondenser5167798-YTG-H-0717 Johnson Controls Unitary Products3 NomenclatureZ F 090CA2A1A1AA2 Product CategoryZ = A/C, Single Pkg., R-410AB = Standard StaticD = High StaticE = VFD/VAV Std StaticG = VFD/VAV High StaticH = VFD/VAV w/Bypass Std StaticK = VFD/VAV w/Bypass High StaticL = VFD/VAV Customer Std StaticN = VFD/VAV Customer High StaticP = VFD IntelliSpeed Std StaticR = VFD IntelliSpeed High StaticS = VFD w/Byp IntelliSp Std StaticU = VFD w/Byp IntelliSp Hi StaticV = VFD Cust IntelliSp Std StaticX = VFD Cust IntelliSp Hi StaticBlower OptionProduct Generation2 = Second GenerationC = Cooling OnlyE = Electric HeatHeat Type09 = 9 KW (078,090,102)18 = 18 KW (078,090,102,120,150)24 = 24 KW (078,090,102,120,150)36 = 36 KW (078,090,102,120,150)54 = 54 KW (120,150)12 = 120 MBH Input (078, 090, 102)

5 18 = 180 MBH Input (078,090,102,120,150)24 = 240 MBH Input (120,150)Heat Capacity078 = TonNominal Cooling Capacity090 = Ton102 = Ton120 = Ton150 = TonProduct IdentifierF = Pkg AC Std EffVoltage2 = 208/230-3-604 = 460-3-605 = 575-3-60 Additional Options1 = STD Throwaway Filter2 = 2" Pleated Filters (Merv 8)3 = 4" Pleated Filters (Merv 13)4 = Coil Guard (CG), STD Filter5 = 2" Pleated Filter,CG6 = 4" Pleated Filter,CGA = Std CabinetE = SSD (SST Drain Pan)R = Reverse Drain PanA = No EconomizerB = Economizer w/Barometric RLFD = Economizer w/Power EXHH = Motorized DamperOutdoor Air Option1 = No Service Options2 = DSC (Disconnect Switch)3 = NCO (Non-PWR Conv. Outlet)4 = PCO (Powered Conv. Outlet)5 = DSC,NCO6 = DSC,PCOA = No SensorsB = PHM (Phase Monitor)C = DFS (Dirty Filter Switch)D = SSD (Supply Air Smoke DET)E = RSD (Return Air Smoke DET)F = PHM,DFSG = PHM,SSDH = PHM,RSDJ = DFS,SSDK = DFS,RSDL = SSD,RSDM = PHM,DFS,SSDN = PHM,DFS,RSDP = PHM,SSD,RSDQ = DFS,SSD,RSDR = PHM,DFS,SSD,RSDR efrigerationA = Standard RefrigerationB = ECC (E-Coat Cond Coil)C = EEC (E-Coat Evap Coil)D = HGBP (Hot Gas Bypass)

6 F = ECC,EECG = ECC,EEC,HGBPJ = ECC,HGBPM = EEC,HGBPS ervice OptionsA = Stand Alone Smart Equipment C = BACnet MSTP,Mdbs,N2 COM CardD = CPC Control, DFS, APSF = Fault Detection DiagnosticsG = Novar UCM Ctrl, DFS, APSH = Hnywll Excel 10 CTRL,DFS,APSM = Verasys Single ZoneN = Verasys Change Over BypassP = Verasys VAVQ = Verasys Single Zone W/FDDR = Verasys COBP W/FDDT = Verasys VAV W/FDDC ontrols Ton York Model Number NomenclatureTwo Stage Natural Gas Heat OptionsN = 2 Stage Gas Aluminized SteelS = 2 Stage Gas Stainless Steel0000 = Cooling OnlyGas MBH Input (Unit Size Allowed)Electric Heat (Unit Size Allowed)SensorsACabinet Options5167798-YTG-H-07174 Johnson Controls Unitary ProductsPrior NomenclatureZ F 090N10 A2 AAA70124 AProduct CategoryZ = A/C, Single Pkg.

7 , R-410AC00 = Cooling Only. No heat installedHeat Type and Nominal Heat CapacityN10 = 100 MBH Output Aluminized SteelN15 = 150 MBH Output Aluminized SteelN20 = 200 MBH Output Aluminized SteelS10 = 100 MBH Output Stainless SteelS15 = 150 MBH Output Stainless SteelS20 = 200 MBH Output Stainless SteelE09 = 9 KWE18 = 18 KWE24 = 24 KWE36 = 36 KW E54 = 54 KW Gas Heat OptionsElectric Heat Options078 = TonNominal Cooling Capacity090 = Ton102 = Ton120 = Ton150 = TonProduct IdentifierF = + EER A/CVoltage2 = 208/230-3-604 = 460-3-605 = 575-3-60 Product StyleA = Style AB = Style BC = Style CA = No Options InstalledInstallation OptionsB = Option 1C = Option 2D = Options 1 & 2E = Option 3F = Option 4G = Options 1 & 3H = Options 1

8 & 4J = Options 1, 2 & 3K = Options 1, 2, & 4L = Options 1,3 & 4M = Options 1, 2, 3, & 4N = Options 2 & 3P = Options 2 & 4Q = Options 2, 3, & 4R = Options 3 & 4S = Option 5T = Options 1 & 5U = Options 1, 3, & 5V = Options 1, 4, & 5W = Options 1, 3, 4, & 5X = Options 3 & 5Y = Options 4 & 5Z = Options 3, 4 & 51 = Disconnect2 = Non-Pwr'd Conv. Outlet3 = Smoke Detector = Smoke Detector = Pwr'd Conv. Ton York Model Number NomenclatureFor Units Produced Before 2-01-2016 Product Generation7 = Seventh GenerationSS Drain PanConfiguration Options (not required for all units)These four digits will not be assigned until a quote is requested, or an order Controller, DFS, APSH oneywell Controller, DFS, APSN ovar Controller, DFS, APS2" Pleated Filters, MERV 7 BAS Ready Economizer (2-10 Actuator without a Controller)Shipping BagYork Commercial Comfort System (YCCS) Rtu ControllerHot Gas Bypass (Standard on VAV, Optional on CV)Variable Air Volume, VFD (not available with factory installed BAS options)Variable Air Volume, VFD Ready (for customer-provided, field-installed drive)

9 Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)Any Combination of Additional Options that Don t Have an Option Code Pre-assigned AA = NoneAB = Phase MonitorAC = Coil GuardAD = Dirty Filter SwitchAE = Phase Monitor & Coil GuardAF = Phase Monitor & Dirty Filter SwitchAdditional OptionsRC = Coil Guard, Shipping Bag & American FlagTA = Technicoat Condenser CoilTJ = Technicoat Evaporator CoilTS = Technicoat Evaporator & Condenser CoilsZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will belocated in digits 15-18. AG = Coil Guard & Dirty Filter SwitchAH = Phase Monitor, Coil Guard & Dirty Filter Switch4" Pleated Filters, MERV 13EA = E-Coat Condenser CoilEJ = E-Coat Evaporator CoilES = E-Coat Cond & Evap CoilsIntelliSpeed with VFDI ntelliSpeed, VFD and Manual BypassIntelliSpeed, VFD Ready (for customer-provided, field-installed drive)AirflowSimplicity Smart Equipment w/Comm Card (BACnet, N2, Mod-Bus)A = Std.

10 MotorD = Std. Motor/Motorized Damper (Downflow Only)H = Std Motor/Low Leak Econ/Barometric Relief (Downflow & Horizontal End Return Only)J = Std Motor/Low Leak Econ/Power Exhaust (Downflow & Horizontal End Return Only)N = Hi StaticR = Hi Static/Motorized Damper (Downflow Only)V = Hi Static Mtr/Low Leak Econ/Barometric Relief (Downflow & Horizontal End Return Only)W = Hi Static Mtr/Low Leak Econ/Power Exhaust (Downflow & Horizontal End Return Only)Fault Detection and Diagnostics (FDD)5167798-YTG-H-0717 Johnson Controls Unitary Products5 Features and BenefitsStandard Features Service Friendly - The Predator incorporates a number of key features for ease of time is reduced through the use of hinged, toolless panels.


Related search queries