Transcription of THREE PHASE uPS cATAloguE - Vertiv
1 THREE PHASE uPS cATAl o g uESolutions for Business Continuity2 Vertiv Vertiv designs, builds and services mission critical technologies that enable the vital applications for data centers, communication networks, and commercial and industrial environments. We support today's growing mobile and cloud computing markets with our portfolio of power, thermal, infrastructure management products, software and solutions, all complemented by our global service network. Bringing together global reach and local knowledge, and our decades-long heritage including brands like Chloride , Liebert , NetSure and Trellis , our team of experts is ready to take on your most complex challenges, creating solutions that keep your systems running-and your business moving. Together, we re building the future of a world where critical technologies always vision, our Offering4 Liebert EXS 10 kVA - 20 kVA6 Liebert NXC 30 kVA - 200 kVA8 Liebert ITA2 10 kVA - 20 kVA10 Liebert ITA 30 kVA - 40 kVA12 Liebert EXL S1 100 kVA - 1200 kVA14 Liebert APM 30 kW - 600 kW16 Liebert Trinergy Cube 150 kW - 3400 kWStatic Switches20 Liebert CROSS Rack 16 A.
2 32 A and 63 A22 Liebert CROSS Chassis/Cabinet from 160 A 1250 ARemote Diagnostics26 Vertiv LIFE Services4 Optimized and integrated THREE - PHASE UPS solution with high efficiency power protectionyyOutput power factor up to 1yyDouble conversion efficiency up to mode efficiency up to 99%yyCompact footprint with multiple internal runtime configurationsyyAvailable in 3/3 and 3/1 versionsyyIntegrated maintenance bypassyyIntegrated input and output breakers/switchesyyParallel capability for capacity and redundancyFEATuRES AND PERFoRMANcESCompact design and improved performancesThe new Liebert EXS is a monolithic transformer-free UPS which brings exceptional features for mission-critical applications. Its extraordinary double conversion efficiency up to ensures remarkable operational cost savings, reducing both the Total Cost of Ownership (TCO) and the environmental the same time, with its unity output power factor and high power density, Liebert EXS is able to provide the utmost active power possible in a compact footprint.
3 In fact, its improved design reduces its footprint to a minimum, providing continuous power protection with optimized internal runtime in a standalone solution, making the Liebert EXS perfect for both IT installations and other mission critical applications, such as transportation, emergency lighting, healthcare, retail and government Power Supply System (CPSS)Liebert EXS is compliant with the CEI EN 50171 standard, which defines the requirements that a UPS shall conform to in order to be considered as a CPSS, and hence capable of supplying the necessary emergency power to essential safety equipment without restrictions in power output. In fact, the unit can be used to power emergency escape lighting in case of normal supply failure and may also be suitable for powering other safety systems such as automatic fire extinguishing installations, signaling safety installations and smoke extraction ensure superior protection for critical loads, the Liebert EXS range has been designed to optimize specific rating requirements, thus enhancing flexibility and installation space needs.
4 Liebert EXS s flexibility is further enhanced through:yySingle and THREE PHASE output configurationsyyIntegrated parallel capability up to 4 unitsyyCommon or distributed battery bankyyInternal and external battery configurations for optimized back up time managementyyCasters for easy UPS repositioningOutput Configuration Liebert EXS models up to 20 kVA can be configured on-site to deliver THREE (3/3) or single (3/1) PHASE output giving it the flexibility to adapt to changes in installation AutonomyLiebert EXS provides an optimized integrated autonomy which results in back up times in a compact EXS 10 kVA - 20 kVAIts internal architecture is able to house up to four battery strings, further optimizing integrated autonomy and delivering the added advantage of virtually eliminating the need for an external battery cabinet. This furthermore reduces installation costs and minimizes the demand on physical space. In addition, Liebert EXS s powerful battery charger ensures rapid recharge, increasing its ability to manage longer back up Galvanic IsolationLiebert EXS offers integrated full galvanic isolation, meaning that an isolation transformer may be housed inside the UPS cabinet.
5 This greatly reduces the system footprint, thus providing space saving transformer may be connected to the input or to the output of the UPS, providing:yyFull galvanic isolation for medical and other critical applicationsyyInstallation with two independent input sources (with different neutrals)yyInstallation in distribution without 10 kva - 20 kva5 Liebert EXS SpecificationsTEcHNicAl cHARAcTERiSTicS Ratings (kVA)101520iNPuTNominal input voltage (V)380/400/415 ( THREE - PHASE + neutral)Input voltage range without battery discharge (V)173 to 498*Nominal frequency (Hz)50/60 Input frequency range (Hz)40 to 70 Input power factor at full load (kW/kVA) THD at full linear load (THDI%) 3%*Bypass voltage tolerance (%)selectable from +20 to -40 Bypass frequency tolerance (%) 20 ( 10 selectable)bATTERYB attery blocks per string 24-40*Voltage temperature compensation (mV/ C/Cell) charger max. current (A)13ouTPuTNominal output voltage (V)380/400/415 ( THREE - PHASE ) or 220/230/240 (single- PHASE )Nominal output frequency (Hz)50/60 Maximum active power (kW)101520 THDv at full linear load (%) 2 Inverter overload capacity105% for 60 min; 125% for 5 min; 150% for 1 min; >150% for 200msDouble conversion efficiencyUp to mode efficiency (%)Up to 99%DiMENSioNS AND wEigHTDimensions (W x D x H) mm335 x 650 x 1300 Net/Shipping weight (excluding battery) kg85/115 Net/Shipping weight (including 2*32 batteries) kg285/315gENERAlNoise at 1 m (dBA) 58 Maximum altitude1500 m without derating (max.)
6 3000 m)Protection level IEC (60529)IP20 General and safety requirements for UPSEN/IEC/AS 62040-1 EMC requirements for UPSEN/IEC/AS 62040-2 UPS classification according to CEI EN 62040-3 VFI-SS-111* Conditions apply6 Compact and Reliable Power in a Fully Integrated Packaged SolutionTo ensure superior protection for critical loads, the Liebert NXC range has been designed to optimize specific rating requirements, thus enhancing flexibility and installation space nXC FamilyliEbERT NXc 30 kVA - 200 kVAContinuous Reliability:The Liebert NXC 30 - 200 kVA range offers reliable and flexible secure power in a fully integrated package solution. Its highly efficient transformer-free double conversion technology delivers installation and running cost savings. With a rated output power factor up to 1, Liebert NXC is also able to provide greater active power than a traditionally rated power factor NXC achieves up to 96% efficiency in double conversion mode and up to 99% in ECO mode, thus ensuring effective load protection, while reducing the total cost of ownership (TCO) Continuous Liebert NXC 30 - 200 kVA range offers reliable and flexible secure power in a fully integrated package solution.
7 Its highly efficient transformer-free double conversion technology delivers installation and running cost savings. With a rated output power factor up to 1, Liebert NXC is also able to provide greater active power than a traditionally rated power factor NXC achieves up to 96% efficiency in double conversion mode and up to 99% in ECO mode, thus ensuring effective load protection, while reducing the total cost of ownership (TCO) and environmental impactLiebert NXC s combination of performance features, impressive integrated autonomy and compact footprint make it ideal for guaranteeing clean, continuous power for a wide range of applications from IT and manufacturing to retail and low THDi and active input power factor correction ensure that the current absorbed from the upstream distribution network is near equal to its nominal output current, hence eliminating the need for oversizing gensets and other and Performances:yyOutput power factor up to 1yyDouble conversion efficiency up to 96%yyECO mode efficiency up to 99%yyInput current total harmonic distortion correction (THDi) < 3%yyBattery charger up to 50 AyyIntegrated manual bypassyyIntegrated input and output breakers/switches (30-60 kVA)yyIntegrated parallel load bus and synchronization port (LBS)7 Liebert NXC SpecificationsTEcHNicAl cHARAcTERiSTicS Ratings (kVA)30406080100120160200iNPuTNominal input voltage (V)380/400/415 Input voltage range without battery discharge (V) 305 to 477 Nominal frequency (Hz)50/60 Input frequency range (Hz)40 to 70 Input power factor (kW/kVA) THD at full linear load (THDI%)<5<3 Bypass voltage tolerance (%)selectable from +20 to -40 Bypass frequency tolerance (%) 20 ( 10 selectable)bATTERYN umber battery cells per string Max: 240; Min: 192 Max: 264.
8 Min: 180 Voltage temperature compensation (mV/ C/Cell) (selectable 0 to around 25 C or 20 C or inhibit) (selectable from 0 to around 25 Cto 30 C, or inhibit)Battery charger max. power (kW) output voltage (V)380/400/415 ( THREE - PHASE )Nominal output frequency (Hz)50/60 Nominal active power (kW)27365480100120160200 THDv with 100% linear load (%) 2 Inverter overload capacity105% for 60 min; 125% for 5 min; 150% for 1 min; >150% for 200ms105% with continuous operation; 125% for 10 min; 150 for 1min; >150% for 200msDouble conversion efficiency 100% mode efficiency (%) and weightDimensions (W x D x H) mm600 x 850 x 1600600 x 1000 x1600600 x 1000 x 2000 Weight (excluding battery) kg210/245225/260285/313337/365475/525520 /570 Weight (including 32 batteries) kg600/635615/650N/AgENERAlNoise at 1 m (dBA) 56 58 58 59 60 60 61 62 Protection level IEC (60529)IP20 General and safety requirements for UPSEN/IEC/AS 62040-1 EMC requirements for UPSEN/IEC/AS 62040-2 UPS classification according to CEI EN 6240-3 VFI-SS-1118 Remarkable Efficiency and Flexibility Characterize the Liebert ITA2 UPSF eaturing true online double conversion technology, unity power factor and an extremely compact rack-tower design, Liebert ITA2 is the perfect power protection solution for your computer rooms, storage and network a unity output power factor, Liebert ITA2 perfectly matches the needs of modern IT loads, and with its wide input voltage and frequency range it effectively reduces the need for battery intervention, thus prolonging battery is also endowed with intelligent fans with automatic speed control, which effectively save energy and reduce ITA2 supports common battery configurations between paralleled UPS and the number of batteries per string, which can be arranged flexibly.
9 Facilitating the utilization of different battery systems and saving on battery investment. An extra powerful battery charger across all models capable of recharging high capacity battery strings ensures a fast charge-restoration even after a prolonged power ITA2 offers enhanced flexibility with a wide range of accessories for both stand-alone and rack-mount installations. When rack mounted, it allows to install up to 20 kVA in just 3 U of space, achieving a remarkable space saving. Parallelability and maintenance are facilitated through the use of dedicated maintenance bypass option while extended backup time can be provided with matching battery modules for a neat rack-mounted ITA2 features a multi-lingual LCD user interface allowing close control and monitoring of system status and iTa2 10 - 20 kvaProduct Features:yyRack-tower design for installation flexibilityyyAble to deliver both THREE - PHASE and single- PHASE output yyUltra high power density, thanks to 30% reduced dimensions compared to the previous input power factor for better grid or generator compatibilityyyUnity output power factor for additional power availabilityyyEfficiency in double conversion up to yyECO mode operation with efficiency up to 99% and remarkable energy-saving performanceyyPowerful charging capability for minimum battery recharging timeProgrammable dry contactsLiebert ITA2 includes two output dry contacts which can be set to.
10 YyLow battery (default)yyOn bypassyyOn batteryyyUPS faultIt also includes two programmable input dry contacts, which can be set to:yyMaintenance mode (default)yyBattery mode shutdownyyAny mode shutdownProgrammable power outputsLiebert ITA2 includes two types of power terminals:yyStandard outputs: sA, sB, sCyyProgrammable outputs: pA, pB, pCIt is possible to power down the load connected to the programmable outputs according to:yyRemaining backup time (min)yyRemaining battery capacity (%)yyTime spent in battery mode (mins)yyOverload when in battery modeliEbERT iTA2 10 kVA - 20 kVA9 TEcHNicAl SPEciFicATioNSRatings (kVA)101520iNPuTNominal input voltage (V)380/400/415 ( THREE - PHASE + neutral)Input voltage range without battery discharge (V)173 to 498*Nominal input frequency (Hz)50/60 Input frequency range (Hz)40 -70 Bypass voltage tolerance (%)selectable from +20 to -40 Bypass frequency tolerance (%) 20 ( 10 selectable)Input power factor at full load (kW/kVA) THD at full linear load (THDI%) 3*bATTERY MANAgEMENTB attery blocks per string24-40*Voltage temperature compensation (mV/ C/Cell)-3mV C/CellBattery charger max.