Example: dental hygienist

TL70 Modular Tower Light - Banner Engineering

Instruction ManualBanner's tl70 Tower Light is a 70 mm, Modular LED indicator with extremely bright and uniformlight. The modularity gives the user flexibility to customize Tower lights as needed and changepositions in the field. The tl70 is also available preassembled for easy installation. Light segments have user-selectable solid ON or flashing Up to six colors, or five colors plus audible, in one device Rugged, water-resistant IP65 housing with UV-stabilized material Bright, uniform indicator segments appear gray when off to eliminate false indicationfrom ambient Light Several connection options to choose from including M12/Euro-style quick disconnect,cabled, and terminal-wiredModelsB-TL70Q5 ConnectionHousingTL70 BaseTL70 SegmentsBase SegmentSG- tl70 HousingTL70 SegmentHousing ColorBlank = BlackC = GrayHousing ColorBlank = BlackC = GrayRColor/Alarm5 = 2 m, 5-wire Integral Cable8 = 2 m, 8-wire Integral CableT = TerminalQ5 = 5-pin M12/Euro-style Integral QDQ8 = 8-pin M12/Euro-style Integral QDQP5 = 150 mm ( in) cable with 5-pin M12/Euro-style QDQP8 = 150 mm ( in)

Instruction Manual Banner's TL70 Tower Light is a 70 mm, modular LED indicator with extremely bright and uniform light. The modularity gives the user flexibility to customize tower lights as …

Tags:

  Light, Modular, Towers, Tl70 modular tower light, Tl70

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of TL70 Modular Tower Light - Banner Engineering

1 Instruction ManualBanner's tl70 Tower Light is a 70 mm, Modular LED indicator with extremely bright and uniformlight. The modularity gives the user flexibility to customize Tower lights as needed and changepositions in the field. The tl70 is also available preassembled for easy installation. Light segments have user-selectable solid ON or flashing Up to six colors, or five colors plus audible, in one device Rugged, water-resistant IP65 housing with UV-stabilized material Bright, uniform indicator segments appear gray when off to eliminate false indicationfrom ambient Light Several connection options to choose from including M12/Euro-style quick disconnect,cabled, and terminal-wiredModelsB-TL70Q5 ConnectionHousingTL70 BaseTL70 SegmentsBase SegmentSG- tl70 HousingTL70 SegmentHousing ColorBlank = BlackC = GrayHousing ColorBlank = BlackC = GrayRColor/Alarm5 = 2 m, 5-wire Integral Cable8 = 2 m, 8-wire Integral CableT = TerminalQ5 = 5-pin M12/Euro-style Integral QDQ8 = 8-pin M12/Euro-style Integral QDQP5 = 150 mm ( in) cable with 5-pin M12/Euro-style QDQP8 = 150 mm ( in)

2 Cable with 8-pin M12/Euro-style QDModels with a quick disconnect require a mating cordsetA = Standard AudibleO = OrangeW = WhiteAP = Programmable AudibleALM = Loud Multi-Tone AudibleAL = Loud AudibleB = BlueR = RedG = GreenY = YellowSelect the 5-pin base for Tower Light configurations of up to 4 modules. Select the 8-pin base for Tower Light configurations of up to 6 modules. Example base model number: B- tl70 -Q5 Example Light segment model number: SG- tl70 -G Example audible segment model number: SG- tl70 -ATL70 HousingTL70 Pre-Assembled ModelsWBGYROH ousing ColorBlank = BlackC = GrayAudible Alarm*Blank = NoneA = Standard AudibleQConnectionBlank = 2 m Integral CableT = TerminalQ = M12/Euro-style Integral QDQP = 150 mm ( in) cable with 5-pin M12/Euro-style QDModels with a quick disconnect require a mating cordsetColor/PositionO = OrangeW = WhiteAP = Programmable Audible* not available with six- Light modelsAL = Loud AudibleB = BlueR = RedG = GreenBlank = NoneY = Yellow123456 Example pre-assembled model number: Modular Tower Light Original Document182214 Rev.

3 G12 October 2017182214 Configuring the Modules12345678910 Turn on the appropriate DIP switch to set the order of the components, counting up from the towerlight's 1 Module 2 Module 3 Module 4 Module 5 Module 6 BaseAssembly OptionsDIP Switches12345678 Light andStandard AudibleComponentsModule 1 ONModule 2 ONModule 3 ONModule 4 ONModule 5 ONModule 6 ONLight ModuleFlash Rate3 HzONONS olid On*OFFOFFS tandard AudibleModule SettingsPulse HzONOFFC hirp AlarmONONS iren AlarmOFFONC ontinuousAlarm*OFFOFFA ssembly OptionsDIP Switches12345678910 Loud AudibleModuleSettingsPulse HzONOFFC hirp AlarmONONS iren AlarmOFFONC ontinuousAlarm* * Factory default setting tl70 Modular Tower - Tel: +1-763-544-3164P/N 182214 Rev. GAssembling the ModulesTo assemble the modules:1. Align the notches on each module and Rotate the top module clockwise to lock intoplace (notches shown in the locked position).Wiring DiagramsPNP Input ModuleM2M3M1M43412512 30 V dc NPN Input ModuleM2M3M1M43412512 30 V dc Euro-style Male Pinouts 14532 Key1 = brown2 = white3 = blue4 = black5 = grayM1 = Module 1M2 = Module 2M3 = Module 3M4 = Module 4 PNP Input 7621548312 30 V dcModuleM1M2M3M4M5M6 Not Used NPN Input 7621548312 30 V dcModuleM1M2M3M4M5M6 Not Used Euro-style Male Pinouts 56718234 Key1 = white2 = brown3 = green4 = yellow5 = gray6 = pink7 = blue8 = redM1 = Module 1M2 = Module 2M3 = Module 3M4 = Module 4M5 = Module 5M6 = Module 6TL70 Modular Tower Light P/N 182214 Rev.

4 - Tel: +1-763-544-31643 Wiring Terminal Block Terminal Block Key0 = dc common1 = Module 12 = Module 23 = Module 34 = Module 45 = Module 56 = Module 6 SpecificationsSupply Voltage and Current12 V dc to 30 V dcIndicator Color or Audible ModelMaximum Current (mA)at 12 V dcat 30 V dcBlue, Green, White420150 Red, Yellow, Orange285120 Standard Audible3030 Loud Audible (Intensity 1)3025 Loud Audible (Intensity 2)5040 Loud Audible (Intensity 3)16575 Loud Audible (Intensity 4)350120 Supply Protection CircuitryProtected against transient voltagesIndicators1 to 6 colors depending on model (Green, Red, Yellow, Blue, White, andOrange)LEDs are independently selectedFlash Rates: Hz 10% and 3 Hz 10%Indicator Response TimeOff Response: 150 s (maximum) at 12 to 30 V dcOn Response: 180 ms (maximum) at 12 V dc; 50 ms (maximum) at 30 V dcAudible AlarmStandard Audible: kHz 250 Hz oscillation frequency; maximum intensity(typical) 92 dB at 1 m ( ft)Loud Audible: kHz 250 Hz oscillation frequency; maximum intensity(typical) at 1 m ( ft) (see table)DIP SwitchesMax Intensity (Loud Audible)910 ONONI ntensity 4: 101 dBOFFONI ntensity 3: 99 dBONOFFI ntensity 2: 92 dBOFFOFFI ntensity 1: 85 dBAudible AdjustmentStandard Audible: Rotate the cover until the desired volume is reachedLoud Audible Alarm: Select the desired volume using DIP switches 9 and 10 Typical Reduction in Sound Intensity with Audible Adjustment (maximum tominimum): Standard Audible: 8 dB Loud Audible: 16 dBConstructionBases, Segments, Covers: polycarbonate tl70 Modular Tower - Tel: +1-763-544-3164P/N 182214 Rev.

5 GIndicator CharacteristicsColorDominant Wavelength (nm)or Color Temperature (CCT)Color Coordinates1 LumenOutput(Typical at25 C)xyGreen525 nm 92 Red625 nm 40 Yellow590 nm 22 Blue470 nm 32 White5000 K 125 Orange M12/Euro-style quick disconnect connector, 8-pin M12/Euro-style quickdisconnect connector, 150 mm ( in) PVC cable with an M12/Euro-style quickdisconnect connector, terminal block, or 2 m ( ft) unterminated cable,depending on modelTerminal Block Models14 to 28 AWG wireOperating Conditions 40 C to +50 C ( 40 F to +122 F)95% at +50 C maximum relative humidity (non-condensing)Environmental RatingIEC IP65 CertificationsVibration and Mechanical ShockVibration 10 Hz to 55 Hz mm p-p amplitude per IEC 60068-2-6 Shock 15G 11 ms duration, half sine wave per IEC 60068-2-27 Required Overcurrent ProtectionWARNING: Electrical connections must be madeby qualified personnel in accordance with localand national electrical codes and protection is required to be provided by end product applicationper the supplied protection may be provided with external fusing or via CurrentLimiting, Class 2 Power wiring leads < 24 AWG shall not be additional product support, go to Wiring (AWG)Required Overcurrent Protection (Amps) mm[ ]M12 1M30 (mounting nutincluded)Internal threads1/2-14 NPTMax Torque.

6 Nm[20 in-lbf]ModelHeight (H)1 Light mm ( in)1 Light module, 1 audible mm ( in)2 Light mm ( in)2 Light modules, 1 audible module194 mm ( in)3 Light modules187 mm ( in)3 Light modules, 1 audible mm ( in)4 Light mm ( in)4 Light modules, 1 audible mm ( in)5 Light mm ( in)5 Light modules, 1 audible mm ( in)1 Refer to CIE 1931 chromaticity diagram or color chart, to show equivalent color with indicated color Modular Tower Light P/N 182214 Rev. - Tel: +1-763-544-31645 AccessoriesCordsets5-Pin Threaded M12/Euro-Style Cordsets Single EndedModelLengthStyleDimensionsPinout (Female) m ( ft)Straight44 Typ. x 1234151 = Brown2 = White3 = Blue4 = Black5 = m (6 ft) m (15 ft) m (30 ft) m (6 ft)Right-Angle 32 Typ.[ "]30 Typ.[ "] [ "]M12 x 1 m (15 ft) m (30 ft)8-Pin Threaded M12/Euro-Style Cordsets with Open-ShieldModelLengthStyleDimensionsPin out (Female) m (6 ft)Straight 44 Typ. x 1 54328176 1 = White2 = Brown3 = Green4 = Yellow5 = Gray6 = Pink7 = Blue8 = m (15 ft) m (30 ft) m (50 ft) m (6 ft)Right-Angle 32 Typ.

7 [ "]30 Typ.[ "] [ "]M12 x 1 m (15 ft) m (30 ft) m (50 ft)All measurements are listed in millimeters, unless noted otherwise. tl70 Modular Tower - Tel: +1-763-544-3164P/N 182214 Rev. GMounting BracketsSMB30A Right-angle bracket with curvedslot for versatile orientation Clearance for M6 ( in)hardware Mounting hole for 30 mmsensor 12-ga. stainless steel456169 ABCHole center spacing: A to B=40 Hole size: A= , B= x , C= 12-ga. stainless steel bracketwith curved mounting slots forversatile orientation Clearance for M6 ( in)hardware Mounting hole for 30 mmsensor7057 ABC57 Hole center spacing: A = 51, A to B = size: A = x 7, B = , C = Flat SMBAMS series bracket 30 mm hole for mountingsensors Articulation slots for 90 +rotation 12-ga. 300 series stainless steel4593 ACBHole center spacing: A= , A to B= size: A= x , B= , C= Single 30 mm hole 8 gauge steel, black finish(powder coat) Front surface for customerapplied labels80856045 BAHole size: A = 7 , B = 30 All measurements are listed in millimeters, unless noted Mount SystemModelFeaturesComponentsSA-M30 - Black Polycarbonate Streamlined black PC or Gray PC thread cover Covers M30 thread on the Light base Mounting hardware includedSA-M30C - Gray PolycarbonatePolished 304 StainlessSteelBlack AnodizedAluminumClear AnodizedAluminum Elevated-use stand-off pipe ( in.)

8 NPSM/DN15) Polished 304 stainless steel, black anodized aluminum,or clear anodized aluminum surface in. NPT thread at both ends Compatible with most industrial environmentsSOP-E12-150SS 150 mm (6 in) longSOP-E12-150A150 mm (6 in) longSOP-E12-150AC 150 mm (6 in) longSOP-E12-300SS 300 mm (12 in) longSOP-E12-300A 300 mm (12 in) longSOP-E12-300AC 300 mm (12 in) longSOP-E12-900SS 900 mm (36 in) longSOP-E12-900A 900 mm (36 in) longSOP-E12-900AC 900 mm (36 in) longSA-E12M30 - Black Acetal Streamlined black acetal or white UHMW mountingbase adapter/cover Connects between in. NPSM/DN15 pipe and 30 mm(1-3/16 in) drilled hole Mounting hardware includedSA-E12M30C - White UHMWPipe Mounting FlangeModelFeaturesConstructionSA-F12 For use elevated stand-off pipes ( in,NPSM/DN15) M5 mounting hardware and nitrile gasketincludedDie-cast zinc base with blackpaint10 28 701/2-14 NPSM4x Modular Tower Light P/N 182214 Rev. - Tel: +1-763-544-31647 Foldable Mounting BracketsModelFeaturesConstructionSA-FFB1 2 For use with 1/2 inch stand-off pipes Stainless steel hardwareBlack polycarbonate111110 1/2-14 NPSM4 x 5 70SA-FFB12 CGray polycarbonateLMB Sealed Right-Angle BracketsModelDescriptionConstructionLMB3 0 RADirect-Mount Models: Bracket kit with base, 30 mmadapter, set screw, fasteners, o-rings, and gasketsBlack polycarbonateLMB30 RACGray polycarbonateLMBE12 RAPipe-Mount Models: Bracket kit with base, -14 pipeadapter, set screw, fasteners, o-rings, and gaskets.

9 Foruse with stand-off pipe (listed and sold separately)Black polycarbonateLMBE12 RACGray polycarbonateBanner Engineering Corp. Limited WarrantyBanner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair orreplace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not coverdamage or liability for misuse, abuse, or the improper application or installation of the Banner LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OFMERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp.

10 , replacement. IN NO EVENT SHALL Banner Engineering CORP. BE LIABLE TO BUYER OR ANYOTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCTDEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previouslymanufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when theproduct is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void theproduct warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any and product information in English supersede that which is provided in any other language.


Related search queries