SIEMENS-ALLIS JfR DISTRIBUTION volt AGE REGULATORS USERS MANUAL 21Xl263-10 www . ElectricalPartManuals . com www . ElectricalPartManuals . com 2 SIEMENS-ALLIS JFR DISTRIBUTION VOLTAGE REGULATORS CONTENTS-------------------------------- ------------ SUBJECT Page SUMMARY OF PROCEDURES .. 3 Placing Regulator in Service .. 3 Checking Regulator Accu/Stat Control .. 3 Removing Regulator from Service .. 3 WARRANTY .. 3 INTRODUCTION .. 4 Inspection for Damage in Shipping 4 Storage.

VOLT AGE REGULATORS USERS MANUAL www 21Xl263-10 . ElectricalPartManuals . com . www . ElectricalPartManuals . com . 2 SIEMENS-ALLIS JFR ... PI!RCI!NT LOAD Installation Diagrams k.C f/ / ll www . ElectricalPartManuals . com . www . ElectricalPartManuals . com . 6 SOURCE LIGHTNING ARRESTER r I I I I I I I I I I I I I I BY-PASS ARRESTER ...

Tags:

  Regulators, Volt, Volt age regulators

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of VOLT AGE REGULATORS - ElectricalPartManuals.com

1 SIEMENS-ALLIS JfR DISTRIBUTION volt AGE REGULATORS USERS MANUAL 21Xl263-10 www . ElectricalPartManuals . com www . ElectricalPartManuals . com 2 SIEMENS-ALLIS JFR DISTRIBUTION VOLTAGE REGULATORS CONTENTS-------------------------------- ------------ SUBJECT Page SUMMARY OF PROCEDURES .. 3 Placing Regulator in Service .. 3 Checking Regulator Accu/Stat Control .. 3 Removing Regulator from Service .. 3 WARRANTY .. 3 INTRODUCTION .. 4 Inspection for Damage in Shipping 4 Storage.

2 4 Protective Measurl!s .. 4 Location .. 5 INSTALLATION DIAGRAMS .. 5 CONNECTION DIAGRAMS Straight Design .. 6 Inverted Design .. 7 Series Transformer Design . 8 PLACING REGULATOR IN SERVICE Before Connecting .. 9 Energizing and Checking Control Operation .. 9 Switching the Regulator "On the Line" .. 9 Checking Mechanism Operation .. 9 Set Vari-Amp Limits .. 9 Energizing and Checking the Control Panel .. 9 External Power Supply .. 9 Bandwidth Check.

3 10 Voltage Level Check .. 10 CONTROL DIAGRAMS IJ-2 Control -Wiring Diagram .. 11 IJ-2 Control -Schematic Diagram .. 11 IJ 2A Control Wiring Diagram .. 12 IJ 2A Control -Schematic Diagram .. 12 IJ-2 Control Circuit-Schematic Diagram .. 13 IJ-2A Control Circuit-Schematic Diagram .. 13' SETTING THE Accu/Stat CONTROLS Introduction .. 14 Voltage Level .. 14 Band Width .. 14 Time Delay .. 14. USERS MANUAL SUBJECT Page Setting line Drop Compensator.

4 14 Load Center Method .. 14 Average Increase Method .. 14,15 Test for Determining Leading and Lagging Regulator (Open Delta) . 16 Further Results of Test . 16 Setting Compensator with Capacitors on the Line .. 16 Table I Distribution Line Resistance and Reactance .. 17 Table II Compensator Multiplier Table .. 17 Table Ill Line Drop Compensator Settings For REGULATORS Connected in Delta .. 18 MAINTENANCE Periodic Inspection .. 19 Accu/Stat Control Maintenance.

5 19 Removing Regulator From Service .. 19 Untanking .. 19 Overloading Regulator . : .. 19 SPECIAL FEATURES Polarized Jack Plug and Hinged Panel .. 20 Vari-Amp Position Indicator, Mounting .. 20 Operation at Less Than Rated Voltage .. 20 Unidirectional Breather .. 21 Reset Drag Hand .. 21 Table IV System Operating Voltages .. 21 Table V Regulating Ranges and Current Capacities .. 21 OPTIONAL FEATURES Forced Air Cooling .. 22 Remote Mounting of Control Compartment .. 22 Installation of the Remote Mounting Kit.

6 22 Meter Sockets .. 23 PARTS LIST Major Components .. 24 Instructions for Ordering Parts .. 24 Accu/Stat Control Panel-Types IJ-2, IJ2A .. 24,25 Dial Switch -Type TLG .. 26 Quick Break Mechanism-Type TLG .. 27 Dial Switch -Type TLF .. 28 Quick Break Mechanism-Type TLF .. 29 Bushings and By-Pass Arresters .. , .. 30,31 www . ElectricalPartManuals . com www . ElectricalPartManuals . com PLACING REGULATOR IN SERVICE (without interrupting the load) For detailed instructions see page 9. 1. The by-pass switch 1, Fig. (7, 10, 13), is in series with the line and will of course, be closed if the line is carrying load.

7 Close the disconnect switch 2, Fig. (7, 10, 13), on the source side of the regulator. This excites the regulator to full line voltage. 2. Run the tap changer to "Neutral" position. 3. Turn transfer switch and voltage source switch to "off". 4. Remove both fuses on front of control panel. 5. Close the disconnect switch 3, Fig (7, 10, 13), on the load side of the regulator. CHECKING REGULATOR ACCUISTAT CONTROL 6. Open the by-pass switch 1. The regulator then carries load. 7. Replace fuses on front of control panel. 8. Set voltage source switch to "Normal".

8 9. Adjust the control (see Page 13) and set the transfer switch to "automatic" position. CAUTION Source (S),Ioad (L) and neutral (SL) designation of bush ings stamped on cover. Check before connecting to line. For detailed instructions to check band width and voltage see page 10. 1. Move transfer switch from "automatic" to "raise" 3. Check the regulator operation in the "lower" dirac-position and allow regulator to operate about five tion in the same manner. steps. 4. If the control operation is satisfactory, return the 2. Return the transfer switch to "automatic" operation.

9 Transfer switch to the "automatic" position. After a short time delay the regulator will operate, and come to rest. REMOVING REGULATOR FROM SERVICE (without interrupting service) 1. Run the regulator to the "Neutral" position. 2. Turn transfer switch and voltage source switch to "off". 3. Remove both fuses on front of the control panel so the regulator cannot operate. 4. Close the by-pass switch 1, Fig. (7, 10, 13), thus shunting the regulator. 5. Open disconnect switch 3, Fig. (7, 10, 13), on load side. 6. Open disconnect switch 2, Fig.

10 (7, 10, 13), on source side. CAUTION When removing the regulator from service, never open the neutral disconnect switch until the source discon nect switch has been opened. Failure to observe this rule may cause a high enough voltage to be induced in the windings to damage the insulation. NOTE: Above instructions and those on Page 9 based on using individual switches for source, load and by-pass. If combination type regula or by-pass switch is used, the by-pass switch No. 1, Fig. (7, 10, 13) ls the by-pass element of the combination switch.