Technical DataEffective July 2018 WaveLinx Wireless area ControllerWireless area ControllerOverviewThe Wireless area Controller (WAC) is the main component of the WaveLinx Wireless Controlled Lighting (WCL) system. WaveLinx eliminates the cost and complexity of typical Wireless control system commissioning while providing a flexible and reconfigurable topology for on the fly space adjustments. The WaveLinx system meets modern code and utility requirements, delivers energy and cost savings, while enabling buildings to become smart WAC coordinates between the WaveLinx smart and connected Mobile App and various WaveLinx devices to create communications and a building ecosystem that provides out of the box functionality and leverages Eaton 's patent

Tenial ata ffectie uly 218 WaveLinx Wireless Area Controller Wireless Area Controller Overview The Wireless Area Controller (WAC) is the main component of the

Tags:

  Controller, Area, Wireless, Wireless area controller, Wireless area controller wireless area controller

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of WaveLinx Wireless Area Controller Spec Sheet - Eaton

1 Technical DataEffective July 2018 WaveLinx Wireless area ControllerWireless area ControllerOverviewThe Wireless area Controller (WAC) is the main component of the WaveLinx Wireless Controlled Lighting (WCL) system. WaveLinx eliminates the cost and complexity of typical Wireless control system commissioning while providing a flexible and reconfigurable topology for on the fly space adjustments. The WaveLinx system meets modern code and utility requirements, delivers energy and cost savings, while enabling buildings to become smart WAC coordinates between the WaveLinx smart and connected Mobile App and various WaveLinx devices to create communications and a building ecosystem that provides out of the box functionality and leverages Eaton 's patent pending automatic code commissioning features.

2 Using standard-based Wireless mesh compliant topology the WAC communicates to various WaveLinx standard-based devices to provide area , lighting zone configuration, monitoring, and WAC provides centralized coordination of multiple areas for partial ON/partial OFF scheduling, demand response, lighting, occupancy and daylight settings and scene control. A single WAC can be connected to the building Local area Network (LAN) to coordinate up to 16 areas, or multiple WAC s can exist on a building LAN to scale the system to hundreds of areas all accessible for setup, configuration and control through the WaveLinx Mobile Easily installed on ceiling, wall, shelf, rack, or DIN rail Powered via Power over Ethernet (PoE - IEEE ) Controls up to 200 WaveLinx devices (light fixtures, relay switchpacks, wallstations, sensors, etc.)

3 Supports up to 16 areas with multiple lighting zones, occupancy sets, and daylight sets per area Drag and drop programming of lighting zones and areas via WaveLinx Mobile App Connects to building LAN for access to BMS and OpenADR interfacesCatalog#Prepared byProjectDateCommentsType2 July 2018 WaveLinx Wireless area Controller ArchitectureThis diagram shows the main components of the WaveLinx Wireless Connected Lighting (WCL) system. The WaveLinx system communicates using Wireless mesh technology based on the IEEE standard.

4 A PoE LAN connection for each Wireless area Controller (WAC) is required for power and data access to the building Wireless network. System setup is achieved through a simple mobile application via Wireless communication to the system. Alternately, Wi-Fi can be used to access the building network and a PoE injector can be used to power the or Room(up to 16) area or Room(up to 16) area or Room(up to 16)20A DimmingRelayRoom Based Occupancy SensorControlledReceptacleScene WallstationWireless Controlled Lighting ready devices(up to 200 per WAC)

5 WaveLinx -Integrated AmbientWi-Fi SignalIEEE WaveLinx -Integrated RecessedBuilding LANW ireless AreaController WaveLinx Mobile Appused for system setupand personal controlBuilding WirelessPoE PowerInsight ManagerBACnet/IPPublic (REST) APIT hird Party system (hardware provided by others)Note:Insight Manager Pro shown in this illustration. Insight Manager hardware can be either Pro, Enterprise or ConnectionsPOE 1-/100 BaseTx Cat. 5 RJ45 portPAIR button allows devices to join the networkStatus IndicatorsStatus LED on front of unit LAN connectivity LED WAN connectivity LED Wi-Fi connectivity LED Bluetooth connectivity LED IEEE connectivity LED Eaton logo LED for powerProgrammingSettings and Configuration stored in non-volatile flash memory Up to 200 total WCL devices (for best performance, connect up to 100 devices)

6 Up to 16 areas Up to 6 scenes per area Up to 16 zones per area Up to 6 occupancy sets per area Individual luminaire daylight sets (when using integrated sensors)Operating EnvironmentOperating Temperature Range: 32 F to 104 F (0 C to 40 C)Operating Humidity: 10% to 90% RH (non-condensing)Storage Temperature: 32 F to 104 F (0 C to 40 C)3 July 2018 WaveLinx Wireless area Controller SpecificationsWeights: 115g ( oz) Wireless manager 40g ( oz) ceiling mounting kitColor: GrayDimensions: " W x " H x 1" D ( W x H x D)MountingCeiling, wall or din rail mount optionsSecurityAES 128-bit encryption for Wireless communicationRegulatorycULus Listed - Energy Management Equipment (UL 916)UL Certified - Cybersecurity for Network-Connectable Products (UL 2900) Complies with the following electromagnetic requirements: EN 61000-4-2 EN 61000-4-4 EN 61000-4-5 FCC Part 15/ICES-003 WirelessRadio: : Power: + 7dBmRange: 150ft (50m) LOS# of Walls.

7 3 interior walls standard constructionMax # of Devices: 200 per Wireless area Controller (best practice 100 devices)PAIR button functionalityUsing the PAIR button on the Wireless area Controller allows the addition or removal of Wireless devices to the WaveLinx system, reset building network login information and restore factory button pressDevice outcomeWAC LED feedbackEnter Construction Group1 press1 press Dim to 10% LED blinksLeave Construction Group1 press (after enter Construction group)Raise to 75% LED ONRemove Devices Default AreaPress and hold for 4 secondsDevices in Default area leave WaveLinx networkReset administrator and Wi-Fi UN/PWPress and Hold for 20 secondsWi-Fi LED fast blinkFactory DefaultsPower cycle WACP ress and hold for 30 secondsAll devices and programming cleared from WACAll LEDs fast blink for 1 minuteEaton1121 Highway 74 SouthPeachtree City, GA 30269P: service or technical assistance:1-800-553-3879 2018 EatonAll Rights ReservedPrinted in USAP ublication No.

8 TD503144 ENJuly 2018 Specifications and dimensions subject to change without notice. July 2018 WaveLinx Wireless area Controller OrderingAll WaveLinx Wireless Connected Lighting (WCL) system accessories require at least one Wireless area Controller (WAC) for communications. Ensure the bill of material includes one of the following #DescriptionWAC-POEW ireless area Controller , POE poweredOptional AccessoriesFor connection to 120 VAC #DescriptionWPOE-12010V to PoE Injector