Example: marketing

www.graceconstruction

0087_01 8/9/04 5:48 PM Page 1. 07812/GRA. G R A C E C O N S T R U C T I O N P R O D U C T S BuyLine 0087. 0087_02 8/9/04 5:50 PM Page 2. MONOKOTE FIREPROOFING.. Monokote MK-6 . Standard Density Fireproofing Lille Airport Terminal, Lille, France Petronis Twin Towers, Kuala Lumpur, Malaysia New York-New York Hotel and Casino, Las Vegas, Nevada Trump International Hotel & Tower, New York, New York Monokote MK-6 /HY and MK-6 s Proven, in-place performance on interior structural steel makes these products the most widely used fireproofing in the world. MK-6 /HY and MK-6 s are cost-effective, gypsum-based, cementitious spray applied fireproofing products designed for easy, fast application to steel and concrete substrates. Both products provide maximum flexibility for a wide variety of jobsite conditions. Typical Uses Benefits Interior, concealed applications such as: High bond strength in excess of 200 psf High rise and low rise commercial Resists damage from air erosion and abrasion office buildings Gypsum-based formulation contains no mineral fibers Government buildings No topcoat or surface sealer required Hotels, resorts and casinos Health care facilities Schools and museums Retro-Guard Replacement Fireproofing Retro-Guard is a cementitious replacement fireproofing designed for retrofit spray appli

Underwriters Laboratories Inc. Fire Ratings The following chart details the most common UL designs utilizing Monokote MK-6 fireproofing. For specific design selection assistance, contact your

Tags:

  Fire, Ratings, Graceconstruction, Fire rating

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of www.graceconstruction

1 0087_01 8/9/04 5:48 PM Page 1. 07812/GRA. G R A C E C O N S T R U C T I O N P R O D U C T S BuyLine 0087. 0087_02 8/9/04 5:50 PM Page 2. MONOKOTE FIREPROOFING.. Monokote MK-6 . Standard Density Fireproofing Lille Airport Terminal, Lille, France Petronis Twin Towers, Kuala Lumpur, Malaysia New York-New York Hotel and Casino, Las Vegas, Nevada Trump International Hotel & Tower, New York, New York Monokote MK-6 /HY and MK-6 s Proven, in-place performance on interior structural steel makes these products the most widely used fireproofing in the world. MK-6 /HY and MK-6 s are cost-effective, gypsum-based, cementitious spray applied fireproofing products designed for easy, fast application to steel and concrete substrates. Both products provide maximum flexibility for a wide variety of jobsite conditions. Typical Uses Benefits Interior, concealed applications such as: High bond strength in excess of 200 psf High rise and low rise commercial Resists damage from air erosion and abrasion office buildings Gypsum-based formulation contains no mineral fibers Government buildings No topcoat or surface sealer required Hotels, resorts and casinos Health care facilities Schools and museums Retro-Guard Replacement Fireproofing Retro-Guard is a cementitious replacement fireproofing designed for retrofit spray application to steel and concrete substrates.

2 Its blue signal coat makes it easy to identify re-sprayed areas. Interior, concealed applications include retrofit of commercial office buildings, asbestos abatement and patching and repair of existing fireproofing. 2. 0087_03 8/9/04 5:51 PM Page 3. 07812/GRA. BuyLine 0087. O U R N E W E S T P R O D U C T I N N O VAT I O N. Monokote MK-6 /HY Extended Set Fireproofing TM. Monokote MK-6 /HY Extended SetTM fireproofing is the newest innovation in MK-6/HY technology. It increases applicator productivity and minimizes the impact of fireproofing on the construction schedule. This single component, mill-mixed, cementitious fireproofing plaster has a delayed set feature which allows it to be left unattended in the delivery system for up to 4 days. At the jobsite, water is added to form a consistent, pumpable slurry and Monokote Accelerator is injected to achieve fast set, high production results.

3 MK-6/HY Extended Set is approved for use on structural steel columns, beams, joists, trusses and floors and on roof decking. It is listed in the UL fire Resistance Directory. Feature Benefit Delayed set time (>96 hrs) Allows applicator to significantly reduce or eliminate time consuming pump-in/. pump-out procedure Allows applicator to increase daily productivity rate (bags/day) up to 20%. Allows applicator to reduce waste water disposal and material scrap Allows applicator to complete fireproofing jobs in less time Same in-place performance Durable and fire rating performance UL listed (MK-6/HY). as MK-6/HY Factory inspected to ensure product performance Compliance with UBC, NBC, SBC and IBC Building Codes Superior technical service Provides application training and support and support Provides timely trouble shooting and follow up service Physical Properties and Recommended Specifications Monokote MK-6 and Retro-Guard RG.

4 Physical Recommended Tested Values Test Method Properties Specifications*. Dry Density, 240 kg/m3 (15 pcf) 240 kg/m3 (15 pcf) ASTM E 605/. Minimum Average UBC STD 7-6. Bond Strength KPa (200 psf) KPa (339 psf) ASTM E 736. Compression,10% 57 KPa (1,200 psf) KPa (1,440 psf) ASTM E 761. Deformation Air Erosion Max. g/m2 ( g/ft2) g/m2 ( g/ft2) ASTM E 859. High Velocity Air Erosion No continued air No continued erosion ASTM E 859. erosion after 4 hours after 4 hours Corrosion Does not contribute Does not contribute to ASTM E 937. to corrosion corrosion Bond Impact No cracking, spalling No cracking, spalling ASTM E 760. or delamination or delamination Deflection No cracking, spalling No cracking, spalling ASTM E 759. or delamination or delamination Resistance to Mold Growth No growth after 28 days No growth after 28 days ASTM G 21. Impact Penetration City No more than 6 cm3 abraded cm3 Developed by the City of San Francisco Abrasion Resistance City No more than 15 cm3 cm3 Developed by the abraded City of San Francisco * Monokote MK-6/HY, MK-6/HY Extended Set and MK-6s meet or exceed these performance standards.

5 Visit our web site at 3. 0087_04 8/9/04 5:52 PM Page 4. MONOKOTE FIREPROOFING.. Monokote Z-106 Medium Density Fireproofing Foxwoods Resort & Casino, Ledyard, Connecticut Old Trafford Stadium, Manchester, United Kingdom One Beacon Street, Boston, Massachusetts Monokote Z-146 High Density Fireproofing New York City Hospital, New York, New York Malden Mills Industries, Lawrence, Massachusetts White Oak Semiconductor, Richmond, Virginia 4. 0087_05 8/9/04 5:54 PM Page 5. 07812/GRA. BuyLine 0087. MEDIUM AND HIGH DENSITY FIREPROOFING PRODUCTS. Monokote Z-106 & Z-106/HY. Medium density, cement-based fire protection products provide superior durability for interior, exposed applications. Z-106 was the first generation of Monokote medium density fireproofing products. Monokote Z-106/HY is the next generation: 100% portland cement binder, medium density fireproofing. In addition to the moisture resistance and durability of Z-106, Z-106/HY incorporates application benefits including Grace's patented injection technology for fast set and improved hangability.

6 Specifying both Z-106 and Z-106/HY allows alternatives for providing highly cost effective installation while assuring the specifier of high performance in-place characteristics. Typical Uses Benefits Interior, exposed applications such as: Cement-based formulation provides high High rise commercial office buildings bond strength >1,000 psf Transportation terminals Damage-resistant surface resists air erosion, Convention centers abrasion and impact damage Parking garages Can be trowel finished for improved aesthetics Light manufacturing facilities Withstands traffic, high humidity and condensation Elevator shafts Swimming pool areas Recommended Specifications for High and Medium Density Products*. Z-146** Z-106 and Z-106/HY Test Method Medium Density 640 kg/m (40 pcf). 3. 350 kg/m (22 pcf). 3. ASTM E 605. Minimum Bond Strength 472 kN/m2 (10,000 psf) kN/m2 (2,000 psf) ASTM E 736.

7 Minimum Compressive Strength MPa (550 psi) 476 KPa (70 psi) ASTM E 761. @ 10% Deformation Deflection & No Cracking No Cracking ASTM E 759. Bond Impact or Delamination or Delamination Air Erosion ( ) ( ) ASTM E 859. Resistance to Yes Yes ASTM G 21. Mold Growth Standard Color Gray Gray * Actual laboratory tested values meet or exceed Grace's recommended value. Test reports are available on request from your Grace sales representative. **ASTM test methods modified where required, for high density, high performance products. Monokote Z-146. High density, cement-based fire protection delivers maximum protection for interior or exterior exposed applications. Typical Uses Benefits Interior or exterior exposed applications such as: Cement-based formulation provides extremely high High-tech clean rooms bond strength >10,000 psf Chip fabrication facilities Tough, concrete-like surface resists air erosion and abrasion Transportation terminals Trowel grade Z-146 can be trowel finished for improved aesthetics Heavy manufacturing facilities Releases no particulate matter or volatile organics to interfere Gymnasiums and sports facilities with sensitive computer chip manufacturing environments Elevator shafts and stairwells Suitable for exterior exposure resists freeze/thaw, wind and rain Mechanical rooms 5.

8 0087_06 8/9/04 5:55 PM Page 6. MONOKOTE FIREPROOFING.. CC-CODES, CERTIFICATION. Performance Underwriters Laboratories Inc. fire ratings Monokote meets or exceeds the in-place The following chart details the most common UL designs utilizing Monokote performance requirements and complies MK-6 fireproofing. For specific design selection assistance, contact your with the following specifications. Grace sales representative. General Services Administration (GSA); AIA/SC/GSA: 07811 Restrained Assembly Department of the Navy; Rating (Hr.). UL. NAVFACENGCOM Guide Construction1. 1 11/2 2 3 4 Design No. Specification NFGS-07810B, Sprayed Applied Fireproofing Protected Floor/Ceiling Systems Veterans Administration (VA); H-08-1 Fluted Deck D779. Environmental Protection Agency Electrified Floor Options D739. (EPA); Regulation 40 CFR, Part 61, Unclassified Painted Decking D744. Sub-part M, Section 61:148.

9 Form Deck D780. Department of the Army Army Corps of Engineers Fluted Deck/3-1/4" LW Concrete D782. Guide Specification For Military Unprotected Floor/Ceiling Systems Construction Section 07810. Spray Applied Fireproofing D9255. CEGS-07810 (May 1998). Concrete Systems fire Test Performance Pan-Joist/Poured-In-Place J701. Monokote fireproofing is included in Slab/Poured-In-Place J709, J712. over 120 design listings at Underwriters Precast/Tees J704, J705. Laboratories Inc. (UL). Precast/Hollow Core J706, J919. It has been tested worldwide and has the following global Roof/Ceiling Systems approvals. USA UL 263/ASTM E 119. Japan JIS A 1304. Spain PNE IRMA Roof P714. England BS 476 Part 8 Polystyrene Foam Insulation P732. Canada ULC S101/ASTM E 119 Polyisocyanurate Foam Insulation P732. France ISO 834. Germany DIN 4102 Spray Polyurethane Foam Insulation P733. Korea KSF-2257 Mineral Fiber Board/Fiberglass Roof Insulation P732.

10 Belgium ISO 834. Lightweight Insulating Concrete Roof Deck P9365. Beams/Joists2. Building Codes Beam Only Floor Systems N706. Monokote fireproofing products meet N708, N782. the requirements of the following building code bodies: Joist Only Floor Systems N736. N777. International Building Code Beam Only Roof Systems S735. Southern Building Code Congress International S734. Building Officials and Code Joist Only Roof Systems S728. Administrators, International S736. International Conference of Columns3. Building Officials (Size) (Metric Equivalent). New York City MEA W6 x 9 To (W150 x 13). National Building Code W14 x 730 (W360 x 1086). of Canada W-shaped Steel Column4 Formula X772, Y715. Tube and Pipe Columns X771, Y710. In areas where local codes dictate, contact Concrete Filled Pipe Column X791. your Grace representative for assistance. 1 Refer to the UL Design Listing for concrete type, beam sizes, composite beam, deck profile, trench header, electrical inserts, roof covering type and other construction details.