1 PageGRAFIK SystemsTXP Switching PanelsPower Equipment369345e 1 SUBMITTALJob Name:Job Number:Model Numbers:Mini XP All voltages 4 to 16 switch legsLarge XP 277 V~ and 347 V~ 4 to 28 switch legsExtra-Large XP (not shown) 277 V~ and 347 V~ 32 to 42 switch legsStandard Size XP All voltages 20 to 48 switch legsStandard Size XP 100 to127 V~, 4 to 28 switch legs 220 to 240 V~ (non-CE), 12 to 24 switch legs 230 V~ (CE), 12 to 24 switch legsFeed-Through XP Without Branch Circuit BreakersXP With Branch Circuit BreakersXP Switching Panels work with: GRX-4000 Control Units GRAFIK 5000T, GRAFIK 6000R, and GRAFIK 7000T Systems GP and LP Dimming Panels DMX512 dimming systems via the 2 LinkT option QuantumR systemsXP Switching Panels provide power and Switching for up to 48 switch legs.
2 Panels control any light source as well as AC general use available with: 100 to 127 V~, 220 to 240 V~ (non-CE), 230 V~ (CE), 277 V~, and 347 V~ input power With or without branch circuit breakers 4 to 48 switch legs (feed-through) 4 to 42 switch legs (with branch circuit breakers)XP Switching PanelsMini XP 220 to 240 V~ 4 to 8 switch legs 230 V~ 4 to 8 switch legs PageGRAFIK SystemsTXP Switching PanelsPower Equipment369345e 2 SUBMITTALJob Name:Job Number:Model Numbers:Regulatory Approvals ULR Listed (Reference: UL File 42071) Complies with ISO-9000 CSA, NOM Seismic Certified (Test Method AC156.)
3 Reference OSHPD Preapproval OSP-0215-10).Power Input power: 100 to 127 V~, 220 to 240 V~ (non-CE), 230 V~ (CE), 277 V~, and 347 V~. All voltages 50/60 Hz, phase-to-neutral. Control circuit (Feed-Through XP Panels only): Dedicated feed, same voltage and phase as Panel. Branch Circuit Breakers: ULR rated thermal magnetic. AIC ratings: 120 V~ 10,000 A 220 to 240 V~ 6000 A 277 V~ 18,000 A 347 V~ 14,000 A Lightning strike protection: Meets ANSI/IEEE standard Can withstand voltage surges of up to 6000 V~ and current surges of up to 3000 A. 10-year power failure memory: Automatically restores lighting to levels prior to power Types (relay ratings)Relay RatingLoad Type120 V~230 V~ (CE)220-240 V~277 V~347 V~Tungsten20 A16 A16 A20 A16 AAC General Use20 A16 A16 A20 A16 AElectric Discharge Lamp16 A16 A16 A16 A16 AElectronic Ballast NEMA 41016 AN/AN/A16 AN/AResistive20 A16 A16 A20 A16 AInductive20 A16 A16 A20 A16 HPN/ HPN/ASpecificationsLoad When using the Switching Module to control receptacles, it may be used with, but is not limited to, the following: Monitors Fans Humidifiers Printers Note.
4 Refer to the manufacturer s guidelines for acceptable Switching methods. When using the Switching Module to control receptacles, it may NOT be suitable for use with devices that require any of the following: Shut-down process before power is interrupted, such as computers. Cool-down process before power is interrupted, such as projectors. Programming, such as clocks or DVRs. Long warm-up cycle. Not for use with loads that present a hazard if automatically energized, for example heaters. Any receptacles that are controlled by an automatic control device must be marked with u located on the controlled receptacle outlet where visible after installation as stated in 2014 NECR Article (E).
5 Switching Modules (120, 277, 347 V~) Able to control 20 A receptacles. Switch legs rated at 20 A. Patented SoftswitchR circuit eliminates arcing at mechanical contacts when loads are switched, which prolongs relay life to an average of 1,000,000 cycles at 16 A. 10 BTU / hour per module. Panel TypeVoltageStd. SCCR RatingXP Feed-through (all sizes)120/277 V~25,000 AXP Main Lug Panels (all sizes)120/277 V~25,000 AShort Circuit Current Ratings (other ratings available) PageGRAFIK SystemsTXP Switching PanelsPower Equipment369345e 3 SUBMITTALJob Name:Job Number:Model Numbers:Specifications (continued)Wiring Internal: Prewired by Lutron .
6 System communications: Low-Voltage IEC PELV/NECR Class 2 wiring connects XP Panels to other components. Line (mains) voltage: Feed and load wiring only. (Feed-Through XP Panels also have control circuit wiring.) No other wiring or assembly Design Enclosure: NEMA-Type 1, IP-20 protection; 16 gauge steel. Indoor use only. Weight: 27 lb (13 kg) for Mini XP, 80 lb (37 kg) for Standard Size XP, 135 lb ( kg) for Large XP, 225 lb (102 kg) for Extra Large XP. Seismic Certification Limits: SDS = g, z/h = , IP = Contact LutronR for details. Mounting Mini XP and Standard Size XP: Surface mount or recess mount between 16 in (40 cm) studs.
7 Large XP: Surface mount only. Extra Large XP: Surface mount only. Environment 32 to 104 F (0 to 40 C). Relative humidity less than 90% non-condensing. PageGRAFIK SystemsTXP Switching PanelsPower Equipment369345e 4 SUBMITTALJob Name:Job Number:Model Numbers:How to Build an XP Model NumberX P 1 2 - 1 2 0 4 M L - 1 5 - C G P - _ _ _Prefix:XP Switching PanelNumber of Switch Legs:Indicates number of load circuits in the panelVoltage:Omit for feed-through120 (100 to 127 V~)230 (230 V~) CE1240 (220 to 240 V~) non-CE1277 (277 V~)347 (347 V~)Feed Type:FT (Feed-Through no branch circuit breakers)4 (3 phase 4 wire)Panel Feed:ML (Main Lugs only)IS (Isolation Switch)Branch Circuit Breakers.
8 20 (20 A branch circuit breakers)15 (15 A branch circuit breakers)16 (16 A branch circuit breakers)Custom Panel Suffix:Indicates panel with special LutronR for specific 230 V~ (CE) and 220 to 240 V~ (non-CE) models with branch circuit breakers are custom Panels . Contact Lutron for more of Switch LegsVoltageFeed TypePanel FeedBranch Circuit BreakersCustom Panel Suffix PageGRAFIK SystemsTXP Switching PanelsPower Equipment369345e 5 SUBMITTALJob Name:Job Number:Model Numbers:Mini XPStandard Size XPMini XP Feed-Through Models 120/277 V~, 230 V~ (CE), 220 to 240 V~ (non-CE), or 347 V~ PowerModel PrefixSwitch LegsFeed TypeMaximum FeedXP44 Feed- Through120/277 V~ 20 A220 to 240 V~ 16 A230 V~ (CE) 16 A347 V~ 20 AXP88XP1212XP1616 Model PrefixSwitch LegsFeed TypeMaximum FeedXP2020 Feed- Through120/277 V~ 20 A220 to 240 V~ 16 A230 V~ (CE) 16 A347 V~ 20 AXP2424XP2828XP3232XP3636XP4040XP4444XP4 848 Standard Size XP Feed-Through Models 120/277 V~, 230 V~ (CE), 220 to 240 V~ (non-CE), or 347 V~ PowerWire Sizes 14 to 10 AWG ( to mm() for Feed Wiring and Switch Legs (to loads))
9 Power (Line/Hot) and Switched Line/Hot connect directly to Terminal Block for Switch LegsFeed-Through XP Models (Without Branch Circuit Breakers)Only standard Panels listed. Consult LutronR for options. PageGRAFIK SystemsTXP Switching PanelsPower Equipment369345e 6 SUBMITTALJob Name:Job Number:Model Numbers:Standard Size XP1 20/16 A, 15/12 A continuous load Models With Branch Circuit BreakersOnly standard Panels listed. Consult LutronR for PrefixSwitch LegsFeed Type and Wire SizeMaximum FeedBranch Circuit Breakers1XP443 4 WMain Lugs OnlyMain Lugs accept 4 AWG (25 mm2) to 250 kcmil (mcm) (120 mm2)200 A15 A or 20 AXP88XP1212XP1616XP2020XP2424XP2828 Model PrefixSwitch LegsFeed Type and Wire SizeMaximum FeedBranch Circuit Breakers1XP443 4 W125 A Isolator SwitchIsolator Switch accepts 14 AWG to 2 AWG ( mm2 to 35 mm2)
10 Feed Wiring125 A16 AXP88 Model PrefixSwitch LegsFeed Type and Wire SizeMaximum FeedBranch Circuit Breakers1XP12123 4 W125 A Isolator SwitchIIsolator Switch accepts 14 AWG to 2 AWG ( mm2 to 35 mm2) Feed Wiring125 A16 AXP1616XP2020XP2424100 to 127 V~ Standard Size XP with Branch Circuit Breakers220 to 240 V~ (non CE) Mini Size XP with Branch Circuit Breakers230 V~ (CE) Standard Size XP with Branch Circuit BreakersMini XPModel PrefixSwitch LegsFeed Type and Wire SizeMaximum FeedBranch Circuit Breakers1XP12123 4 W125 A Isolator SwitchIsolator Switch accepts 14 AWG to 2 AWG ( mm2 to 35 mm2) Feed Wiring125 A16 AXP1616XP2020XP2424220 to 240 V~ (non CE) Standard Size XP with Branch Circuit BreakersModel PrefixSwitch LegsFeed Type and Wire SizeMaximum FeedBranch Circuit Breakers1XP443 4 W125 A Isolator SwitchIsolator Switch accepts 14 AWG to 2 AWG ( mm2 to 35 mm2) Feed Wiring125 A16 AXP88230 V~ (CE) Mini Size XP with Branch Circuit Breakers PageGRAFIK SystemsTXP Switching PanelsPower Equipment369345e 7 SUBMITTALJob Name:Job Number:Model Numbers.