Total System - MSHS Group
Product Specification 03371 (Rev. C) ProTech TPS . Total Protection System IEC61508 SIL-3. (Safety PLC with Integrated Overspeed Protection) Certified API670 & API612. Compliant Description Overspeed The ProTechTPS is a protection safety PLC (programmable logic controller) with Acceleration &. integrated overspeed deceleration protection designed to safely shut down any plant protection process equipment, engine, or steam, gas, or User- hydro turbine upon programmable sensing a safety event. logic This stand-alone safety device accepts 10 discrete o 10 inputs or analog inputs per o Discrete or module (30 Total ) and one analog speed (MPU or PROX). input (3 Total ), uses custom-programmed logic to determine when a true safety event has o Trip/alarm logic occurred, then issues a shutdown command to safely shut down the equipment or turbine. o Test logic The ProTechTPS utilizes a triple modular redundant architecture and 2-out-of-3 voting logic to 2-out-of-3 voting accurately determine unsafe conditions and ensure that no single-point failure will affect System reliability or availability.
Woodward 03371 p.2 Alternatively, this stand-alone safety device can be configured to protect any plant system or device, and report the system’s/
Download Total System - MSHS Group
Information
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
Related search queries
VOLVO PENTA INBOARD DIESEL KAMD43P, JEDEC Publication, Models, Reliability, OneTechnologyWay P.O.Box9106 Norwood, In reliability, Models APM and APH, Greenheck, ACCELERATION FACTORS AND THERMAL, Acceleration factors and thermal cycling test efficiency for, Hyundai Inverter, By Scott Speaks Vicor Reliability