PDF4PRO ⚡AMP

Modern search engine that looking for books and documents around the web

Example: dental hygienist

CHAPTER 21 MASONRY - iccsafe.org

CHAPTER 21 MASONRY SECTION 2101 GENERAL Scope The provisions of this CHAPTER shall govern the materials, design , construction and quality of MASONRY . Exception: Buildings and structures located within the High Velocity Hurricane Zone shall comply with the provisions of 2116 and 2118 through 2122. MASONRY shall comply with or Construction documents. Drawings and details shall show all the items required to be shown on the drawings by this code including the following: 1. Specified size, grade, type and location of reinforce-ment, anchors and wall ties. 2. Reinforcing bars to be welded and welding procedure. 3. Size and location of all structural elements. 4. Provision for dimensional changes resulting from elas-tic deformation, creep, shrinkage, temperature and moisture. Support Lintels. MASONRY directly above chases or recesses wider than 12 inches (305 mm) shall be support-ed on lintels.

CHAPTER 21 MASONRY SECTION 2101 GENERAL 2101.1 Scope 2101.1.1 The provisions of this chapter shall govern the materials, design, construction and quality of masonry. Exception: Buildings and structures located within the High Velocity Hurricane Zone shall comply with the

Loading..

Tags:

  Design, Chapter, Masonry, Iccsafe, Chapter 21 masonry

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Spam in document Broken preview Other abuse

Transcription of CHAPTER 21 MASONRY - iccsafe.org

Related search queries