CompressionConnectorSystemStep OnePreparing the CableWire Stripper shown is Part No. the insulation to the proper length sothat conductors can be fully inserted into theconnector Length Too LongStrip Length Too ShortStrip Length Just RightStrip the insulation carefully to avoid nickingor cutting conductors (wire brush if required).StrandsCutNickedStrandsGoodStr ip33 Step TwoDetermining the Proper ConnectorDetermine the proper Color-Keyed Connectorfor the cable size being used. connectors marked with just cable size or CUshould be used on copper conductors only. connectors marked AL9 *with the cable sizeshould be used on aluminum conductors only. connectors marked AL9CU with the cablesize may be used on the aluminum orcopper conductors.* Aluminum lugs with a 9 indicate 90oC are marked to show cable SizeStep ThreeChoosing Tool and Proper DieBattpac Tool TBM62 BSCR the proper installingdie and appropriate connectors have colored bandsor colored dots that correspond tocolor markings on the and dies also have a diecode number marked or stamped onthem.
Compression Connector System. Step One Preparing the Cable ... Main Branch 1 Branch 2 Branch 3 H-Tap Color Die Tool # Of Crimps Die Embossing Strip Length Insulating Cover 8-14 (8-14) 8-14 (8-14) - - CHT814-10 Green 15CA37RCH* Group 1 1 37R 1/2" HTC2S ... Tool and Die Chart for Standard C-Taps