CONSULTANT PROCEDURES & DESIGN GUIDELINES UNIVERSITY OF MISSOURI 232200 Steam and Condensate Piping and Pump Systems Revised 12/20/2013 Page 1 of 7 232100 General : Steam and condensate piping and pump systems included in this document are for building systems starting at the pressure reducing station (PRV). DESIGN GUIDELINES: A. DESIGN General 1. Definitions: Low pressure steam is 15 psig or less. High pressure steam is above 15 psig. 2. Campus Systems: MU: The steam distribution system operates at 60 psig and 400 F degrees. All equipment using campus steam must be capable of using steam at a temperature of 350F degrees.
hardened stainless steel head and seat; balanced pressure thermostatic air vent made of stainless steel or monel bellows with stainless steel head and seat. b) Inverted Bucket Trap: ASTM A126, cast iron body with stainless steel inverted bucket and internals. Provide a bi-metal air vent and strainer screen. 4. Pressure Power Pump (MU Only)