SHORT CIRCUIT CURRENT RATINGSHow to Determine and Increase SHORT CIRCUIT CURRENT RATINGS for Industrial Control PanelsWHITE PAPER2 2019 Littelfuse, to Determine and Increase SHORT - CIRCUIT CURRENT RATINGS for Industrial Control PanelsIntroductionA SHORT - CIRCUIT CURRENT rating (SCCR)1 is the maximum CURRENT a device or system can safely withstand for a specified time (such as seconds), or until a specified fuse or CIRCUIT breaker opens and clears the CIRCUIT . SCCR is usually expressed in kiloamperes (kA). SCCR labeling requirements create a safe installation and help manufacturers, owners and managers meet OSHA regulations and NFPA codes and standards. Both the NEC and OSHA forbid equipment from being located near any point where the available SHORT - CIRCUIT CURRENT is more than what the equipment can withstand. Available fault currents are increasing in industrial facilities due to a continuously increasing demand for electric power.
Arcing energy (l2t) Maximum peak-let through current with noncurrent-limiting fuses. (Peak value can be as high as 2.3 times the available rms fault current.) Melting energy (l2t) Melting time Arcing time Fuse total clearing time (less than ½ a cycle)