Sizing and PlacementAs shown above, it has been established that the preferred locationfor the Water hammer arrestor is at the end of the Branch line betweenthe last two fixtures location of the Water hammer arrestor shown above applies tobranch lines that do not exceed 20 feet in length, from the start of thehorizontal Branch line to the last fixture supply on this Branch the Branch line exceeds the 20 foot length, an additional waterhammer arrestor should be used. This practice is best defined by tworules which have been established to cover the placement of waterhammer Hammer ArrestorTypical Branch LineRiserRule 1covers multiple fixture Branch lines which do not exceed20 feet -Fixture unit sizing and selection table is used toselect the required PDI unit ( Water hammer arrestor).Rule 2covers multiple fixture Branch lines which exceed 20 feetin -Fixture unit sizing and selection table is used toselect the required PDI unit ( Water hammer arrestor).
Sizing and Placement As shown above, it has been established that the preferred location for the water hammer arrestor is at the end of the branch line between
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Line, Branch, Design Information Designing Your Dust Collection, Surge Protective Device, Installation of Pressure-Relieving Devices in Refineries, Flower Parts, Virginia Department of Education, Unbalanced Voltages and Electric Motors: Causes, SMARTSPOT INDICATOR AMP-TRAP, Structual Design of Utility Distribution Poles