ADD - ON COILSFOR USE WITH SPLIT-SYSTEMCOOLING & HEAT PUMPSMODELS: CF, CM, CU600 - 2000 CFM - 5 TON COILSDue to continuous product improvement, specifications are subject to change without us on the web and rating information can be found CASEDCFFULL CASEDMULTI-POSITIONCMUPFLOWUNCASEDCUA036 8-001 ISO 9001 Certified QualityManagement System5005744-BTG-C-0815 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALETECHNICALGUIDE TECHNICALGUIDE DESCRIPTIONT hese indoor coils are designed to be installed with UPGfurnaces or modular air handlers and matched with UPGcooling and heat pump outdoor units. All coil models areavailable as flex-coil units without a factory installed meteringdevice. Flex-coil models allow These coils to be used with R-410A or R-22 for added flexibility to meet refrigerant systemchoice. A piston or TXV metering device should be installed inthe field to meet your system Models, Full Case coils - Full cased coils are suitable foruse in upflow or downflow Models, Multi-Position coils - CM coils have the addedflexibility that allow them to be installed in any position - upflow,downflow, or horizontal (right or left).

5005744-BTG-C-0815 4 Johnson Controls Unitary Products DIMENSIONS CU Models Dimensions 1 1. All dimensions are in inches. Refrigerant Connections 2,3,4 2. Refrigerant line sizes may require larger lines for extended line lengths.

Tags:

  Model, Sheet, Control, Indoor, Technical, Descriptions, Coils, Johnson, Johnson controls, Technical description these indoor coils

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of TECHNICAL DESCRIPTION These indoor coils are …

1 ADD - ON COILSFOR USE WITH SPLIT-SYSTEMCOOLING & HEAT PUMPSMODELS: CF, CM, CU600 - 2000 CFM - 5 TON COILSDue to continuous product improvement, specifications are subject to change without us on the web and rating information can be found CASEDCFFULL CASEDMULTI-POSITIONCMUPFLOWUNCASEDCUA036 8-001 ISO 9001 Certified QualityManagement System5005744-BTG-C-0815 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALETECHNICALGUIDE TECHNICALGUIDE DESCRIPTIONT hese indoor coils are designed to be installed with UPGfurnaces or modular air handlers and matched with UPGcooling and heat pump outdoor units. All coil models areavailable as flex-coil units without a factory installed meteringdevice. Flex-coil models allow These coils to be used with R-410A or R-22 for added flexibility to meet refrigerant systemchoice. A piston or TXV metering device should be installed inthe field to meet your system Models, Full Case coils - Full cased coils are suitable foruse in upflow or downflow Models, Multi-Position coils - CM coils have the addedflexibility that allow them to be installed in any position - upflow,downflow, or horizontal (right or left).

2 This coil can be easilyinstalled with a UPG furnace or modular air handler in Models, Uncased coils - These coils are designed forinstallation on top of upflow furnaces, and they are to be usedfor upflow only applications. The uncased coils require fieldmodification of the furnace duct for the coil installation. FEATURESRC2 - Rigid Case Construction interior endoskeleton forstructural support, flush side, and locks in insulation. Powder-painted - G30 galvanized steel case provide a coatededge that resists corrosion and rust creep. MaxAlloyTM Coil - Long life aluminum coils built to deliverlasting performance, efficiency and reliability. Quality Construction - Structural components are made ofAluminum or G90 galvanized steel to prevent corrosion. Improved Insulation Design - Single piece with no externalscrews to reduce thermal transmission paths to preventsweating. Foil faced insulation for ease of Expansion Valve - Bolt-on TXV provides easyinstallation to convert the indoor coil to the required refrigerantthat does not require brazing to replace or install.

3 Some modelsare available with factory installed TXVs. Case Depth - These models have casing which provideease of attic access and tight applications. Thermoset Drain Pan - Positive slope for drainage to reducecause for potential mold or to Price Manual for specific model Kits - Thermal expansion valve kits are available for flex-coil applications with R-410A refrigerant. All TXV kits are non-braze. All connections are bolt-on including the valve assemblyand equalizer tube. No orifice or any other metering device is tobe used in conjunction with the Case Available to be used with CU coils in four option is intended for upflow applications where heightlimitations in the application prevent the installation of full casedcoils. The partial case design allows the top section of theindoor coil to be installed in the duct or plenum. Coil Casing Without Coil - Coil casings are available in fourwidths that can be installed with the furnace or modular airhandler during initial installation.

4 This option is available to allowthe installer the flexibility to add the coil at a later date withoutduct Germicidal Light - The UVC technology effectivelyprevents mold, bacteria, and other microorganisms thatdevelop in air handling systems. The UVC Light Kit providessafe, continuous cleaning while actually saving money byreducing HVAC system maintenance and energy Controls Unitary ProductsLIST OF SECTIONSDESCRIPTION .. 1 FEATURES .. 1 ACCESSORIES .. 1 NOMENCLATURE .. 2 DIMENSIONS CF .. 3 DIMENSIONS CM .. 3 DIMENSIONS CU .. 4 COOLING CAPACITY - UPFLOW N TYPE COIL (COIL ONLY) .. 4 COOLING CAPACITY - FULL-CASED N TYPE MULTI-POSITION COIL (COIL ONLY) .. 6 COOLING CAPACITY - UNCASED UPFLOW N TYPE COIL (COIL ONLY) .. 7 APPLICATION FACTOR-RATED CFM VS. ACTUAL CFM .. 8 APPLICATION LIMITATIONS .. 8 STATIC PRESSURE VS. AIRFLOW BASED ON WET COIL - UPFLOW CASED N TYPE COIL .. 9 STATIC PRESSURE VS. AIRFLOW BASED ON WET COIL - CASED N TYPE MULTI-POSITION COIL.

5 9 STATIC PRESSURE VS. AIRFLOW BASED ON WET COIL - UNCASED UPFLOW - N TYPE COIL .. 10 COIL TECHNICAL DATA - CASED UPFLOW/DOWNFLOW .. 11 COIL TECHNICAL DATA - FULL CASED N TYPE MULTI-POSITION .. 11 COIL TECHNICAL DATA - UNCASED UPFLOW - N TYPE .. 12 UPFLOW N TYPE COIL - AIR FLOW DATA (CFM) .. 12 MULTIPOSITION N TYPE COIL - AIR FLOW DATA (CFM) .. 13 UNCASED UPFLOW N TYPE COIL - AIR FLOW DATA (CFM) .. 13 NOMENCLATUREPRODUCT TYPECC = Fan CoilPOSITIONMOTOR TYPEFM = Multi-Poise CasedF = Full Case, Up/DnH = Horizontal CasedD = Horizontal DuctU = UncasedNOMINALUNIT CAPACITY3618 = Ton42 = Ton24 = 2 Ton48 = 4 Ton30 = Ton60 = 5 Ton36 = 3 TonCABINET WIDTHBA = "B = "C = "D = "TXV INDICATORXBA-BF = Valve SizeX = no valveCOIL TYPEAA = Aluminum TubesC = Copper TubeGENERATION(MAJOR REVISION)11 = 1st Gen2 = 2nd LETTER(MINOR REVISION)NOT USED FOR ORDERINGAA = Style AB = Style Controls Unitary Products3 DIMENSIONS CFModels1 Dimensions 2 Refrigerant Connections 3,4,5 HeightWidthOpening WidthsLine SizeABCDL iquidVaporCF18A*A119-1/214-1/213-1/213-1 /2 3/8 3/4CF18 BXA11917-1/216-1/216-1/2CF24A*A119-1/214 -1/213-1/213-1/2CF24 BXA11917-1/216-1/216-1/2CF24 CXA121212020CF30 AXA121-5/814-1/213-1/213-1/2CF30B*A12317 -1/216-1/216-1/2CF30 CXA121212020CF30 DXA12524/1/223-1/223-1/2CF36 AXA125-1/214-1/213-1/213-1/2CF36B*A125-5 /817-1/216-1/216-1/2CF36 CXA123212020CF36 DXA12524-1/223-1/223-1/2CF42 BXA12517-1/216-1/216-1/27/8CF42C*A125212 020CF42 DXA12524-1/223-1/223-1/2CF48C*A127212020 CF48 DXA12724-1/223-1/223-1/2CF60C*A133212020 CF60 DXA132-3/424-1/223-1/223-1/2CF64 DXA132-3/424-1/223-1/223-1/21.

6 Asterisk (*) denotes coil model is available as a flex coil or with factory installed All dimensions are in Refrigerant line sizes may require larger lines for extended line lengths. See Application Data part number Adapter fitting must be field installed for other line set See outdoor unit TECHNICAL guide for proper line set CMModels1 Dimensions 2 Refrigerant Connections3,4,5 HeightWidthOpening WidthsLine SizeABCDL iquidVaporCM18A*A119-1/214-1/213-1/213-1 /2 3/8 3/4CM18 BXA11917-1/216-1/216-1/2CM24A*A119-1/214 -1/213-1/213-1/2CM24B*A11917-1/216-1/216 -1/2CM24 CXA121212020CM30A*A125-1/214-1/213-1/213 -1/2CM30B*A12317-1/216-1/216-1/2CM30 CXA123212020CM30 DXA12524/1/223-1/223-1/2CM36 AXA125-1/214-1/213-1/213-1/2CM36B*A125-5 /817-1/216-1/216-1/2CM36C*A125212020CM36 DXA12524-1/223-1/223-1/2CM42C*A127212020 7/8CM42 DXA12724-1/223-1/223-1/2CM48C*A133212020 CM48D*A132-3/424-1/223-1/223-1/2CM60C*A1 33212020CM60D*A132-3/424-1/223-1/223-1/2 CM64 DXA132-3/424-1/223-1/223-1/21.

7 Asterisk (*) denotes coil model is available as a flex coil or with factory installed All dimensions are in Refrigerant line sizes may require larger lines for extended line lengths. See Application Data part number Adapter fitting must be field installed for other line set See outdoor unit TECHNICAL guide for proper line set (OPENING)C (OPENING)19-1/8"D (OPENING)21-1/2 A0322-001 BOTTOM OPENINGDIMENSIONS20-1/2 BAB19-1/8 (OPENING)C(OPENING)19-1/8"D (OPENING)A0323-001 BOTTOM OPENINGDIMENSIONS20-1/2 21-1/2 5005744-BTG-C-08154 johnson Controls Unitary ProductsDIMENSIONS CUModelsDimensions 11. All dimensions are in Connections 2,3,42. Refrigerant line sizes may require larger lines for extended line lengths. See Application Data part number Adapter fitting must be field installed for other line set See outdoor unit TECHNICAL guide for proper line set SizeABLiquidVaporCU18 AXA1 13-3/813-3/8 3/8 3/4CU18 BXA1 13-1/416-3/8CU24 AXA1 15-3/813-3/8CU24 BXA1 15-1/416-3/8CU24 CXA1 14-7/819-7/8CU30 AXA1 19-3/813-3/8CU30 BXA1 19-1/216-3/8CU30 CXA1 19-1/419-7/8CU30 DXA1 1923-3/8CU36 BXA1 21-1/216-3/8CU36 CXA1 21-1/819-7/8CU36 DXA1 21-1/423-3/8CU42 CXA1 23-1/819-7/87/8CU42 DXA1 22-7/823-3/8CU48 CXA1 25-1/819-7/8CU48 DXA1 2523-3/8CU60 CXA1 29-1/419-7/8CU60 DXA1 2923-3/8 COOLING CAPACITY - UPFLOW N TYPE COIL (COIL ONLY1) ModelsRated CFME ntering AirDry/Wet Bulb ( F)MBH@ Evap.

8 Temp. and Corresponding R-410A Pressure ( F/PSIG)35 60085 notes see Page 5005744-BTG-C-0815 johnson Controls Unitary Products5CF30C100085 120085 120085 120085 120085 - See Condensing Unit or Heat Pump TECHNICAL Guide for Total Cooling Capacity and Sensible CAPACITY - UPFLOW N TYPE COIL (COIL ONLY1) (Continued)ModelsRated CFME ntering AirDry/Wet Bulb ( F)MBH@ Evap. Temp. and Corresponding R-410A Pressure ( F/PSIG)35 Controls Unitary ProductsCOOLING CAPACITY - FULL-CASED N TYPE MULTI-POSITION COIL (COIL ONLY1) model CoilRated CFME ntering Air F (Dry/Wet Bulb)MBH@ Evaporator Temperature and Corresponding Pressure F / PSIG35 / / / / notes see Page Controls Unitary Products7CM42D140085 See Condensing Unit or Heat Pump TECHNICAL Guide for Total Cooling Capacity and Sensible CAPACITY - FULL-CASED N TYPE MULTI-POSITION COIL (COIL ONLY1) (Continued) model CoilRated CFME ntering Air F (Dry/Wet Bulb)MBH@ Evaporator Temperature and Corresponding Pressure F / PSIG35 / / / / CAPACITY - UNCASED UPFLOW N TYPE COIL (COIL ONLY1) ModelsRated CFM2 Entering AirDry/Wet Bulb ( F)MBH@ Evap.

9 Temp. and Corresponding R-410A Pressure ( F/PSIG)35 notes see Page Controls Unitary Products*Do not exceed minimum/maximum CFM limits shown under Air Flow LIMITATIONST hese units must be installed in accordance with all nationaland local safety flow must be within the minimum and maximum limitsapproved for electric heat, evaporator coils and outdoor See Condensing Unit or Heat Pump TECHNICAL Guide for Total Cooling Capacity and Sensible CAPACITY - UNCASED UPFLOW N TYPE COIL (COIL ONLY1) (Continued)ModelsRated CFM2 Entering AirDry/Wet Bulb ( F)MBH@ Evap. Temp. and Corresponding R-410A Pressure ( F/PSIG)35 FACTOR-RATED CFM VS. ACTUAL CFM% Of Rated Air Flow (CFM)*80%90%100%110% 120%Capacity Controls Unitary Products9 STATIC PRESSURE VS. AIRFLOW BASED ON WET COIL - UPFLOW CASED N TYPE COIL ModelAirflowWet CoilCF18A PRESSURE VS. AIRFLOW BASED ON WET COIL - CASED N TYPE MULTI-POSITION COIL ModelAirflowWet CoilCM18A PRESSURE VS.

10 AIRFLOW BASED ON WET COIL - UPFLOW CASED N TYPE COIL (Continued)ModelAirflowWet Coil5005744-BTG-C-081510 johnson Controls Unitary PRESSURE VS. AIRFLOW BASED ON WET COIL - UNCASED UPFLOW - N TYPE COIL ModelAirflowWet PRESSURE VS. AIRFLOW BASED ON WET COIL - CASED N TYPE MULTI-POSITION COIL (Continued)ModelAirflowWet PRESSURE VS. AIRFLOW BASED ON WET COIL - UNCASED UPFLOW - N TYPE COIL (Continued)ModelAirflowWet Coil5005744-BTG-C-0815 johnson Controls Unitary Products11 COIL TECHNICAL DATA1 - CASED UPFLOW/DOWNFLOW (Sq. Ft.)RowsDeepFin Per Weight (lbs)Installed Weight (lbs)CF18 ACooling/Heat (3) 12 x x 3/8 Sine (3) 12 x (3) 14 x (3) 14 x (3) 14 x (3) 18 x (3) 18 x (3) 18 x (3) 18 x (3) 20 x (3) 20 x (3) 20 x (3) 20 x (3) 22 x (3) 22 x (3) 22 x (3) 24 x (3) 24 x (3) 28 x (3) 28 x (3) 28 x Refer to the matching outdoor unit TECHNICAL Guide for correct TECHNICAL DATA1 - FULL CASED N TYPE (Sq. Ft.)RowsDeepFinPer Weight (lbs)Installed Weight (lbs)CM18 ACooling /Heat (3) 12 x x (3) 12 x (3) 14 x (3) 14 x (3) 14 x (3) 18 x (3) 18 x (3) 18 x (3) 18 x (3) 20 x (3) 20 x (3) 20 x (3) 20 x (3) 22 x (3) 22 x (3) 24 x (3) 24 x (3) 28 x (3) 28 x (3) 28 x Refer to the matching outdoor unit TECHNICAL Guide for correct : CM coils supplied with a factory installed horizontal drain pan (H)5005744-BTG-C-081512 johnson Controls Unitary ProductsCOIL TECHNICAL DATA1 - UNCASED UPFLOW - N TYPEM odelsApplicationRefrig.