IV. Fire Resistance - Aercon AAC

IV. fire ResistanceA. GeneralPageIV-2B. fire Rated Wall SystemsPageIV-4C. fire Rated Floor and Roof SystemsPageIV-8D. fire Rated Joint SystemsPageIV-10E. fire Rated Through-Penetration SystemsPageIV-11 Unaffected by the industrial fire that destroyed an adjacent wing, a surviving roof serves as a platform for firemen fighting the blaze. The aerated concrete demising wall protected the remaining portion of the building, enabling it to maintain its structural products are non-combustible. So in the case offire, Aercon will help preventthe spread of the fire to otherrooms. When exposed to afire, no toxic gases or vaporsare emitted from systems such as inte-rior and exterior walls, andfloor and roof panels providetremendous fire rated assem-blies in all types of and multifamily;townhouses; commercial, pub-lic and industrial buildings allbenefit from the extraordinaryfire ratings provided by Aercon products.

IV. Fire Resistance A. GeneralPage IV-2 B. Fire Rated Wall Systems Page IV-4 C. Fire Rated Floor and Roof Systems Page IV-8 D. Fire Rated Joint Systems Page IV-10

Tags:

  Resistance, Fire, Fire resistance

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of IV. Fire Resistance - Aercon AAC

1 IV. fire ResistanceA. GeneralPageIV-2B. fire Rated Wall SystemsPageIV-4C. fire Rated Floor and Roof SystemsPageIV-8D. fire Rated Joint SystemsPageIV-10E. fire Rated Through-Penetration SystemsPageIV-11 Unaffected by the industrial fire that destroyed an adjacent wing, a surviving roof serves as a platform for firemen fighting the blaze. The aerated concrete demising wall protected the remaining portion of the building, enabling it to maintain its structural products are non-combustible. So in the case offire, Aercon will help preventthe spread of the fire to otherrooms. When exposed to afire, no toxic gases or vaporsare emitted from systems such as inte-rior and exterior walls, andfloor and roof panels providetremendous fire rated assem-blies in all types of and multifamily;townhouses; commercial, pub-lic and industrial buildings allbenefit from the extraordinaryfire ratings provided by Aercon products.

2 A uniqueproperty of Aercon is that itcontains water in crystallineform, which acts as a heat sink,absorbing heat and changinginto steam. Aercon s porousstructure allows this steam toescape without causing surfacespalling. The following sections describethe numerous and diverse sys-tems which can be used in firerated applications to providesuperb systems can be con-structed using blocks, panelsor a combination of these are solid elementswith very simple connectiondetails, the ease of construc-tion helps to ensure a mono-lithic, highly the specific details andrequirements of each systemthat is available, please see thereferenced document. (Accessto the UL references is current-ly available through their website at From theirhome page, select Certifications and search bycompany name: Aercon .)

3 A. GeneralIV - fire Resistance06/03 / IV-206/03 / IV-3IV - fire ResistanceWalls, Floors and Roof SystemsFireResistanceMin Thk ofType of ElementRatingAERCONR eferenceBlock Wall - LoadBearing4 hr6" NominalUL U919 Block Wall -Non-load Bearing4 hr4" NominalUL U919 Block Wall -Non-load Bearing2 hr3" NominalUL U919 Wall Panel - LoadBearing4 hr6" NominalUL U920 Wall Panel -Non-load Bearing4 hr6" NominalUL U920 Wall Panel - T&GNon-load Bearing4 hr8" NominalUL U920 Wall Partition -Non-load Bearing3 hr4" NominalASTM E 119 Floor & RoofPanels4 hr6" NominalUL K909 &P932 Attached to Non-load Bearing Studs2, 3, 4 hrSee GraphicsAttached to LoadBearing Studs1, 1-1/2, 2 hrSee GraphicsSteel ColumnProtection4 hr4" Block or8" PanelUL X901 Through-Penetration SystemsF RatingT RatingUL NumberSingle Commodity40C-BJ-1037 Two Commodities40W-J-8009 MultipleCommodities30C-BJ-8010 Joint SystemsRatingUL System NumberFloor-to-3 hrFF-D-0018 & FF-D-0020 Floor2 hrFF-D-0017 Joint1 1/2 hrFF-D-0019 Floor-to-3 hrFW-D-0013 & FW-D-0015 Wall2 hrFW-D-0012 Joint1 1/2 hrFW-D-0014 Head ofWall Joint3 hrHW-D-0166 & HW-D-0177 Wall-to-Wall Joint3 hrWW-D-0023 & WW-D-0024 Due to their exceptional perfor-mance when exposed to fire , Aercon products are the idealsolution for a multitude ofsuperstructures and interiorspaces that require a fire rat-ing.

4 Whether it s blocks orpanels, Aercon can be usedas fire separation wallsbetween townhouses, condo-miniums, apartments and other multifamily is also appropriate forhotels, motels, dormitories,assisted-living facilities, hospi-tals, prisons, jails, detentioncenters, schools, movie the-atres, exit corridors, shaftwalls, and stairwell uses include electri-cal rooms, mechanical rooms,computer rooms, communica-tions equipment rooms, flam-mable materials storage, docu-ment storage, warehouses,laundry rooms, boiler rooms,maintenance shops, emer-gency generator rooms, pro-duction control rooms, sprin-kler control rooms and inciner-ator products can be usedas the primary load resistingstructural system in addition tobeing used as cladding toincrease the fire rating of studwalls and to protect othermaterials such as bearing or non-load bear-ing; interior or exterior; single-story or multi-story; if you havea fire hazard, Aercon can pro-vide a system to contain it.

5 UseAERCON to restrict a fire fromspreading or to protect valu-ables from an external safety is an issue, Aercon takes the fire Rated Wall SystemsIV - fire Resistance06/03 / IV-406/03 / IV-5IV - fire ResistanceIV - fire Resistance06/03 / IV-64" or 6" MIN x 8"x24"SOLID BLOCK 6" MIN FOR LOAD BEARING WALL 4" MIN FOR NON-LOAD BEARING WALL0500100015002000250001234 Temperature FHoursFurnace TemperatureAverage Unexposed Surface TemperatureAERCON Block Wall - 4 Hour fire Rating (ANSI/UL 263) fire Test Wall Temperatures for 8" Load Bearing Block Wall (ANSI/UL 263)06/03 / IV-7IV - fire Resistance4"x24"x10'SOLID WALL PARTITION4" fire Test Wall Temperatures for 4" Wall PanelsTemperature F20001800160014001200100080060040020000 1 2 3 HoursFurnace TemperatureAverage Interior Wall Surface TemperatureAverage Exterior Wall Surface TemperatureAERCON Interior Wall Partitions - 3 Hour fire Rating (ASTM E 119) fire Test Wall Temperatures for 4" Wall Partitions (ASTM E 119)IV - fire Resistance06/03 / IV-8In multi-story construction, Aercon floor panels are amulti-functional element.

6 Inaddition to serving as thestructural floor system, Aercon floor panels also pro-vide any fire protection thatmay be required. The integralfire rating of Aercon floorpanels eliminates the need forany ancillary materials or coat-ings to achieve a fire resistantassembly. A basic 6 inch thickfloor panel system has a 4 hourfire Resistance rating per ULK909. For an assembly to beconsidered restrained merelyrequires that a concrete ringbeam, also referred to as abond beam, be poured aroundthe perimeter of the floor sys-tem, with the inclusion of rein-forcing steel in the ring beamand in the grouted key the concrete and groutpours are integral componentsof the structural system, oncethey are completed, so is thefire rated assembly. No addi-tional materials; no additionallabor.

7 One system excep-tional fire as Aercon floor panelsprovide superb fire Resistance ,so too do Aercon roof and installed justlike floor panels, Aercon roofpanels have a 4 hour fire resis-tance rating per UL the fire is above orbelow the roof, Aercon roofpanels provide the peace ofmind that your structure is fire Rated Floor and Roof Systems06/03 / IV-9IV - fire Resistance6" MIN x 2'- 0"REINFORCED FLOOR/ROOF PANEL6"GROUT FILLEDKEY JOINTCONCRETEBOND BEAM050010001500200001234 Temperature FHoursFurnace TemperatureAverage Panel TemperatureAverage Unexposed Surface TemperatureAERCON Reinforced Floor/Roof Panels - 4 Hour fire Rating (ANSI/UL 263) fire Test Panel Temperatures for 8" Floor/Roof Panels (UL 263)IV - fire Resistance06/03 / IV-10 Whenever fire rated elementsabut one another, a linear jointor gap is usually created.

8 Inorder to maintain the integrityof the overall assembly, a firerated system must be used toseal the joint or gap. There arefour primary configurations ofjoints as illustrated. The basic standard used toinvestigate products that areused in joint systems isANSI/UL 2079, Tests for FireResistance of Building JointSystems . The hourly ratingsapply only to the complete sys-tems. Individual componentsare designated for use in a spe-cific system to achieve a speci-fied rating. Each of the jointsystems identified are classi-fied as dynamic , that is, hav-ing movement capabilities. Alljoint systems are tested at theirmaximum joint width. The rat-ings for the joint systemsinstalled in walls apply wheneither face of the wall isexposed to fire . The ratings forjoint systems installed in afloor or roof apply when theunderside or ceiling surface isexposed to fire Rated Joint SystemsIV - fire Resistance06/03 / IV-11 Whenever a commodity such aspiping or electrical wiring mustpass through a fire rated ele-ment, a circular or rectangularjoint or gap is usually order to maintain the integri-ty of the overall assembly, a firerated system must be used toseal the joint or gap.

9 A firestopsystem is a specific configura-tion of items that consists of awall or floor assembly, an itemthat penetrates that wall or floorassembly, and the materialsdesigned to prevent the spreadof fire through the opening thatis created around the penetrat-ing item. There are currentlythree through-penetrationfirestop systems that can be uti-lized with Aercon walls andfloors. These are illustrated toshow the various items associ-ated with each basic standard used toinvestigate products that areused in through-penetrationsystems is ANSI/UL 1479, FireTests of Through-PenetrationFirestops . This standarddefines the criteria for hourly Fand T ratings for firestop sys-tems. The F rating criteria pro-hibits flame passage throughthe system and requiresacceptable hose stream testperformance.

10 The T rating cri-teria prohibits flame passagethrough the system andrequires the maximum temper-ature rise (on the side which isnot exposed to the fire duringtesting) to 325 F above thestarting temperature and alsorequires acceptable hosestream test performance. Theratings for firestop systemsinstalled in walls apply wheneither face of the wall isexposed to fire . The ratings forfirestop systems installed in afloor or roof apply when theunderside or ceiling surface isexposed to fire Rated Through-Penetration Systems