Example: stock market

15kV Shielded Power Cable - Okonite

Okoguard -Okoseal Type MV-105 15kV Shielded Power CableOne Aluminum Conductor/105 C Rating100% and 133% Insulation LevelFor Cable Tray Use-Sunlight ResistantAUncoated Aluminum ConductorStrand Screen-ExtrudedBSemiconducting EPRI nsulation-Okoguard EPRCI nsulation Screen-ExtrudedDSemiconducting EPRS hield-Copper TapeEJacket-OkosealFProduct DataSection 2: Sheet 59 InsulationOkoguard is Okonite 's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in othersolid dielectrics. Okoguard insulation, withthe distinctive red color and a totallyintegrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free triple tandem extrusion of the screenswith the insulation provides optimumelectrical Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to flame, oil, acids andmost Shielded Okoseal Type MV-105power cables are recommended for use asfeeder circuits, in electric utility generatingstations, for distribution circuits, and forfeeders or branch circuits in industrial andcommercial MV cables may be installed in wet ordry locations, indoors or outdoors (exposedto sunlight), in any raceway or undergroundduct

resistant, and for use in cable tray in accordance with UL 1072. CSA C68.10 listed as FT4, SR, LTGG (-40°C), TC (< 500 kcmil) and TC-ER (≥ 500 kcmil). Product Features • Triple tandem extruded, all EPR system. • Okoguard cables meet or exceed all recognized industry standards (UL, CSA, AEIC, NEMA/ICEA, IEEE). • 105°C continuous ...

Tags:

  Cable

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 15kV Shielded Power Cable - Okonite

1 Okoguard -Okoseal Type MV-105 15kV Shielded Power CableOne Aluminum Conductor/105 C Rating100% and 133% Insulation LevelFor Cable Tray Use-Sunlight ResistantAUncoated Aluminum ConductorStrand Screen-ExtrudedBSemiconducting EPRI nsulation-Okoguard EPRCI nsulation Screen-ExtrudedDSemiconducting EPRS hield-Copper TapeEJacket-OkosealFProduct DataSection 2: Sheet 59 InsulationOkoguard is Okonite 's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in othersolid dielectrics. Okoguard insulation, withthe distinctive red color and a totallyintegrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free triple tandem extrusion of the screenswith the insulation provides optimumelectrical Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to flame, oil, acids andmost Shielded Okoseal Type MV-105power cables are recommended for use asfeeder circuits, in electric utility generatingstations, for distribution circuits, and forfeeders or branch circuits in industrial andcommercial MV cables may be installed in wet ordry locations, indoors or outdoors (exposedto sunlight), in any raceway or undergroundduct, directly buried if installed in a systemwith a grounding conductor in close proximitythat conforms with NEC Section (A)(5)

2 , or messenger supported inindustrial establishments and electric 1/0 AWG and larger may also beinstalled in Cable tray as permitted by NECS ection (2).SpecificationsConductor:Aluminum per ASTM B-609,Class B Stranded per Screen:Extruded EPRsemiconducting strand screen. Meets orexceeds electrical and physical requirementsof ICEA S-93-639/NEMA WC74 & S-97-682,AEIC CS8, CSA and UL :Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA and UL Screen:Extruded EPRsemiconducting insulation screen applieddirectly over the insulation. Meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC74 & S-97-682,AEIC CS8, CSA and UL :5 mil bare copper tape helicallyapplied with 25% minimum :Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA UL 1072 for polyvinyl chloride listed as Type MV-105, sunlightresistant, and for use in Cable tray inaccordance with UL listed as FT4, SR, LTGG(-40 C), TC (< 500 kcmil) and TC-ER ( 500kcmil).

3 Product Features Triple tandem extruded, all EPR system. Okoguard cables meet or exceed allrecognized industry standards (UL, CSA,AEIC, NEMA/ICEA, IEEE). 105 C continuous operating temperature. 140 C emergency rating. 250 C short circuit rating. Passes the Vertical Tray Flame Testrequirements of UL 1072 and IEEE 383 and1202. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Exceptional resistance to moisture. Resistant to most oils, acids, and alkalies. Sunlight resistant. For Cable Tray Use. Improved Temperature Rating. Compact constructions available uponspecial 5 4/0 AWG AL OKOGUARD EP PVC 15kV 133% INSUL LEVEL 220 Okoguard-Okoseal Type MV-10515kV Shielded Power Cable105 C RatingOne Aluminum Conductor/100% and 133% Insulation LevelFor Cable Tray Use - Sunlight ResistantProduct DataSection 2: Sheet 59 Okoguard Insulation: 175 mils ( ), 100% Insulation Level135-23-3202135-23-3203135-23-32041/ 02/03 775170 230 165200 260 190225 295 21533*3135-23-4021135-23-3206135-23-4027 4 830846 9391012 1126260 340 245290 370 270350 450 3303 3 *4* 13891612 17992059 24412110 2364430 545 400540 680 490640 795 565675 870 5754*566 Okoguard Insulation.

4 220 mils ( ), 133% Insulation Level135-23-3301135-23-3302135-23-33031/ 02/03 748715 807784 877170 230 165200 260 190225 295 21533 3 * 135-23-3107135-23-3305 135-23-31744 953958 10661132 1248260 340 245290 370 270350 450 3303 *44 135-23-3175 15481758 19672223 26052273 2580430 545 400540 680 490640 795 565675 870 575556*6D/21120259 THE Okonite COMPANYR amsey, New Jersey 07446 Catalog NumberConductor SizeAWG or kcmilApprox. Dia. overInsulation (in.)Approx. Dia. overScreen (in.)Jacket Thickness - milsJacket Thickness - mmApprox. -InchesApprox. -mmApprox.

5 Net Approx. Ship Ampacities (1) Conduit in AirAmpacities (2) Direct BurialConduit SizeInches (4)*Ampacities (3) Underground Duct Available from our Customer Service Stock Manufacturing Quantity for non-stock items is 5000 .Ampacities(1) Ampacities are in accordance with Table (C)(74) of the NEC for three singleType MV-105 conductors, or single conductors twisted together (triplexed) andinstalled in an isolated conduit in air at an ambient temperature of 40 C and aconductor temperature of 105 C.(2) Ampacities are in accordance with Table (C)(78) of the NEC for three singleconductors or triplexed Cable in one underground raceway, three feet deep witha conductor temperature of 105 C, 100% Load Factor, an ambient earth temperatureof 20 C, and thermal resistance (RHO) of to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite EngineeringData Bulletin EHB for installation in duct banks, multiple point ground shields, otherambient temperatures, circuit configurations or installation requirements.

6 (4) Recommended size of rigid or nonmetallic conduit for three conductorsbased on 40% maximum fill.* The jam ratio, conduit to Cable should be checked to avoid possiblejamming.(3) Ampacities for Cable in Cable tray are in accordance with the NEC,Section (B)(2)(2), Table (C)(70) (copper), for single conductorcables installed in a single layer, in uncovered tray, with a maintained spacingof 1 Cable OD or more at 105 C conductor temperature and 40 C ambienttemperature and multi-point s web site, contains the most up to date