fx3u SERIES PROGRAMMABLE CONTROLLERS Hardware MANUALThis manual describes the part names, dimensions, mounting,cabling and specifications for the product. This manual is extractedfrom fx3u Series User's Manual - Hardware Edition. Refer to FX3 USeries User's Manual - Hardware Edition for more details. Beforeuse, read this manual and manuals of relevant products fully toacquire proficiency in the handling and operating the product. Makesure to learn all the product information, safety information, , store this manual in a safe place so that you can take it out andread it whenever necessary. Always forward it to the end company name and the product name to be described in thismanual are the registered trademarks or trademarks of May 2011 Specifications are subject to change without notice. 2005 Mitsubishi Electric CorporationSafety Precaution (Read these precautions before use.)This manual classifies the safety precautions into two categories: and .Depending on the circumstances, procedures indicated by may also cause severe is important to follow all precautions for personal NumberJY997D18801 RevisionKDateMay 2011 Indicates that incorrect handling may causehazardous conditions, resulting in death orsevere that incorrect handling may causehazardous conditions, resulting in medium orslight personal injury or physical AND MAINTENANCE PRECAUTIONS Do not touch any terminal while the PLC's power is so may

FX3U SERIES PROGRAMMABLE CONTROLLERS HARDWARE MANUAL This manual describes the part names, dimensions, mounting, cabling and specifications for the product. This manual is extracted

Tags:

  Hardware, Electric, Mitsubishi, Mitsubishi electric, 188k, Fx3u, 188k fx3u hardware

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 188k FX3U Hardware A4編集用 - Mitsubishi Electric

1 fx3u SERIES PROGRAMMABLE CONTROLLERS Hardware MANUALThis manual describes the part names, dimensions, mounting,cabling and specifications for the product. This manual is extractedfrom fx3u Series User's Manual - Hardware Edition. Refer to FX3 USeries User's Manual - Hardware Edition for more details. Beforeuse, read this manual and manuals of relevant products fully toacquire proficiency in the handling and operating the product. Makesure to learn all the product information, safety information, , store this manual in a safe place so that you can take it out andread it whenever necessary. Always forward it to the end company name and the product name to be described in thismanual are the registered trademarks or trademarks of May 2011 Specifications are subject to change without notice. 2005 Mitsubishi Electric CorporationSafety Precaution (Read these precautions before use.)This manual classifies the safety precautions into two categories: and .Depending on the circumstances, procedures indicated by may also cause severe is important to follow all precautions for personal NumberJY997D18801 RevisionKDateMay 2011 Indicates that incorrect handling may causehazardous conditions, resulting in death orsevere that incorrect handling may causehazardous conditions, resulting in medium orslight personal injury or physical AND MAINTENANCE PRECAUTIONS Do not touch any terminal while the PLC's power is so may cause Electric shock or malfunctions.

2 Before cleaning or retightening terminals externally cut off allphases of the power to do so may cause Electric shock. Use the battery for memory backup correctly in fx3u SeriesUser's Manual - Hardware Use the battery only for the specified Connect the battery Do not charge, disassemble, heat, put in fire, short-circuit, connect reversely, weld, swallow or burn the battery, or apply excessive forces (vibration, impact, drop, etc.) to the Do not store or use the battery at high temperatures or expose to direct Do not expose to water, bring near fire or touch liquid leakage or other contents Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid leakage or deformation, and lead to injury, fire or failures and malfunctions of facilities and other equipment. Before modifying or disrupting the program in operation orrunning the PLC, carefully read through this manual and theassociated manuals and ensure the safety of the operation error may damage the machinery or cause AND MAINTENANCE PRECAUTIONS Turn off the power to the PLC before attaching or detaching thememory cassette.

3 If the memory cassette is attached ordetached while the PLC's power is on, the data in the memorymay be destroyed, or the memory cassette may be damaged. Do not disassemble or modify the so may cause fire, equipment failures, or repair, contact your local Mitsubishi Electric distributor. Turn off the power to the PLC before connecting or disconnectingany extension to do so may cause equipment failures or malfunctions. Turn off the power to the PLC before attaching or detaching thefollowing to do so may cause equipment failures or Display module, peripheral devices, expansion boards, and special adapters- Connector conversion adapter, extension blocks, and FX Series terminal blocks- Battery and memory cassetteDISPOSAL PRECAUTIONS Please contact a certified electronic waste disposal companyfor the environmentally safe recycling and disposal of disposing of batteries, separate them from other wasteaccording to local regulations.

4 (For details of the Battery Directive in EU countries, refer toFX3U Series User's Manual - Hardware Edition.)TRANSPORTATION AND STORAGE PRECAUTIONS Before transporting the PLC, turn on the power to the PLC tocheck that the BATT LED is the PLC is transported with the BATT LED on or the batteryexhausted, the battery-backed data may be unstable AND MAINTENANCE PRECAUTIONSM arine standardPlease consult with Mitsubishi Electric for the information on marinestandard practices and the corresponding types of of UL, cUL standardsFX3U series main units, fx3u series special adapters and FX2N seriesinput/output extension units/blocks supporting UL, cUL standardsare as follows:UL, cUL file number :E95239 Models :MELSEC fx3u series manufacturedFX3U- MR/ES(-A) fx3u - MT/ES(-A) fx3u - MT/ESSW here indicates:16,32,48,64,80,128FX3U- MR/DSFX3U- MT/DSFX3U- MT/DSSW here indicates:16,32,48,64,80FX3U- MR/UA1FX3U- MS/ESWhere indicates.

5 32,64FX3U-232 ADP(-MB) fx3u -485 ADP(-MB) fx3u -4AD-ADPFX3U-4DA-ADPFX3U-3A- ADPFX3U-4AD-PT-ADPFX3U-4AD-PTW-ADP fx3u -4AD-PNK-ADPFX3U-4AD-TC-ADPFX3U-4 HSX-ADPFX3U-2 HSY-ADPFX3U-CF-ADPM odels :MELSEC FX2N series manufacturedFX2N- ER-ES/ULFX2N- ET-ESS/ULWhere indicates:32,48FX2N-48ER-DSFX2N-48ET-DSS FX2N-48ER-UA1/ULFX2N-8ER-ES/ULFX2N-8EX-E S/ULFX2N-8 EYR-ES/ULFX2N-8 EYR-S-ES/ULFX2N-8 EYT-ESS/ULFX2N-8EX-UA1/ULFX2N-16EX-ES/UL FX2N-16 EYR-ES/ULFX2N-16 EYT-ESS/UL FX2N-16 EYSC ompliance with EC directive(CE Marking )This document does not guarantee that a mechanical systemincluding this product will comply with the following to EMC directive and LVD directive of the entiremechanical system should be checked by the user / more details please contact the local Mitsubishi Electric for Compliance with EMC directiveThe following products have shown compliance through directtesting (of the identified standards below) and design analysis(through the creation of a technical construction file) to the EuropeanDirective for Electromagnetic Compatibility (2004/108/EC) whenused as directed by the appropriate This product is designed for use in industrial Manufactured by.

6 Mitsubishi Electric Corporation2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan Manufactured at: Mitsubishi Electric Corporation Himeji Works840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan Authorized Representative in the European Community: Mitsubishi Electric Europe Str. 8, 40880 Ratingen, :Programmable Controller (Open Type Equipment)Models :MELSEC fx3u series manufacturedfrom May 1st, 2005FX3U- MR/ES(-A)Where indicates:16,32,48,64,80FX3U-4 HSX-ADPFX3U-2 HSY-ADPFX3U-FLROM-16FX3U-FLROM-64 LFX3U-7 DMfrom June 1st, 2005FX3U-232 ADPFX3U-485 ADPFX3U-4AD-ADPFX3U-4DA-ADPFX3U-4AD-PT-A DP fx3u -4AD-TC-ADPFX3U-232-BDFX3U-422-BDFX3 U-485-BDFX3U-USB-BDFX3U-FLROM-64FX3U-CNV -BDfrom November 1st, 2005 fx3u - MT/ES(-A) fx3u - MT/ESSW here indicates:16,32,48,64,80from February 1st, 2006FX3U-128MR/ES(-A) fx3u -128MT/ES(-A) fx3u -128MT/ESSFX3U- MR/DSFX3U- MT/DSFX3U- MT/DSSW here indicates:16,32,48,64,80from April 1st, 2007FX3U-232 ADP-MBFX3U-485 ADP-MBfrom December 1st, 2007 fx3u -4AD-PTW-ADPFX3U-4AD-PNK-ADPfrom June 1st, 2009FX3U-3A-ADPFX3U-CF-ADPfrom August 1st, 2010FX3U-8AV-BDfrom September 1st, 2010FX3U- MR/UA1FX3U- MS/ESWhere indicates:32,64from May 1st, 2011FX3U-FLROM-1 MModels.

7 MELSEC FX2N series manufacturedfrom July 1st, 1997FX2N- ER-ES/UL FX2N- ET-ESS/ULWhere indicates:32,48FX2N-16EX-ES/UL FX2N-16 EYR-ES/ULFX2N-16 EYT-ESS/ULfrom April 1st, 1998FX2N-48ER-DSFX2N-48ET-DSSfrom August 1st, 1998 FX2N-48ER-UA1/ULfrom August 1st, 2005 FX2N-8ER-ES/ULFX2N-8EX-ES/ULFX2N-8 EYR-ES/UL FX2N-8 EYT-ESS/ULfrom September 1st, 2010FX2N-8 EYR-S-ES/ULFor the products above, PLCs manufacturedbefore March 31st, 2002 are compliant with EN50081-2 (EN61000-6-4) and EN50082-2from April 1st, 2002 to April 30th, 2006 are compliant with EN50081-2 (EN61000-6-4) and EN61131-2:1994+A11:1996+A12:2000after May 1st, 2006 are compliant with EN61131-2:2007 The PLC is a precision instrument. During transportation, avoidimpacts larger than those specified in Section Failure to doso may cause failures in the transportation, verify the operations of the PLC. When transporting lithium batteries, follow required transportation regulations.(For details of the regulated products, refer to fx3u SeriesUser's Manual - Hardware Edition.)

8 TRANSPORTATION AND STORAGE PRECAUTIONSS tandardRemarkEN61131-2:2007 Programmable controllers-Equipment requirements and testsCompliance with all relevant aspectsof the Radiated Emission Conducted EmissionEMS Radiated electromagnetic field Fast Transient burst Electrostatic discharge High-energy surge Voltage drops and interruptions Conducted RF Power frequency magnetic fieldJY997D18801K(ENGLISH)Requirement for Compliance with LVD directiveThe following products have shown compliance through directtesting (of the identified standards below) and design analysis(through the creation of a technical construction file) to the EuropeanDirective for Low Voltage (2006/95/EC) when used as directed bythe appropriate :Programmable Controller (Open Type Equipment)Models :MELSEC fx3u series manufacturedfrom May 1st, 2005FX3U- MR/ES(-A)Where indicates:16,32,48,64,80from November 1st, 2005 fx3u - MT/ES(-A) fx3u - MT/ESSW here indicates:16,32,48,64,80from February 1st, 2006FX3U-128MR/ES(-A) fx3u -128MT/ES(-A)FX 3U-128MT/ESSFX3U- MR/DSWhere indicates:16,32,48,64,80from September 1st, 2010FX3U- MR/UA1FX3U- MS/ESWhere indicates:32,64 Models :MELSEC FX2N series manufacturedfrom July 1st, 1997FX2N- ER-ES/UL FX2N- ET-ESS/ULWhere indicates:32,48FX2N-16 EYR-ES/ULfrom April 1st, 1998FX2N-48ER-DSfrom August 1st, 1998 FX2N-48ER-UA1/ULfrom August 1st, 2005 FX2N-8ER-ES/ULFX2N-8 EYR-ES/ULfrom September 1st, 2010FX2N-8 EYR-S-ES/ULFor the products above, PLCs manufacturedbefore March 31st, 2002 are compliant with IEC1010-1from April 1st, 2002 to April 30th, 2006 are compliant with EN61131-2:1994+A11:1996+A12:2000after May 1st, 2006 are compliant with EN61131-2:2007 Caution for compliance with EC DirectiveInstallation in EnclosureProgrammable logic controllers are open-type devices that must beinstalled and used within conductive control boxes.

9 Please use theFX3U Series programmable logic controllers while installed inconductive shielded control boxes. Please secure the control box lidto the control box (for conduction). Installation within a control boxgreatly affects the safety of the system and aids in shielding noisefrom the programmable logic for Analog Products in useThe analog special adapters have been found to be compliant to theEuropean standards in the aforesaid manual and directive. However,for the very best performance from what are in fact delicatemeasuring and controlled output device Mitsubishi Electric would liketo make the following points;As analog devices are sensitive by nature, their use should beconsidered carefully. For users of proprietary cables (integral withsensors or actuators), these users should follow thosemanufacturers installation Electric recommend that shielded cables should be NO other EMC protection is provided, then users may experiencetemporary induced errors not exceeding +10%/-10% in very heavyindustrial , Mitsubishi Electric suggest that if adequate EMCprecautions are followed with general good EMC practice for theusers complete control system, users should expect normal errorsas specified in this Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling.

10 Where possible users should run analog cables Good cable shielding should be used. When terminating the shield at Earth - ensure that no earth loops are accidentally :2007- Generic emission standardIndustrial environmentEN50081-2:1993 ElectromagneticcompatibilityCompliance with all relevant aspectsof the standard. Emission-Enclosure port Emission-Low voltage AC mainsport Emission-Telecommunications/network portEN50082-2:1995 Electromagneticcompatibility- Generic immunity standardIndustrial environmentCompliance with all relevant aspectsof the standard. RF immunity Fast Transients ESD Conducted Power magnetic fieldsEN61131-2:1994 /A11:1996 /A12:2000 Programmable controllers-Equipment requirements and testsCompliance with all relevant aspectsof the standard. Radiated electromagnetic field Fast transient burst Electrostatic discharge Damped oscillatory waveEN61131-2:2007 Programmable controllers-Equipment requirements and testsCompliance with all relevant aspectsof the Radiated Emission Conducted EmissionEMS Radiated electromagnetic field Fast Transient burst Electrostatic discharge High-energy surge Voltage drops and interruptions Conducted RF Power frequency magnetic fieldStandardRemarkEN61131-2:2007 Programmable controllers-Equipment requirements and testsThe equipment has been assessedas a component for fitting in asuitable enclosure which meets therequirements of EN61131-2:2007 StandardRemarkIEC1010-1:1990 /A1:1992 Safety requirements for electrical equipment for measurement, control, and laboratory use- General requirementsThe equipment has been assessedas a component for fitting in asuitable enclosure which meets therequirements of IEC 1010-1:1990+A1:1992EN61131-2.