Example: marketing

1P Arktite Heavy Duty Circuit Breaking Plugs and Receptacles

US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 PArktite Heavy duty CircuitBreaking Plugs and ReceptaclesIndustrial Heavy DutyNon-hazardous AreasNEMA 4 WatertightApplications:Arktitecircuit Breaking Plugs andreceptacles are used: To supply power to portable electricallyoperated devices such as motor-generator sets, compressors, heatingand cooling units, welders, conveyors,lighting systems and similar equipment Where temporary power is needed, suchas at trailers, building units, heavymachinery and similar equipment Wherever electrical loads must bequickly disconnected from power source In a typical installation, where a largemachine utilizes a number of electricalmotor drives and for ease of adjustment,removal, maintenance and replacement,each motor is connected by portablecord and Arktitereceptacles rather thanpermanently wired In areas where dust, dirt, moisture andcorrosion are a problem Indoors and outdoors in non-hazardousareas of chemical plants, processindustry facilities, meat packing plants,manufacturing plants and similarindustrial locationsFeatures: Circuit Breaking .

1P www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business 1313 Arktite® Heavy Duty Circuit 1P Breaking Plugs ...

Tags:

  Receptacles, Heavy, Duty, Plugs, Circuit, Breaking, Heavy duty circuit breaking plugs and receptacles

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 1P Arktite Heavy Duty Circuit Breaking Plugs and Receptacles

1 US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 PArktite Heavy duty CircuitBreaking Plugs and ReceptaclesIndustrial Heavy DutyNon-hazardous AreasNEMA 4 WatertightApplications:Arktitecircuit Breaking Plugs andreceptacles are used: To supply power to portable electricallyoperated devices such as motor-generator sets, compressors, heatingand cooling units, welders, conveyors,lighting systems and similar equipment Where temporary power is needed, suchas at trailers, building units, heavymachinery and similar equipment Wherever electrical loads must bequickly disconnected from power source In a typical installation, where a largemachine utilizes a number of electricalmotor drives and for ease of adjustment,removal, maintenance and replacement,each motor is connected by portablecord and Arktitereceptacles rather thanpermanently wired In areas where dust, dirt, moisture andcorrosion are a problem Indoors and outdoors in non-hazardousareas of chemical plants, processindustry facilities, meat packing plants,manufacturing plants and similarindustrial locationsFeatures: Circuit Breaking .

2 Plugs through 100ampere rating may be disconnectedunder load; 150-400 ampere units arefor service disconnect use only. Receptacles accept only Plugs of thesame amperage rating, style andnumber of poles, making it impossible to mismate, and provides for positivepolarization. Extra wide electrical spacing allows formaximum safety. Insulator materials are the result ofintensive testing. Selection has beenmade based on highest dielectricstrength, maximum mechanical andimpact resistance, lowest moistureabsorption and highest arc trackingresistance. A variety of installations is possible dueto the availability of several types ofback boxes. Designed to withstand rough usage andthe effects of adverse environments. Reversible interiors, 30, 60 and 100ampere (except 30 and 60 ampere, 5-pole) Arktiteplug and receptacleinteriors are interchangeable using ascrewdriver. This makes it possible tofeed a normally de-energized receptaclefrom an energized plug with usual Arktitesafety; no energized contacts areexposed.

3 * APJ and NPJ Plugs only** Excludes 200A and 400A APR ConnectorsCertifications andCompliances: UL Standards: 1203*; 1682, 1686 CSA Standard: No. CE (LVD) 2006/95/EEC** US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 PArktite Heavy duty CircuitBreaking Plugs and ReceptaclesIndustrial Heavy DutyNon-hazardous AreasNEMA 4 WatertightSplit Pin Contact Design: Provides nearly 360 of contact atevery insertion, ensuring protectionagainst heat rise and eliminatingarcing on critical surfaces Continuous contact over lengthand circumference of mated pinsprovides superior safety and long-term performance Self-wiping at every insertion toprevent environmentalcontamination build-up The additional features below are called out in the illustration on this pageThe ground contact is bonded to thereceptacle housing (Style 2)Unimpeded, easy-access phase and groundterminals make wire termination quick and easyGrounding contacts that make-first and break-last in the unlikely event of keyway failureAn arc formed when the plug is beingremoved is instantly snuffed in the deepconfined insulated arcing chamberA detent spring forms a parallel groundingpath through the metallic plug sleeve andreceptacle housing and is the first contact tomake and the last to breakThe plug sleeve is keyed to the receptacle toprevent mispolarizationThe gasketing system providesunsurpassed watertight integrity (NEMA 4)All aluminum Uni-Shell constructionprovides superior strength in abusiveenvironmentsThe Tri-Lock cable grip has 3-piece designthat equally distributes gripping power aroundperimeter of cable.

4 Cord jacket does not getpinched, eliminating potential for damage toboth internal conductors and external cablejacket. Cable grip is located inside plughousing, eliminating corrosion of vitalhardware and making plug maintenance unique Sure-Seal cable gland has twogasket sizes which fit entire range of cablediameters, reducing risk of improperassembly. The gasket ratchets into the Tri-lock cable grip to prevent plug fromturning or loosening in high vibration surfaces make Arktite plugsquick and easy to assembleSmooth and contoured design of plughousing eliminates occurrence of cable gripsnagging or Breaking off. Tri-Lock screwsare captive so cable grip cannot come apartduring assembly. Prevents critical screwsfrom getting lost during sleeve between insulator body andhousing minimizes possibility of electricalshock in event of ground failure. Increasescreepage and clearance Advantage Features.

5 Internal Plug Safety Insulator Plastic barrier between insulator body andmetal housing minimizes risk of energizinghandle body due to stray conductor strands Increases creepage and clearance protectionCE Marked Offers a borderless solution with no additionalinspection or documentation required forapprovalLockout Plug Allows users to comply with OSHA lockout/tagout requirements Ensures plug cannot be inserted intoreceptacle when maintenance is beingperformed downstream of power supplyTri-Lock Cable Grip Three-piece design equally distributes griparound perimeter of cable Cable jacket does not get pinched, eliminatingpotential for damage to internal conductors Captive screws allow maximum extension ofcord grip without risk of loose componentsSure-Seal Cable Gland Two gasket sizes fit entire cable range,reducing risk of improper assembly Gasket ratches into Tri-Lock cable grip toprovide environmental protection in highvibration areasPlug Housing Smooth design eliminates occurrence of cablegrip snagging or Breaking off Houses Tri-Lock cable grip to eliminatecorrosion of vital hardware and increase ease ofmaintenanceCombination Drive Stainless Steel Hardware Increases ease of installation by allowing formore than one option for installation tools Stainless steel external hardware eliminatescorrosion on critical components and extendsproduct lifeInsulator Assemblies Unimpeded.

6 Easy access phase and groundterminals make wire termination quick and easy Lug screws secured with tape to prevent themfrom vibrating loose and falling out duringshippingCombination Slot and Hex Mechanical Lugs* Increases ease of installation by allowing formore than one option for installation tools Hex head allows for easy achievement ofspecified torque valueReceptacle Cover Automatic weatherproof seal every time plug isdisengaged Field replaceable design allows for new coverto be threaded on quickly and easily*60, 100, and 150A US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 PArktite Heavy duty CircuitBreaking Plugs and ReceptaclesNEMA 4 WatertightGrounding: Style 1 vs. Style 2 Eaton's Crouse-Hinds Arktite devices utilize two methods, or styles, for completing the grounding Circuit in Plugs and Receptacles . NECreference (A) & (B).Style 1 MetallicA Style 1 plug is one in which thegrounding conductor in the flexible cable isbonded to the plug sleeve by a pressureconnector.

7 A Style 1 receptacle is onewhich is grounded by virtue of the fact thatit is an integral part of a grounded conduitsystem. On insertion, the plug sleevemakes contact with detent springs of thegrounded receptacle housing before lineand load poles engage, and on withdrawal,remains in contact until after line and loadpoles disengage. Therefore, exposed metalparts of the portable equipment or plug aresuitably 1 Ground conductorattaches to 2 MetallicA Style 2 metallic housing plug is one inwhich the grounding conductor in theflexible cable is bonded to the extra(grounding) pole and metal plug sleeve bya pressure connector. A Style 2 metallichousing receptacle is one in which theextra (grounding) pole is electricallyconnected to the equipment groundingconductor and the metal receptaclehousing which itself is grounded by virtueof the fact that it is an integral part of agrounded conduit system. In Style 2, non-metallic housing Plugs and Receptacles , theextra pole is used for grounding since thehousings are 2 Ground conductorattaches to contact,which is bonded 2 Non-metallicIn a Style 2 receptacle, the groundingconnection is made before line and loadpoles engage, and is broken after the lineload poles disengage.

8 Furthermore, uponinsertion, the plug sleeve of metal shelledunits makes contact with detent springs ofthe grounded receptacle housing beforeline and load poles engage, and onwithdrawal, remains in contact until afterline and load poles disengage. Therefore,exposed metal parts of the portableequipment or plug are suitably ofnon-metallicKrydonmaterialIndustrial Heavy DutyNon-hazardous US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds BusinessArktite Heavy duty Circuit Breaking Plugs and ReceptaclesIndustrial Heavy duty Non-hazardous AreasNEMA 4 WatertightThe mating plug has a cast groovelocated on the outside of the plugsleeve. This groove lines up with theraised Receptacles have a cast raisedrib located inside the receptacle location of the rib is in a specificrelationship to the receptacle insulatorthat houses the Materials: Metallic receptacle housings, plug andcord connector bodies high impactstrength copper-free aluminum Non-metallic Receptacles , Plugs andcord connectors Krydon fiberglass-reinforced polyester material Back boxes: 20, 30, 60, 100, 150 and200 ampere cast aluminum; 400ampere Feraloy iron alloy Insulation (metallic products): (2-, 3-,and 4-pole) 30, 60, 100, 200, 400ampere fiberglass-reinforcedpolyester; 20, 30 ampere (5-pole) melamine Contacts: pressure, solder, bindingscrew brass; crimp/solder 20, 30, 60,100 ampere leaded red brass.

9 Crimp/solder 150, 200, 400 ampere telurium copperStandard Finishes: Feraloy electrogalvanized andaluminum acrylic paint Aluminum natural Krydonfiberglass-reinforced polyestermaterial gray Fiberglass-reinforced polyesterinsulation (red) Melamine natural (brown) Brass natural Leaded red brass electro-tin-plateAccessories: Accessories include a variety of angle adapters, panel adapters and back boxes for Arktitereceptacles, see pages 1332 1335. Included throughout 1P are wire mesh cable grips and protective caps for Installation 150A, 200A and 400A rated units are for service disconnect use :The following special options are availablefrom factory by adding the suffix to theCat. #:DescriptionSuffix Reversed contacts. Receptacleassembled with plug interior(exposed contacts), plugassembled with receptacle interior (recessed contacts). Forapplications where plug isenergized to feed normally de-energized receptacle.

10 Availableon 30 through 400 ampere Special polarity. For use wheretwo or more Receptacles of thesame ampere rating, style andnumber of poles are to beinstalled in the same area for useon different voltages and/orfrequencies. Prevents insertion ofa plug in a receptacle withdifferent electrical on 20 through 400 ampereunits as follows: Receptacle interior rotated 221/2 to right and plug changed tomatch (see photo to right)..S4 Corro-free epoxy powder finishfor added corrosion US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 PArktite Heavy duty Circuit Breaking Plugs and ReceptaclesIndustrial Heavy duty Non-hazardous AreasNEMA 4 WatertightArktite Horsepower RatingsLocked-Rotor InterruptingMotor Horsepower Ampere RatingPlug and Receptacle120 Volts240 Volts480 Volts600 VoltsSingle-phase Electrical 10252010010202001540 Three-phase Electrical System3035101060102040501001530402520030 602515 Maximum Horsepower for Plug andReceptacle Combinations by InputVoltage*Following values are typical horsepower ratings based on NECA rticle 430 Ratings are based on the largest conductor size for eachplug and receptacle combination per the Wire Size table Horsepower Ampere RatingPlug and Receptacle240 Volts480 Volts600 Volts30153040602040501003060751504075100 20060125150 Wire Sizes.


Related search queries