373-ELR Earth Leakage Protection RelayResidual current devices are used to detect potentially dangerous earthfault currents before damage is caused. An undetected fault current maylead to cables overheating, which could start a fire. If high fault currentsare involved, hazardous voltages may also appear on earthed equipment,putting lives at risk. The 373-ELR Earth Leakage Protection Relay allowsthe fault current to be continuously monitored and compared with theuser selectable Leakage level. Should the Leakage exceed this level, therelay will trip to indicate a fault condition. With a very fast response time of under 40ms, the supply can be disconnected before seriousdamage can occur. This product is intended to provide a high degree of Earth Leakage Protection and monitoring for any electrical equipment, specifically motors and their control gear, generator sets and 373-ELR range offers a standard DPCO version, incorporating a single set point,LED Leakage level indicator and double-pole change over Relay contacts.

373-ELR Earth Leakage Protection Relay Residual current devices are used to detect potentially dangerous earth fault currents before damage is caused.

Tags:

  Earth, Protection, Current, Early, Leakage, 373 elr earth leakage protection relay

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 373-ELR Earth Leakage Protection Relay - Te Connectivity

1 373-ELR Earth Leakage Protection RelayResidual current devices are used to detect potentially dangerous earthfault currents before damage is caused. An undetected fault current maylead to cables overheating, which could start a fire. If high fault currentsare involved, hazardous voltages may also appear on earthed equipment,putting lives at risk. The 373-ELR Earth Leakage Protection Relay allowsthe fault current to be continuously monitored and compared with theuser selectable Leakage level. Should the Leakage exceed this level, therelay will trip to indicate a fault condition. With a very fast response time of under 40ms, the supply can be disconnected before seriousdamage can occur. This product is intended to provide a high degree of Earth Leakage Protection and monitoring for any electrical equipment, specifically motors and their control gear, generator sets and 373-ELR range offers a standard DPCO version, incorporating a single set point,LED Leakage level indicator and double-pole change over Relay contacts.

2 The default relayoperation is to de-energise on trip, however, Relay operation can be reversed to energise ontrip by fitting a wire link between two terminals. For additional functionality, an optional pre-alarm Relay version is available where the main set point Relay has two single-polechange over contacts, one which will de-energise on trip function and the other which willde-energise when the Leakage level reaches 60% of the selected protector does not check the continuity of any part of the earthing circuit. It isdesigned for secondary Protection due to the externally connected current transformer andcontactor components. Life Protection devices require an integral CT and main 373-ELR features two incremental rotary selector switches on the front panel and aseries of LED annunciators. The 10 position trip current switch offers selectable earthleakage current settings from 30mA to 10 amps and the 16 position time delay set pointswitch offers additional delay for fault discrimination, selectable from 0 to 10 the 30mA trip current Leakage is selected, the time delay is disabled.

3 Once thetrip current and time delay selections have been made, a green LED provides indicationof mains healthy supply. The red LED will automatically illuminate if the pre-set leakagelevel has been exceeded, after any selected time delay. The unit also incorporates a bargraph of five yellow LEDs providing indication of thelevel of Leakage in 20% increments. When all five LEDs are illuminated the leakagelevel has reached 100% of the set point setting. The enhanced pre-alarm single-polechange over Relay contact version also incorporates a red LED providing indication thatthe level of Leakage has reached 60% of the selected range and that the pre-alarmrelay has unit features a combined reset and test button. A short press of the button willreset the unit after a trip and one long press initiates an electronic confidence Relay latches on to a fault until the test/reset button is pressed or the auxiliarypower is removed.

4 The Relay will de-energise on trip (fail safe) as standard. Fitting a linkbetween two terminals will select energise on OutputsThe 373-ELR unit incorporates a 0/1mA analogue output which equals 0% to 100% ofthe selected tripping level. It can be used to drive an external test meter or panel meter,thus providing measurements for test commissioning and a useful indication of potentialproblems. The analogue output also enables fault level diagnosis to be communicatedinto building management or intelligent SCADA systems, whereby insulationdeterioration can be monitored over a period of time and preventative maintenancearrangements made prior to expensive equipment Balanced current TransformersThe Leakage current is determined by passing the phase conductors (and neutral ifpresent) through a core balanced current transformer. All supply cables must passthrough the same aperture.

5 The current transformers sum the currents flowing intoand back from the load. Ideally, the load will have no Leakage current , so current flowthrough the CT will completely cancel out. For example, 100 amps flowing into loadand 97 amps flowing back provides an output of 3 amps. Crompton offers a full rangeof core balanced current transformers suitable for use with 373-ELR Earth leakageprotection digital settingsLED bargraph display10 selectable trip levels 30mA to 10A16 selectable time delay 0ms to 10 secondsLess than 40ms response time0-1mA analogue output8 amp 250V rated Relay contactsUser selectable energise or de-energise linkDouble-pole change over relaySingle-pole pre-alarm optionBenefitsDIN rail 43880 enclosureSwitched mode supply accepts a widerange of auxiliary voltagesDetects residual current flowIsolation of faulty circuitsInsulation monitoringAdvanced warning of faultsComplementary range of core balanced CTsProtection of expensive power assetsApplicationsSwitchgearDistribution systemsGenerator setsControl panelsBuilding managementUtility power monitoringProcess controlMotor protectionTransformer protectionApprovalsUL

6 3111-1 File No: E203000 CSA compliantEMC and LVD 35 Specification - Earth LeakageMeasuring input From core balanced current transformerOverload 20 x nominal for 1 secondFrequency 50Hz or 60Hz 10%Auxiliary voltage 12-48V dc, 24-48V ac and dc or100-250V ac and dcAuxiliary burden Less than WattsTrip current settings Selectable 30mA, 100mA, 200mA, 300mA, 500mA, 1A, 2A, 3A, 5A, 10 ATrip accuracy 50% <trip point current <100% in accordance with IEC 1543 Trip response time <40ms (at 5 x rated trip current , ignoring the selected time delay)Time delay set points Selectable 0ms, 50ms, 100ms, 150ms, 200ms, 300ms, 400ms, 500ms, 600ms, 700ms, 800ms, 900ms, 1 second, 2 seconds, 5 seconds, 10 seconds. When 30mA Leakage is selected, the time delay is disabledIndication 5 yellow LED bargraph for Leakage levelsRed LED indicated trip functionGreen LED indicated auxiliary power presenceRed LED pre-alarm indication (SPCO version only) Relay contacts Standard: 2-pole change overOption: 2 1-pole change over (pre-alarm and main alarm) Relay contact rating 8 amps at 250V ac8 amps at 30V dc resistiveRelay mechanical life >100,000 operationsAnalogue output 0 to 1mA = 0 to 100% of selected tripping level.

7 Compliance 1V, accuracy 10%Enclosure style DIN 43880, rail width 70mmCompliant with EMC and LVD, UL 3111-1 File No: E203000,CSA BSEN 50081-1, BSEN 50082-2,IEC 60255-22-1 (BS5992), IEC 60255-11, BSEN 61543 (IEC 1543), BSEN 61010 (IEC 1010), EN 60068 (IEC 68)Material Flame retardant UL94V0 Terminals 1 to 4mm2solid or stranded protectionOperating temperature 10 C to +60 CStorage temperature 20 C to +70 CRelative humidity <95% non condensingWeight <250gDimensions 71mm wide x high x 73mm " wide x " high x " deepDimensions " "RemoteResetSwitchFusedAuxiliarySupplyTh e equipment groundingconductor must bypass the CTCommissioningMeterLink to energiseon tripGNDR elay 1 Relay 2 Product Codes Double-pole Change Over RelayFrequencyAuxiliary supplyCat. 12-48V dc 373-ELRW-CBC5-A1-ST50Hz 24-48V ac and dc 373-ELRW-CBC5-A2-ST50Hz 100-250V ac and dc 373-ELRW-CBC5-A3-ST60Hz 12-48V dc 373-ELRW-CBC6-A1-ST60Hz 24-48V ac and dc 373-ELRW-CBC6-A2-ST60Hz 100-250V ac and dc 373-ELRW-CBC6-A3-STProduct Codes Pre-Alarm Single-pole Change Over RelayFrequencyAuxiliary supplyCat.

8 12-48V dc 373-ELRW-CBC5-A1-PA50Hz 24-48V ac and dc 373-ELRW-CBC5-A2-PA50Hz 100-250V ac and dc 373-ELRW-CBC5-A3-PA60Hz 12-48V dc 373-ELRW-CBC6-A1-PA60Hz 24-48V ac and dc 373-ELRW-CBC6-A2-PA60Hz 100-250V ac and dc " " " " " "DIN 43880 CBT-94F Core Balanced current TransformsersThe CBT-94F series of core balanced current transformers are exclusivelyfor use with our 373-ELR Earth Leakage Protection Relay . The extremelysensitive toroidal core and secondary winding are encapsulated by a selfextinguishing case providing excellent mechanical strength, protectionfrom damage and electrical current devices are used to detect potentially dangerous Earth fault currentsbefore damage is caused. An undetected fault current may lead to cables overheating,which could start a fire.

9 If high fault currents are involved, hazardous voltages may alsoappear on earthed equipment, putting lives at risk. An Earth Leakage Protection Relay isintended to provide a high degree of Protection and monitoring for any electricalequipment, specifically motors and their control gear, generator sets and Leakage current is determined by passing the phase conductors (and neutral ifpresent) through a core balanced current conductors should be grouped together and fed through the current transformeraperture. It is essential that each conductor passes through the device in the samedirection. Each phase conductor (and neutral if present) must pass through the currenttransformer. The current transformers sum the currents flowing into and back from theload. Ideally, the load will have no Leakage current , so current flow through the CT willcompletely cancel out. For example, 100 amps flowing into load and 97 amps flowingback provides an output of 3 equipment grounding conductor must always bypass the current connections between the current transformer and protector should be kept as short aspossible to minimise signal noise.

10 For best results, use screened cable with the screengrounded at the measurement range0-10 amps6 models availableIntegral wire sealable terminal coverFlame retardant high impact mouldedcaseBenefitsReduction of high currents for ease ofmeteringWide operating temperature 10 C to +50 CSteel mounting feet suppliedLong product lifeApplicationsSwitchgearDistribution systemsGenerator setsControl panelsMotor protectionTransformer protectionOverload protectionApprovalsIEC 185 VDE 0414 SpecificationProduct Codes and DimensionsSystem voltage720V maximumTest voltage3kV ac for 1 minuteSystem frequency50Hz or 60 HzPrimary ratingsFrom 30mA to 10 ASecondary terminalsProtected to IP20 Operating temperature 10 C to +50 CEnclosureUL94V0 flame retardant plasticCompliant withIEC185, VDE 0414 Mounting hardwareSteel mounting feet for wall or base mountingApertureDim EDim ADim BDim CDim DCat CBT-94F-300A EB33DC4637373-GFR Ground Fault RelayFeaturesPrecision digital settingsLED bargraph display10 selectable trip levels 100 to 1200 amps16 selectable time delay 0ms to 10 secondsLess than 40ms response time0-1mA analogue outputUser selectable input range of or 2m ohmsUser selectable latching/self-resettingSingle-pole change over relay8 amp 250V rated Relay contactsBenefitsDIN rail 43880 enclosureSwitched mode supply accepts a widerange of auxiliary voltagesIsolation of faulty circuitsInsulation monitoringAdvanced warning of faultsProtection of expensive power assetsCurrent transformer not requiredApplicationsSwitchgearDistributi on systemsGenerator setsControl panelsUtility power monitoringTransformer protectionApprovalsUL 3111-1 File No.