Example: marketing

4010 Fire Alarm

4010 fire AlarmPC ProgrammerInstallation and Programming Instructions574-187 Rev. C Technical Manuals Online! - Copyright Simplex Time Recorder Co., 2000. All rights reserved. Printed in the United States of America. Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Simplex Time Recorder Company. Walk Test is protected by US Patent No. 4,725,818. MAPNET addressable communications is protected by US Patent ,796,025. IDNet is patent pending. TrueAlarm Analog Detection is protected by US Patent No. 5,155,468. TrueAlarm Detector Base is protected by US Patent No. 5,173, 683. SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in accordance with NFPA72-1996, Chapter 7 after any programming operation or change in site-specific software.

The 4010 is listed for the following. UL 864 Listings for Type of System: • UL 864 Power-Limited Fire Alarm Control Unit. • Local (formerly NFPA 72A).

Tags:

  0041, Fire, Lamar, 4010 fire alarm

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 4010 Fire Alarm

1 4010 fire AlarmPC ProgrammerInstallation and Programming Instructions574-187 Rev. C Technical Manuals Online! - Copyright Simplex Time Recorder Co., 2000. All rights reserved. Printed in the United States of America. Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Simplex Time Recorder Company. Walk Test is protected by US Patent No. 4,725,818. MAPNET addressable communications is protected by US Patent ,796,025. IDNet is patent pending. TrueAlarm Analog Detection is protected by US Patent No. 5,155,468. TrueAlarm Detector Base is protected by US Patent No. 5,173, 683. SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in accordance with NFPA72-1996, Chapter 7 after any programming operation or change in site-specific software.

2 Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in the installation, operating and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. fire Alarm Control Panel (FACP) operation and reliability depend upon proper installation. DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED.

3 Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex. ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified Simplex Representatives. RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.

4 Copyright and Trademarks Cautions and Warnings Technical Manuals Online! - The 4010 is listed for the following. UL 864 Listings for Type of System: UL 864 Power-Limited fire Alarm Control Unit. Local (formerly NFPA 72A). Requires the sounding of an Alarm via listed notification appliance(s). Auxiliary (formerly NFPA 72B). Requires 4010-9809 City Circuit Module. Remote Station - protected premise (formerly NFPA 72C). Requires 4010-9809 City Circuit Module or the 4010-9810 or -9816 DACT. Proprietary - protected premise (formerly NFPA 72D). Requires 4010-9817 (with 4010-9818 or 4010-9819) or 4010-9821 Network Interface Modules. Central Station - protected premise (formerly NFPA 71). Requires 4010-9810 or -9816 DACT. Suppression Releasing Service. Requires 4010-9814 Suppression Kit. UL 864 Listings for Type of Service: Automatic, Manual, Waterflow, and Sprinkler Supervisory.

5 UL 864 Listings for Type of Signaling: Coded, Non-Coded, March-Time and DACT. DACT requires the 4010-9810 or -9816. Factory Mutual Approved: Same as UL above. Local Approvals: CSFM MEA Continued on next page Codes and Standards Technical Manuals Online! - The installer should be familiar with the relevant codes listed below as well as any other applicable local codes and standards, when installing a fire Alarm system. NFPA 72 National fire Alarm Code NFPA 11 Standard for Low-Expansion Foam and Combined Agent Systems NFPA 11A Standard for Medium- and High-Expansion Foam Systems NFPA 12 Standard on Carbon Dioxide Extinguishing Systems NFPA 12A Standard on Halon 1301 fire Extinguishing Systems NFPA 13 Standard for the Installation of Sprinkler Systems NFPA 14 Standard for the Installation of Standpipe and Hose Systems NFPA 15 Standard for Water Spray Fixed Systems for fire Protection NFPA 16 Standard for the Installation of Deluge Foam-Water Sprinkler and Foam-Water Spray Systems NFPA 16A Standard for the Installation of Closed-Head Foam-Water Sprinkler Systems NFPA 17 Standard for Dry Chemical Extinguishing Systems NFPA 17A Standard for Wet

6 Chemical Extinguishing Systems NFPA 25 Standard for Inspection, Testing, and Maintenance of Water-Based fire Protection Systems NFPA 70 National Electrical Code NFPA 80 Standard for fire Doors and fire Windows NFPA 90A Standard for the Installation of Air Conditioning and Ventilation Systems NFPA 90B Standard for the Installation of Warm Air Heating and Air Conditioning Systems NFPA 92A Recommended Practice for Smoke-Control Systems NFPA 92B Guide for Smoke Management Systems in Malls, Atria, and Large Areas NFPA 101 Life Safety Code NFPA 170 Standard for fire Safety Symbols NFPA 231C Standard for Rack Storage of Materials NFPA 1221 Standard on the Installation, Maintenance, and Use of Public fire Service Communication Systems Before you start using the 4010 fire alarm Installing, Operating, and Programming Instructions, it s important to understand the conventions used in this publication.

7 The following conventions are used in this publication to identify special names or text. When a membrane panel key (located below the display) is referenced in this manual, it is normally shown between left and right arrows. Examples are < Alarm SILENCE> and <SYSTEM RESET>. Italic type indicates important terms or titles of publications, such as the 4010 fire alarm - Programming Instructions. Bulleted lists, such as this one, provide you with information. They are also used to indicate alternatives in numbered procedural steps. Numbered lists indicate procedures with steps that you must carry out sequentially. Codes and Standards (continued) About this Manual Technical Manuals Online! - v Chapter 1. Overview 1-1 Related Documents .. 1-1 In this 1-1 Programmer 1-2 1-2 1-3 1-4 Menu Structure .. 1-4 4010 FACP Version Feature 1-6 Summary of Features .. 1-6 4010 Upgrade 1-8 1-8 Using the Version Programmer with Version Jobs.

8 1-9 Chapter 2. Installing/Upgrading PC Programmer Software 2-1 Before You Begin .. 2-1 In this 2-1 Before You Begin .. 2-2 System 2-2 Required 2-2 Step 1. Install the Software Key .. 2-3 2-3 Installation .. 2-3 Step 2. Create Floppy Disks (If Necessary) .. 2-4 2-4 Procedure .. 2-4 Step 3. Install or Upgrade the PC Programmer Software .. 2-7 2-7 Procedure .. 2-7 Chapter 3. Downloading a Bin File 3-1 Before You Begin .. 3-1 In this 3-1 Step 1. Connect Serial Cable and Set Serial Parameters .. 3-2 3-2 Step 1. Connect the Serial 3-2 Step 2. Set PC Programmer Communication Parameters .. 3-2 Step 3. Set 4010 FACP Baud 3-3 Table of Contents Technical Manuals Online! - vi Step 2. Enable Panel for Download .. 3-4 Procedure .. 3-4 Step 3. Upload and Archive Version Job Files .. 3-5 Upload, Backup, and Archive Existing Version 3-5 Step 4. Download BIN 3-6 3-6 Step 1.

9 Copy BIN File from Floppy to PC Programmer Computer .. 3-6 Step 2. Start Download on PC 3-6 Step 3. Warm Start the 4010 FACP .. 3-8 Chapter 4. Getting Started 4-1 In this 4-1 Using Quick CFIG to Autoconfigure a Panel .. 4-2 Using Quick CFIG to Create a New Job .. 4-2 Quick CFIG Reconfigure All Hardware Option .. 4-2 Upload the Job from the Panel to the 4-3 Starting the Programmer .. 4-4 Using the Start Menu .. 4-4 Creating a New 4-5 4-5 Step 1. Invoke New System Dialog .. 4-5 Step 2. Specify Job 4-6 Step 3. Specify System Type .. 4-6 Step 4. Specify Standalone or Network 4-6 Opening an Existing Job Stored on the PC .. 4-7 4-7 Procedure .. 4-7 Uploading a Job from the 4-8 4-8 Step 1. Set Panel and PC Baud Rates to 19, 4-8 Step 2. Connect Serial Cable between PC and Panel .. 4-9 Step 3. Enable Upload on 4-9 Step 4. Start Upload at PC .. 4-10 Saving, Archiving, Backing Up, and Restoring 4-13 4-13 Saving a Job.

10 4-13 Using Save 4-14 Archiving a Job .. 4-14 Backing Up a Job .. 4-15 Restoring a Backed Up or Archived 4-16 Chapter 5. Setting General Information, System Options, Passcodes, and Access Levels 5-1 In this 5-1 Entering General Information .. 5-2 Entering General Information .. 5-2 Technical Manuals Online! - vii Enabling System 5-3 5-3 Time Format .. 5-3 Depleted Battery .. 5-4 Alarm Silence / 5-4 Alarm Cutout 5-4 Door Drop on 5-5 Door Drop on AC Fail .. 5-5 Air Handling Units (AHU) Stagger 5-5 Suppression 5-6 Active Status Reminder .. 5-7 Signal Operation .. 5-7 Setting Passcodes and Access Levels .. 5-9 5-9 Setting Passcodes .. 5-10 Setting Access Levels .. 5-10 Chapter 6. Programming Cards 6-1 In this 6-1 Overview Card 6-2 Card Tab Screen 6-2 Card Configuration Rules .. 6-2 Using AutoFill .. 6-3 Adding / Deleting Cards .. 6-4 6-4 Adding Cards.