Example: bachelor of science

5069 Compact I/O Modules Specifications Technical Data

Technical Data5069 Compact I/O Modules SpecificationsDigital I/O Module Catalog Numbers 5069 -IB16, 5069 -IB16F, 5069 -IB6F-3W, 5069 -OB16, 5069 -OB16F, 5069 -OW4I, 5069 -OX4 IAnalog I/O Module Catalog Numbers 5069 -IF8, 5069 -IY4, 5069 -OF4, 5069 -OF8 High-speed Counter Module Catalog Number 5069 -HSC2x0B4 Field Potential Distributor Catalog Number 5069 -FPDA ddress Reserve Module Catalog Number 5069 -ARME therNet/IP Adapter Catalog Number 5069 -AEN2 TRThe 5069 Compact I/O architecture provides a wide range of input and output Modules to span many applications, from high-speed digital to process control. The architecture uses Producer-Consumer technolog y that allows input information and output status to be shared among multiple Logix5000 5069 Compact I/O module is installed in a 5069 Compact I/O system that also includes a 5069 -AEN2TR EtherNet/IP adapter. The I/O module requires a removable terminal block (RTB) to connect field-side wiring.

2 Rockwell Automation Publication 5069-TD001C-EN-P - November 2015 5069 Compact I/O Modules Specifications Digital I/O Modules 5069-IB16 and 5069-IB16F Digital 16-point Sinking Input Modules Figure 1 shows a wiring diagram for the 5069-IB16 and 5069-IB16F modules.

Tags:

  5069

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 5069 Compact I/O Modules Specifications Technical Data

1 Technical Data5069 Compact I/O Modules SpecificationsDigital I/O Module Catalog Numbers 5069 -IB16, 5069 -IB16F, 5069 -IB6F-3W, 5069 -OB16, 5069 -OB16F, 5069 -OW4I, 5069 -OX4 IAnalog I/O Module Catalog Numbers 5069 -IF8, 5069 -IY4, 5069 -OF4, 5069 -OF8 High-speed Counter Module Catalog Number 5069 -HSC2x0B4 Field Potential Distributor Catalog Number 5069 -FPDA ddress Reserve Module Catalog Number 5069 -ARME therNet/IP Adapter Catalog Number 5069 -AEN2 TRThe 5069 Compact I/O architecture provides a wide range of input and output Modules to span many applications, from high-speed digital to process control. The architecture uses Producer-Consumer technolog y that allows input information and output status to be shared among multiple Logix5000 5069 Compact I/O module is installed in a 5069 Compact I/O system that also includes a 5069 -AEN2TR EtherNet/IP adapter. The I/O module requires a removable terminal block (RTB) to connect field-side wiring.

2 RTBs are not included with the I/O Modules . They must be ordered I/O Modules2 Analog I/O Modules245069-HSC2X0B4 High-speed Counter Module475069-FPD Field Potential Distributor555069-ARM Address Reserve Module585069-AEN2TR EtherNet/IP Communication Adapter612 Rockwell Automation Publication 5069 -TD001C-EN-P - November 20155069 Compact I/O Modules SpecificationsDigital I/O Modules5069-IB16 and 5069 -IB16F Digital 16-point Sinking Input ModulesFigure 1 shows a wiring diagram for the 5069 -IB16 and 5069 -IB16F 1 - 5069 -IB16 and 5069 -IB16F Wiring DiagramI/O TypeCat. digital input5069-IB165069-IB16F5069-IB6F-3W227D C digital output5069-OB165069-OB16F11 Relay output5069-OW4I5069-OX4I1620 Input Channel 0 (I00)Input Channel 1 (I01)Input Channel 2 (I02)Input Channel 3 (I03)Input Channel 4 (I04)Input Channel 5 (I05)Input Channel 6 (I06)Input Channel 7 (I07)Input Channel 8 (I08)Input Channel 9 (I09)Input Channel 10 (I10)Input Channel 11 (I11)Input Channel 12 (I12)Input Channel 13 (I13)Input Channel 14 (I14)Input Channel 15 (I15)No ConnectNo ConnectDC (+)2-wire Sensor3-wire SensorDC ( )Connections to an external power supply that provides SA Power via the SA Power RTB on the 5069 -AEN2TR EtherNet/IP adapter or 5069 -FPD field potential : The 5069 -IB16 and 5069 -IB16F module inputs use a shared common.

3 The inputs have a return through internal module circuitry to the SA ( ) terminal on the SA Power Automation Publication 5069 -TD001C-EN-P - November 201535069 Compact I/O Modules SpecificationsFigure 2 shows a functional block diagram for the 5069 -IB16 and 5069 -IB16F 2 - 5069 -IB16 and 5069 -IB16F Functional Block DiagramTable 1 - Technical Specifications - 5069 -IB16 and 5069 -IB16 FAttribute5069-IB165069-IB16 FOn-state voltage, min(1)10V DCOn- state voltage, nom(1)24V DC On-state voltage, max(1)32V DCOn-state current, min(1)5 mA @ 10 VOn-state current, nom(1)6 mA @ 24V DCOn-state current, max(1) mA @ 32V DCOff-state voltage, max(1)5V DCOff-state current, min(1) mAInput impedance, k Input impedance, k Inrush current, max< 250 mA peak (decaying to, 37% in 22 ms, without activation)Input delay time (screw to backplane)Off to OnOn to Off 100 s, 10 s @ 25 C (77 F) 100 s, 10 s @ 25 C (77 F) 10 s, 10 s @ 25 C (77 F) 10 s, 10 s @ 25 C (77 F)Input drift10 ns/ C ( F)< 10 ns/ C ( F)Input drift over temperature span 100 ns/ C ( F) C ( F) 10 ns/ C ( F) C ( F)Input On to Off minimum pulse width 60 s 6 sInput Off to On minimum pulse width 60 s 6 sInput filter timeOff to OnOn to OffHardware delay: 50 s + filter timeUser-selectable filter time: msHardware delay: 50 s + filter timeUser-selectable filter time: msHardware delay: 2 s + filter timeUser-selectable filter time: msHardware delay: 3 s + filter timeUser-selectable filter time.

4 MsReverse polarity protectionYe s 5069 Current Limiting Input CircuitsMOD Power24V DCSA Power DC (+)SA Power DC ( )DC (+)Transient SuppressionInputIsolationNon-volatile MemoryBackplane ASICS tatus IndicatorsModule Power SupplyInputBackplaneBackplane Communication4 Rockwell Automation Publication 5069 -TD001C-EN-P - November 20155069 Compact I/O Modules SpecificationsOvervoltage protection, max36V (fuse protected)Pulse and period measurementsNot supported 2 sSimple countersCounter frequency0 - fmax = 500 Hz (inv period 2 ms)0 - fmax = 30 kHz (inv period s)Frequency counter0 - fmax = 500 Hz (inv period 2 ms)0 - fmax = 30 kHz (inv period s)Timestamp of inputsNot supported 10 s accuracy1 ns resolutionCIP syncNot supportedTransport clock, and slave only ordinary clockOverridesNot supportedPulse latchingNot supportedSupportedEventsNot supportedFour events supported (triggered by any input or simple counters)Pattern matchingNot supportedSupportedExtended countersNot supported(1)Sensor Actuator (SA) Power-related 2 - General Specifications - 5069 -IB16 and 5069 -IB16 FAttribute5069-IB165069-IB16 FInputs16 Channels (1 group of 16), sinkingVoltage category12/24V DC SinkInput voltage DCModule Power bus (MOD Power) voltage DCModule Power bus (MOD Power) current, max30 mAModule Power bus (MOD Power) Passthrough voltage DCModule Power bus (MOD Power) current rating, max(1) ASensor Actuator Power bus (SA Power) voltage DCSensor Actuator Power bus (SA Power)

5 Current, max8 mA per channel128 mA moduleSensor Actuator Power bus (SA Power) Passthrough voltage DCSensor Actuator Power bus (SA Power) current rating, max(2) APower dissipation, WThermal dissipation, BTU/hrIsolation voltage300V (continuous), Basic Insulation TypeNo isolation between SA Power and input portsNo isolation between individual input portsModule keyingElectronic keying via programming softwareIndicators1 green/red module status indicator16 yellow I/O status indicatorsSlot width1 Dimensions (HxWxD), approx138 x 22 x 105 mm ( x x in.)Table 1 - Technical Specifications - 5069 -IB16 and 5069 -IB16 FAttribute5069-IB165069-IB16 FRockwell Automation Publication 5069 -TD001C-EN-P - November 201555069 Compact I/O Modules SpecificationsDIN railCompatible zinc-plated, yellow-chromate steel DIN rail. You can use the following DIN rail sizes: EN50022 - 35 x mm ( x in.)

6 EN50022 - 35 x 15 mm ( x in.)Removable terminal block5069-RTB18-SPRING RTB5069-RTB18-SCREW RTBT erminal screw torque ( 5069 -RTB18-SCREW only) N m ( lb in)RTB keyingNoneWire category(3)2 - input ports2 - power ports1 wire per terminal for each signal portWire size5069-RTB18-SPRING mm2 ( AWG) solid or stranded shielded copper wire rated at 105 C (221 F), or greater, mm ( in.) max diameter including insulation, single wire connection mm2 ( AWG) solid or stranded shielded copper wire rated at 105 C (221 F), or greater, mm ( in.) max diameter including insulation, single wire connection stripping length5069-RTB18-SPRING connections: 10 mm ( in.) 5069 -RTB18-SCREW connections: 12 mm ( in.)Weight, approx175 g ( lb)Enclosure typeNone (open-style)North American temp codeT4 ATEX/IECEx temp codeT4 IECEx Temp CodeT4(1)Maximum level of MOD Power current that the module is capable of passing through to the next module in the system.

7 The specific level of current passed through varies based on system configuration.(2)Maximum level of SA Power current that the module is capable of passing through to the next module in the system. The specific level of current passed through varies based on system configuration.(3)Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 3 - Environmental Specifications - 5069 -IB16 and 5069 -IB16 FAttribute5069-IB16, 5069 -IB16 FTemperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock) C ( F)Temperature, surrounding air, max60 C (140 F)Temperature, nonoperatingIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) C ( F)Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat) noncondensingVibrationIEC 60068-2-6 (Test Fc, Operating) g @ HzShock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)30 gShock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

8 50 gEmissionsIEC 61000-6-4 Table 2 - General Specifications - 5069 -IB16 and 5069 -IB16 FAttribute5069-IB165069-IB16F6 Rockwell Automation Publication 5069 -TD001C-EN-P - November 20155069 Compact I/O Modules SpecificationsESD immunityIEC 61000-4-26 kV contact discharges8 kV air dischargesRadiated RF immunityIEC 61000-4-310V/m with 1 kHz sine-wave 80% AM from MHz10V/m with 200 Hz 50% pulse 100% AM at 900 MHz10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz3V/m with 1 kHz sine-wave 80% AM from MHzEFT/B immunityIEC 61000-4-4 4 kV @ 5 kHz on power ports 3 kV @ 5 kHz on input portsSurge transient immunityIEC 61000-4-5 1 kV line-line (DM) and 2 kV line-earth (CM) on power ports 1 kV line-line (DM) and 2 kV line-earth (CM) on input portsConducted RF immunityIEC 61000-4-610V rms with 1 kHz sine-wave 80% AM from 150 MHzVoltage variationIEC 61000-4-2910 ms interruption on MOD Power portTable 4 - Certifications - 5069 -IB16 and 5069 -IB16 FCertification(1)(1)When marked.

9 See the Product Certification link at for Declarations of Conformity, Certificates, and other certification , 5069 -IB16Fc-UL-usUL Listed Industrial Control Equipment, certified for US and Canada. See UL File Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for and Canada. See UL File Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; , Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)European Union 2006/95/EC LVD, compliant with: EN 61010-2-201; Control Equipment Safety RequirementsRCMA ustralian Radiocommunications Act, compliant with:EN 61000-6-4; Industrial EmissionsExEuropean Union 94/9/EC ATEX Directive, compliant with: EN 60079-0; General Requirements EN 60079-15; Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc DEMKO 15 ATEX 1484 XIECExIECEx System, compliant with: IEC 60079-0; General Requirements IEC 60079-15.

10 Potentially Explosive Atmospheres, Protection "n" II 3 G Ex nA IIC T4 Gc IECEx UL Registration of Broadcasting and Communications Equipment, compliant with:Article 58-2 of Radio Waves Act, Clause 3 Table 3 - Environmental Specifications - 5069 -IB16 and 5069 -IB16 FAttribute5069-IB16, 5069 -IB16 FRockwell Automation Publication 5069 -TD001C-EN-P - November 201575069 Compact I/O Modules Specifications5069-IB6F-3W Digital 3-wire Sinking Input ModuleFigure 3 shows a wiring diagram for the 5069 -IB6F-3W 3 - 5069 -IB6F-3W Wiring DiagramFigure 4 shows a functional block diagram for the 5069 -IB6F-3W 4 - 5069 -IB6F-3W Functional Block DiagramInput Channel 0 (I00)SA+ (24V DC)SA- (24V DC Return)Input Channel 1 (I01)SA+ (24V DC)SA- (24V DC Return)Input Channel 2 (I02)SA+ (24V DC)SA- (24V DC Return)Input Channel 3 (I03)SA+ (24V DC)Input Channel 4(I04)SA+ (24V DC)SA- (24V DC Return)Input Channel 5 (I05)SA+ (24V DC)SA- (24V DC Return)SA- (24V DC Return)