8-ChannelRTD Card3007/04-0003007/04-000 8-Channel RTD Analog input CardRTP Corp. 1834 SW 2nd Street Pompano Beach, Florida 33069 PHONE (954) 974-5500 FAX (954) 975-9815 INTERNET: EMAIL HIGHLIGHTS Eight 3-Wire or Four 4-Wire RTD Channels 100-Ohm Platinum RTD Supported 16-Bit A/D Converter -200 C to +850 C Measurement Range Built-in Calibration Channels I/O Bus Checking Diagnostics LED card Health Indicator Supports Dual and Triple Redundancy Hot swappablePRODUCT OVERVIEWThe Eight- channel RTD card is IEC 61131-2 qualified and pro-vides high accuracy RTD measurements for any 3000 3007/04-001 card supports either eight 3-wire or four 4-wireRTDs. 100-Ohm Platinum RTDs can be conncted to measuretemperature from -200 C to +850 C.

8-Channel RTD Card 3007/04-000 3007/04-000 8-Channel RTD Analog Input Card RTP Corp. • 1834 SW 2nd Street • Pompano Beach, Florida 33069 PHONE (954) 974-5500 • FAX (954) 975-9815 • INTERNET: www.rtpcorp.com • EMAIL rtpinfo@rtpcorp.com

Tags:

  Input, Card, Channel, 8 channel rtd card

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 8-Channel RTD Card - rtpcorp.com

1 8-ChannelRTD Card3007/04-0003007/04-000 8-Channel RTD Analog input CardRTP Corp. 1834 SW 2nd Street Pompano Beach, Florida 33069 PHONE (954) 974-5500 FAX (954) 975-9815 INTERNET: EMAIL HIGHLIGHTS Eight 3-Wire or Four 4-Wire RTD Channels 100-Ohm Platinum RTD Supported 16-Bit A/D Converter -200 C to +850 C Measurement Range Built-in Calibration Channels I/O Bus Checking Diagnostics LED card Health Indicator Supports Dual and Triple Redundancy Hot swappablePRODUCT OVERVIEWThe Eight- channel RTD card is IEC 61131-2 qualified and pro-vides high accuracy RTD measurements for any 3000 3007/04-001 card supports either eight 3-wire or four 4-wireRTDs. 100-Ohm Platinum RTDs can be conncted to measuretemperature from -200 C to +850 C.

2 Isolation is provided be-tween the field and RTP chassis ground. The RTDs are notisolated from one another; they share a common power supplyfor the precision excitation current sources. A guard band aboveand below the full-scale signal range allows signals exceedingthe specified input signal range to be detected by conversion is performed by a 16-bit switchedcapacitor successive approximation A/D converter. No field ad-justments are necessary after initial factory trim. The A/D con-verter calibration is continually checked by monitoring aninternal fixed voltage, which is passed through every activecomponent on the to noise is further enhanced with a single-pole, lowpass input Bus self-test functions are performed for all input data, sta-tus and command transfers to and from the RTD card .

3 Eachtransfer is performed twice (all the data bits in the second trans-fer are inverted.) Both transfers are then compared to insurethat no errors exist in the data path between the RTD card andthe processor. I/O Bus slot address and control signal conten-tion tests are also performed. Cable detection tests verify thatthe termination cable is properly connected to the card . Anyerrors are reported in the card s status and triple redundant configurations can be implementedby adding one or two additional 3007/04-000 RTD cards. Twoor three cards may be connected to the RTDs in parallel usingthe 3099/34-000 RTD Triple Termination Module. When usingredundant configurations, the signal validation ( input voting)function can be used to validate the inputs received by thenode processor.

4 Redundant configurations increase is the Best Technology for Your Investment,Here s Why:The 3000 is a multi-processor architecture that deliversexceptional Performance and ComprehensiveDiagnostics. The results speak for themselves: AReaction Time of 12 msec, true 1 msec SOE (Analogand Digital), an MTBF of greater than 3000 years, anMTTFS of greater than 4000 years, and a PFDavg of5x10-5. Compare these numbers to any other Proof Test Diagnostics means it will never benecessary to shut down at the proof test online downloads of logic and configurationchanges do not require a periodic shut down like othersystems. Compare this functionality to any Suite Software: One-time price includes unlimiteduse of Logic Development, Alarm Manager, DataArchive and Historian, and HMI without hardware orsoftware keys.

5 Compare this functionality and priceto all other , a Safety Instrumented System (SIS) shouldalways take the process it protects to a safe state whenit is required to do so, and it should never interfere withthe operation of the process at any time. The 3000does this better than any other 3007/04-000 RTD card s hot swappable design hasbackplane interface logic to protect the card from damage,and to prevent control and data signal degradation on thebus, when plugged into a live RTP chassis. A front panelLED indicates overall health status of the acknowledgments: RTP is a registered trademark of RTP Corp. All other product or service names mentioned herein are trademarks of theirrespective owners. Specifications and information are subject to change without notice.

6 Contact RTP s corporate office for the latest information, data, graphics and statements in this document are proprietary intellectual property of RTP Corp. unless otherwise indicated and are to beconsidered RTP Corp. confidential. This intellectual property is made available solely for the direct use of potential or licensed RTP Corp. customers in theirapplication of RTP Corp. products, and any other use or distribution is expressly prohibited. If you have received this publication in error, immediately delete,discard or return all copies to RTP Redundant input ConfigurationSPECIFICATIONSE lectrical SpecificationsRTD Types:100 platinum3-wire or 4-wire configurationScan Rate:1000 scans/secondInput Signal Range: 160 mVTemperature Measuremnet Range:100 Platinum 200 C to +850 CAccuracy: of Full Scale Voltage at +25 C of Full Scale Voltage/K temperature coefficient of Full Scale Voltage maximum (0 C to +55 C)Isolation:600 VAC RMS or 400 VDC.

7 1500 VAC @ 50 Hz / 60 Hz for 60 sec*Field to RTP chassis ground*Based on Environmental ConditionCommon Mode Voltage:600V AC RMS or 400V DC Mode Rejection:0 dB at 50 Hz / 60 HzHardware Filter:First Order, -3 dB at 2 kHzInput Bias Current:90 nA maximumInput Source Impedance:1 k maximum including cablesRTD Excitation Current:3-WireTwo 400 A current sourcesconnected to Sense+ and Sense 4-WireOne 400 A current sourceconnected to Excitation SourcePower Requirements: +5V DC @ 300 mA +24V DC @ 250 mA (from RTP backplane external voltage)Environmental*Standard Operating Temperature Range: 20 C to +60 CStorage Temperature Range: 25 C to +85 CRelative Humidity Range:10% to 95% non-condensing*Complies with IEC 61131-2 Termination Modules*3099/34-000 RTD Triple Termination Module3099/31-100 Single Termination ModuleTermination Cable included with 3007/04-000 card *Consult factory for a complete list of all available terminationsBackplaneInterfaceandControl LogicLowPassFilterPrecisionVoltageA/DCon verterInput channel MultiplexerBackplaneBusChassisProcessorA mplifierTerminationCableSense +Sense -3-Wire Configuration1 of 8 input Channels3099/34 TerminationModuleRTDB ackplaneInterfaceandControl LogicLowPassFilterPrecisionVoltageA/DCon verterInput channel MultiplexerBackplaneBusChassisProcessorA mplifier1 of 8 input ChannelsBackplaneInterfaceandControl LogicLowPassFilterPrecisionVoltageA/DCon verterInput channel

8 MultiplexerBackplaneBusChassisProcessorA mplifier1 of 8 input ChannelsTerminationCableTerminationCable Excitation Retur