Transcription of BEFORE YOU BEGIN CONFIGURING YOUR UNIT …
1 Simplicity Smart Equipment (SSE) Quick Start Guide1 Simplicity Smart Equipment Controls (SSE) Quick Start Guide1136326-USG-A-0414 BEFORE YOU BEGIN CONFIGURING your unit CONTROLLERE nsure you understand the application and identify the equip-ment configuration: Constant Volume Variable Air Volume (VAV) Economizer Hot Gas Reheat Dual Stage Four Stage Heat Pump Thermostat Controls Network Sensor Control Space Sensor Control Discharge Air ControlUNDERSTANDING THE LOCAL LCDA fter you apply power to your Rooftop unit (RTU), a start-upcountdown begins on the unit Control Board (UCB) the controller is ready, the screen will be blank if nofaults are present. Use the joystick and the two push buttonsbelow the LCD, to navigate through the menus (Figure 1).FIGURE 1 - Joystick and Push Buttons on UCBUp and down movements of the joystick move the > cursorand scroll through the selections in the active section of themenu (Figure 2).
2 FIGURE 2 - UCB Top Level MenuEach menu selection represents either a submenu or a prop-erty. Press "ENTER" to display the items in the submenu orthe values of the selected property. Press "ENTER" to displaythe current value of the selected property. Move up or downwith the joystick to display the values of other : Please see the menu navigation example onpage >StatusAlarmsUpdate>DetailsSummaryCommis nContrler1136326-USG-A-04142 Simplicity Smart Equipment (SSE) Quick Start GuidePOWERING THE UNITWhen you apply power to the unit (the C and 24V terminals),the UCB begins a start-up LCD scrolls the text Johnson Controls on the top line andJCI on the bottom line (Figure 3).FIGURE 3 - Powering the UnitThe display backlight and green Power LED remain lit as longas power is applied to the C and 24V red Fault LED lights, goes off briefly, and then flashesthroughout the start-up green SA Bus LED lights the start-up sequence, the joystick, the "ENTER" but-ton, and the Cancel button are not LCD shows a countdown on the top 4 - Start-up CountdownAfter approximately 15 seconds, the green SA Bus LED doesone of the following: Lights to indicate the UCB has not establishedcommunication and is awaiting communicationfrom SA Bus devices Flashes to indicate the UCB established commu-nication with SA Bus devicesAfter the start-up sequence finishes (90 - 120 seconds), thedisplay shows the current operating status.
3 Idle, startupdelay, on both lines if no alarm is active. The redFault LED stops flashing and turns off. The joystick,"ENTER", and Cancel buttons are WITH THE LOCAL LCDF igure 5 shows the Commissioning view second level Commissioning view consists of 9 nine main menus andseveral 5 - Commissioning View: Second Level MenusCOMMISSIONING VIEW SUBMENUSYour equipment configuration determines which menusappear in the Commissioning view. Use the joystick to movebetween the menu options. Press "ENTER" to select anoption. NOTE: Please see the Commissioning Menu Start-ing on Page : Please see the Pages 7 - 16 for a detailedtable of all menus, sub-menus and your CONFIGURATIONUse the Details > Service > Inputs menu to ensure your con-figuration parameters are correct. This view shows the inputvalues for each input.
4 You can view the Sensors and CoilSensors +-C PWR7777 JohnsonJCIENTERCANCELJOY+-C PWR777718>HVACZonIndoorFaClgHtg>EconDVen tPowerEXHGR>Network1136326-USG-A-0414 Simplicity Smart Equipment (SSE) Quick Start Guide3If no input value appears, the input states No Input. This is aconvenient way to ensure all your configuration parametersare set and reading - Remember to save your configura-tion parameters using the Update > Backup featurewith the USB port on the UCB. See Connecting yourFlash Drive and Performing a System ConfigurationBackup for more your FLASH DRIVEWhen you connect your flash drive to the USB port on theUCB, USB: Wait appears (Figure 6).FIGURE 6 - USB Port ConnectionNOTE: If you do not see USB: Wait after you connect yourflash drive to the UCB, ensure it is properly con-nected.
5 If it is properly connected, and you do notsee the USB: Wait text, your flash drive may not becompatible with the UCB or is defective. After a few seconds, the top line of the UCB displays USB:OK (Figure 7). The Scan number indicates the files and fold-ers in the top level of the flash with the 7 - USB ScanYou can keep the flash drive connected to the UCB after thescan the "ENTER" button, press the cancel button, or movethe joystick up or down to navigate through the display A SYSTEM CONFIGURATION BACKUPI nsert your flash drive into the USB port. Navigate to theUpdate > Backup menu and press "ENTER" (Figure 8).FIGURE 8 - Backup Menu OptionBKP: Wait appears while the backup is in progress. Duringthe backup procedure, the colon (:) flashes on the top lineand the percentage increases on the bottom line of the backup completes in approximately 30 seconds andBKP: OK appears on the screen.
6 The percentage shows 9 - Backup CompleteYou may remove the flash drive from the USB the backup completes, a comma separated value (.csv)restoration file is created in the top level of the flash file name is drawn from the date and time settings in theUCB at the time you create the file. The restoration file size isgenerally less than 30 KB. Figure shows an example of file name +-C PWR7777 USB: WaitScan 0 ENTERCANCELJOY+-C PWR7777 USB: OKScan 18 ENTERCANCELJOY+-C PWR7777>BackupRestoreBKP:OKbCfg 1001136326-USG-A-04144 Simplicity Smart Equipment (SSE) Quick Start GuideFIGURE 10 - Restoration File Name StructureYou can restore the backup file to the unit and retrieve theconfiguration after performing an upgrade or making setpointchanges by using the Upgrade > Restore the Partial Cloning feature to take the configurationparameters from one unit , via the backup file, and update thedata on another unit .
7 Use the Upgrade > Part Clone featureon the unit you wish to update using the backup file from thepreviously configured : Only use the Full Cloning feature when you arereplacing the UCB SSE SOFTWAREA USB Flash Drive must be plugged into the UCB. It mustcontain the appropriate software file (ending in .pkg ). This isat the top level of the flash drive. On the UCB, at the display, push the joystick down until thedisplay has a line showing: > 11 - Display UpdatePush the "ENTER" button. The first line should now display:>View Ver. If you want to verify the version in the UCB, pushthe "ENTER" button now. The current version willbe displayed. Push the Cancel button to return todisplaying ">Update"Push the joystick down until the display is showing: >BackupPush the "ENTER" button. Wait until the top line says "BKP:OK" and the second line says 100%Push the Cancel button.
8 The display should now show:>UpdatePush the "ENTER" button. The display should now show:>View VerPush the joystick down. The first line should now display:>LoadFirmPush the "ENTER" button. The top line should display:> or the current firmware not, push the joystick down (or up) so the carrot (>) pointsto the appropriate filePush the "ENTER" button. Push again to UCB and economizer will now be reprogrammed with theselected software, if they are different. Wait until the every-thing is complete, and the control has done a Restart (as ifpower was just applied).On the UCB, at the display, push the joystick "down" until thedisplay has a line showing: >UpdatePush the "ENTER" button. The first line should now display:>View VerPush the joystick down until the display is showing: >RestorePush the "ENTER" the joystick down until the display line starts with:>RTUxxxx and ends with.
9 CsvThe UCB will now read back the stored setup. When it isdone, the control will Restart. When that is complete, the newsoftware version will be the "ENTER" again to THE VERSION ON THE ECONOMIZERWith Econ and UCB attached together (see Step 1 above).Push the joystick "down" (or up, if you go past) until the dis-play shows: >ContrlerFIGURE 12 - Display UpdatePush the "ENTER" button. The first line should now display:>FirmPush the joystick down until the display shows: >SysCntlrsPush the "ENTER" button. The first line should now display:>MiscPush the joystick down until the display shows: >EconPush the "ENTER" button. The first line should now display:>EconMainVerPush the "ENTER" button again. The second line should nowdisplay the version of software installed in the Economizer. Restoration File Name YearMonthDayHour (Military Time)MinuteSecondContrler>Update>Contrle rUpdate1136326-USG-A-0414 Simplicity Smart Equipment (SSE) Quick Start Guide5 SIMPLICITY SE (SMART EQUIPMENT) FIRMWARE VERSION 1.
10 BASIC unit CONTROL BOARD NAVIGA-TION EXAMPLES:The following document details the navigation and viewing of the LCD display screen equipped as a standard item on the Sim-plicity SE control installed within various commercial UPG packaged and split system equipment. The following information pro-vides a step-by-step demonstration on how to navigate the basic status menu and how to change basic configuration basic navigation steps outlined in this short demonstration applies to most menus within the Simplicity SE the Local LCDA fter you apply power to your Rooftop unit (RTU), a start-up countdown begins on the unit Control Board (UCB) LCD. When the controller is ready, the screen is blank because no faults are present. Use the joystick and the two push buttons below the LCD, to navigate through the menus. Joy Stick Down ENTERCANCELJOY+-C PWR7777T>StatusAlarms Step 1 - After the start-up countdown is FRPSOHWH WKH UVW VFUHHQ GLVSOD\HG LV WKH Status & Alarms screen.