Transcription of Catalog Pages: SolaHD SDN-C Performance DIN …
1 Power Supplies SDN-C Performance DIN Rail Series High Performance specifications and extensive international UL 60950. certifications ensure that the SDN-C is suitable for the ULE61379. 508 Listed E137632. E137632. E234790. IND. CONT. most extreme environments, including hazardous locations E61379. No. 234-M90. and off-shore applications. Features like wide operating temperature range, power boost capability, and adjustable EMC and Low Volt. output voltage ensure reliable operation in the harshest IECEx Directive industrial environments.
2 Parallel operation, extensive LED. diagnostics, and universal AC or DC input voltage simplify installation and maintenance. For added reliability, the SDN-C power supplies can be used with the SolaHD . Redundancy modules to provide redundant power supply operation. Certifications and Compliances *. All Models Applications Listed, Ind. Control Equipment, E61379. Industrial Automation IND. - CONT. UL 508, UL 508 Listed EQ. CSA No. Process Control E61379. UL Recognized Component, ITE, E137632. Material Handling and Conveyors UL 60950.
3 - UL 60950-1/CSA No. 60950-1, 2nd Edition E137632. Hazardous Locations No. 234-M90. - Low Voltage Directive Marine Applications EMC and -Low IEC/EN60950-1, Volt. 2nd Edition Directive Features RoHS Compliant Extensive international hazardous location certifications, Models SDN 5-24-100C, SDN 10-24-100C, SDN 16-12-100C, SDN. including Class 1 Zone 2, ATEX, IECEx, ExEAC. Haz- 20-24-100C, SDN 40-24-100C, SDN 5-24-480C, SDN 10-24-480C, ardous location temperature code (T-Code) rating of T4. SDN 20-24-480CD. International off-shore certifications, including ABS and UL Recognized Component, Haz.
4 Loc., E234790. UL 60950. DNV-GL - UL60079-0/CSA. E137632. E60079-0, UL 60079-15, CSA. PowerBoostTM enables short duration overload capabil- E60079-15. No. 234-M90. ity, to start loads with high inrush current - Class I, Zone 2, AEx nA nC IIC, Ex nA nC IIC. Three LEDs provide extensive diagnostics ATEX Directive Dual output terminals for convenience in wiring - EN60079-0, EN60079-7, EN60079-15. DC OK relay to provide diagnostic information to a PLC, controller, or monitoring system - II 3 G, Ex ec nC IIC Gc Universal AC and DC input voltages to accommodate IECEx Certified global requirements - IEC 60079-0, IEC 60079-7, IEC 60079-15.
5 Wide operating temperature range accommodates both - Ex ec nC IIC Gc extreme hot and extreme cold environments Active Power Factor Correction on most models Models SDN 5-24-100C, SDN 10-24-100C, SDN 16-12-100C, SDN. 20-24-100C, SDN 40-24-100C, SDN 5-24-480C, SDN 10-24-480C. Parallel operation capability standard Supports redundant power supply operation using op- TR CU 012/2011 Safety of Equipment intended for tional SDN Redundancy modules Explosive Atmospheres 5-year limited warranty Type Approval Models SDN 5-24-100C, SDN 10-24-100C, SDN 16-12-100C, SDN.
6 20-24-100C, SDN 40-24-100C. Type Approved Models SDN 5-24-100C, SDN 10-24-100C, SDN 20-24-100C, SDN. 40-24-100C. Certified * Refer to user manual for installation requirements when used in hazardous locations. 124 Visit our website at or contact Technical Services at (800) 377-4384 with any questions. June 2018. Power Supplies Related Products Accessories SDN-C Redundancy Modules Chassis Mount Brackets IP67 SCP-X Extreme Environment Series SDU UPS. The SolaHD Difference Multiple output connections for ease of Rugged metal housing wiring multiple devices Visual LED diagnostics show input and output status (see table below).
7 DC OK Relay Terminals provide diagnostic information to a PLC. or controller Single or parallel use selectable by user Adjustable output voltage Clearly labeled front panel No internal fan, no extra cooling required in any power level Multiple certifications for versatility in applications Automatically adjusts for global Input voltages Narrow width saves panel space LED Light Status Conditions Normal AC Power Loss AC Input Low No DC High Load Overload Hot Too Hot Input Green - Amber Green Green Green Green Green Output Green - Green - Amber Amber Green - Alarm - - - Red Amber Red Amber Amber Visit our website at or contact Technical Services at (800) 377-4384 with any questions.
8 125. June 2018. Power Supplies SDN-C Specifications (Single Phase). Catalog Number Description SDN 16-12-100C SDN 5-24-100C SDN 10-24-100C SDN 20-24-100C SDN 40-24-100C. Input Nominal AC Voltage (Range) 100 - 240 Vac (85-264 Vac). 100-250 Vdc 120-340 Vdc Nominal DC Voltage (range) 100-340 Vdc (90-375 Vdc). (90-275 Vdc) (108-375 Vdc). Frequency 43 - 67 Hz Nominal Current 1 A - A - A 6-3A 12 - 4 A. Typ. < at 120 Vac, Typ. < at 120 Vac, Typ. < at 120 Vac, Typ. < at 120 Vac, Typ. < at 120 Vac, -Inrush current < at 230 Vac, < at 230 Vac, < at 230 Vac, < at 230 Vac, < at 230 Vac, measured at 25 C measured at 25 C measured at 25 C measured at 25 C measured at 25 C.
9 Efficiency (Losses 2) > typ. (24 W) > 88% typ. (14 W) > 90% typ. (24 W) > 92% (38 W) > 93 % (67 W). Power Factor Correction Active power factor correction typ. @ 115 Vac/ @ 230 Vac Output Nominal Voltage 12 V (12-15 Vdc Adj.) 24 V ( Vdc Adj.). Initial Voltage Setting V 1% V 1%. -Tolerance < 2 % overall (combination Line, load, time and temperature related changes). -Ripple 3 < 100 mVpp < 50 mVpp < 100 mVpp PARD 100 mVpp max (Periodic and Random Deviation). Nominal Current (Rated Power 16 A (192 W) 5 A (120 W) 10 A (240 W) 20 A (480 W) 40 A (960 W).)
10 At +60 C). Parallel Operation 4 Single or Parallel operation selectable via front switch. Active Paralleling. Turn On Time < 1 s after AC is applied to input at full resistive load ( Tamb=+25 C ). < ms with capacitive load 7000 F. >40ms (Full load, 100 Vac Holdup Time Input @ Tamb =+25 C) to >20 ms (Full load, 100 Vac Input @ Tamb=+25 C) to 95% output voltage 95% output voltage Voltage Fall Time <150 mS from 95% to 10% rated voltage @ full load (Tamb=+25 C). Protection -Short Circuit Output automatically goes to near zero and output is protected from continuous short circuit.