CONTROL SECTION 1 NEMA full voltage power devices - ABB

CONTROL SECTION 1 NEMA full voltage power devices1-2 NEMA full voltage power devices , CONTROL SECTION 11-3 NEMA full voltage power devices , CONTROL SECTION 1 Table of contents1-4 Application information and technical data Magnetic starters1-8 CR306, CR386 magnettic starters, nonreversing, noncombination1-20 CR309 magnetic starters, reversing, noncombination1-25 CR309 magnetic two-speed starters1-29 CR307, CR407 magnetic starters, nonreversing, combination1-49 CR387, CR487 mag-break magnetic starters, nonreversing, combination1-66 CR310, CR410, CR311, CR411 magnetic starters, reversing, combination1-75 CR390, CR490, mag-break magnetic starters, reversing, combination1-81 CR412, CR413, CR492 magnetic two-speed, 1-winding starters1-94 CR414, CR415, CR494 magnetic two-speed, 2-winding starters1-106 Magnetic starters factory-installed modif

NEMA FULL OLTAGE POWER DEVICES, CONTROL SECTION 1 1-5 Short-circuit ratings Fusible forms of combination magnetic starters equipped with UL labeled, nonrenewable, NEC-type fuses listed in the table below, are adequate for installation on motor branch circuits where the available short-circuit current at the

Tags:

  Devices, Name, Power, Full, Voltage, Fuse, Nema full voltage power devices

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of CONTROL SECTION 1 NEMA full voltage power devices - ABB

1 CONTROL SECTION 1 NEMA full voltage power devices1-2 NEMA full voltage power devices , CONTROL SECTION 11-3 NEMA full voltage power devices , CONTROL SECTION 1 Table of contents1-4 Application information and technical data Magnetic starters1-8 CR306, CR386 magnettic starters, nonreversing, noncombination1-20 CR309 magnetic starters, reversing, noncombination1-25 CR309 magnetic two-speed starters1-29 CR307, CR407 magnetic starters, nonreversing, combination1-49 CR387, CR487 mag-break magnetic starters, nonreversing, combination1-66 CR310, CR410, CR311, CR411 magnetic starters, reversing, combination1-75 CR390, CR490, mag-break magnetic starters, reversing, combination1-81 CR412, CR413, CR492 magnetic two-speed, 1-winding starters1-94 CR414, CR415, CR494 magnetic two-speed, 2-winding starters1-106 Magnetic starters factory-installed modifications1-117 Magnetic starters field-installed kits, modifications1-121 Enclosures for 300-line magnetic starters1-127 CR324 block overload relays1-131 Electronic overload relays1-132 Approximate motor full load current ratings1-134 CR123C.

2 CR123F motor starter heater selection1-140 CR123K, CR123L panel mount overload relay heater selection1-141 CR324X solid state overload relays Manual motor starters1-146 CR101H, CR101Y manual motor starters, non-combination, single phase Manual starters1-152 CR1062 manual starters, single-phase and polyphase1-157 Heaters Pumping panels1-159 CR340, CR341 pumping panels1-160 Fusible disconnect type1-163 With thermal overload relay1-164 Mag-break type1-165 Heaters Magnetic contactors1-170 CR305, CR385 magnetic contactors1-176 Magnetic contactors factory-installed modifications1-181 Magnetic contactors field-installed kits, modificationsNEMA full voltage power devices .

3 CONTROL SECTION 11-4 300-line startersApplication information and technical dataDescriptionMaximum horsepower NEMA size000123456789 Normal starting duty HP rating1 Single phase115 V 60 Hz11 33123711 22 230 V 60 Hz123711 2215 Three phase200 V 60 Hz111 225711 2210254075150 230 V 60 Hz111 225711 22153050100200300450800380 415 V 50 Hz111 223102550751503005007501350460 V 60 Hz231025501002004006009001600575 V 60 Hz251025501002004006009001600 Plugging or jogging HP rating1 Single phase115 V 60 Hz 11 22125 230 V 60 Hz 111 223711 2210 Three phase200 V 60 Hz 111 22515152560125 230 V 60 Hz 2515303075150 380 415 V 50h 25153050125250 460 V 60 Hz 111 223103060150250 575 V 60 Hz 1252060150250 Continuous current maxStarters and enclosed contactors91827459013527054081012152250 Open contactors102030501001503006009001350250 0 Coil burden (VA)

4 Inrush 2-pole1511511515281152124825803360160015 002900 Holding 2-pole242424608387191255210140300 Inrush 3-pole1511511515281152124825803360160029 003600 Holding 3-pole242424608387191255210300400 Inrush 4- and 5-pole151151151576124813563600 Holding 4- and 5-pole242424758795276 CONTROL power transformer VA (min)50505010020025050025002100021500215 012 Coil operating voltage % Minimum pickup6385858585858585858585% Maximum dropout15 3063636865656565505050 Switching delay 3-polePickup typical (milliseconds)7 1515 3015 3020 4020 4520 4530 5030 5060 9080 12580 125 Dropout typical (milliseconds)207 157 157 157 157 1515 2515 25100 15025 10025 100 Mechanical life (millions nominal)2 33 (less carton)Contactor (pounds)333 442 33 442 33 446 11 221514 33 44484879203302 Starter (pounds)14 83 33 443 33 447 11 2217 33 4417 11 225375106263365 power terminalsWire size range (75o) AWG2014 814 814 410 1 08 3 01 0 500kcmil2 2 0 500kcmil3 2 600kcmil4 2 600kcmil Torque (pounds inches)50202050150200300375500500 Max.

5 Noise (DBA)85505050505065656565651 When operation of the controller requires jogging (inching) or plug stopping or when normal operation requires continued operation in excess of 5 operations per minute or 10 operations in a 10-minute period, the plugging or jogging horsepower ratings must be In lieu of a 500 to 1500 VA CONTROL transformer, a 50 VA unit in conjunction with a CONTROL relay can be used as follows: a. Wire CONTROL relay coil in CONTROL circuit on secondary side of CONTROL transformer. b. Wire two poles of CONTROL relay in series with contactor coil at line positionDevices must be mounted to a sturdy vertical surface with the line side terminals up.

6 No other orientations are temperatureEquipment is designed for ambient temperature outside of equipment enclosures to be -25 to 40 C. When contactor is energized, temperatures will be above outside ambient in equipment enclosures. Temperature rises inside the enclosures should be limited so that internal air temperature does not exceed 65 C for sizes 00 to 6 and 60 C for sizes 7 to 9. If condensing moisture is present, space heater kits should be used to prevent condensation when contactor is not temperature should be -30 to 65 C. If equipment is stored over 1 week, it may be necessary to cover the equipment and provide a source of heat to prevent full voltage power devices , CONTROL SECTION 11-5 Short-circuit ratingsFusible forms of combination magnetic starters equipped with UL labeled, nonrenewable, NEC-type fuses listed in the table below.

7 Are adequate for installation on motor branch circuits where the available short-circuit current at the incoming line terminals of the starter does not exceed the value breaker-type combination magnetic starters equipped with the circuit breakers listed in the table at right are adequate for installation on motor branch circuits where the available short-circuit current at the incoming line terminals of the starter does not exceed the value either type, it is recognized that maintenance of some components may be required after a branch circuit fault and in some cases a device may require replacement.

8 Fusible combination startersNEMA sizeFuse typeMaximum symmetricalRMS amperes0 3H, K5,0004, 5H, K10,0000 5J, RK-1, RK-5100,0006J, L, RK-1, RK-5100,000 Circuit breaker combination startersTmax XT molded case breakers and motor circuit protectors (MCP)Breaker modelNEMA sizeMaximum symmetrical RMS amperes240 V480 V600 VXT20 3100,000100,00025,000XT43 4100,000100,00025,000 Circuit breaker combination startersBreakermodelRating amperesNEMA sizeMaximum symmetrical RMS amperes240 V480 V600 VTJJ and TJK225 600510,00010,00010,000 THJK225 400535,00035,00025,000 THJK450 600510,00010,00010,000 TKM, TKC300 800642,00030,00022,000 THKM8300 800665,00035,00025,000TB6, TBC300 800665,00065,00042,000 300-line startersApplication information and technical dataNEMA full voltage power devices .

9 CONTROL SECTION 11-6 300-line startersApplication information and technical data CONTROL transformers where to useIt is often desirable to use a CONTROL transformer in conjunction with a magnetic starter or controller to provide low voltage factory wiredA transformer, with sufficient capacity for the CONTROL circuit, mounted with the starter can be supplied by the factory for the majority of transformer ratings and types of suffix(This table is to be used for starter forms without CONTROL transformers.)Indicates voltage and frequency of operating coils. For use in ordering full voltage starters and contactors, sizes 00 6, with other coil ratings than those shown in listing in SECTION 2, magnetic (Hz)24 V115 120 V5200 208 V5230 240 V5265 277 V460 480 V5575 600 V56024022303130405 Frequency(Hz) 110 V 220 V380 415 V440 V550 V50 02 03640405 Note: The 02 coil suffix (115 120 V, 60 Hz/110 V, 50 Hz) supersedes the 22coil suffix (120 V, 60 Hz).

10 5 Suffix shown for this voltage is part of product number in magnetic starter-contactor listings. Auxiliary contact ratings NEMA size 0 9AC volts12510 full voltage power devices , CONTROL SECTION 11-7 Contactor DC ratings NEMA sizeNo. of poles in seriesContinuous current ratingInterrupting ratingsInductive amps @125 VInductive amps @250 VNoninductive amps @125 VNoninductive amps @250 60 9 234514 120 40 244525 7 160 80 32907 600 300 339014 600 600 349025 9 600 600 421357 600 300 4313514 600 600 4413525 9 600 600 300-line startersApplication information and technical data NEMA full voltage power devices , CONTROL SECTION 11-8 CR306.