DeltaV SIS Process Safety SystemProduct Data SheetNovember 2017 CTO csls CHARM Cabinets Delivers Electronic Marshalling enabled by CHARMs technology Reduce system footprint Eliminate I/O home run cables Significantly reduce cabinet design engineering Fully documented packageIntroductionThe DeltaV SIS Configure-To-Order (CTO) CHARMs Smart Logic Solver ( csls ) Cabinets provide an off-the-shelf solution for faster project execution and reduced installation costs. CTO csls Cabinets are factory tested and ready for installation in technical rooms. Electronic Marshalling eliminates traditional I/O design tasks and allows field wiring to start long before safety strategies are csls CHARM ViewRear csls CHARM Cabinets November 2017 BenefitsDelivers Electronic Marshalling enabled by CHARMs technology: The CTO csls Cabinets offer the full benefits of Electronic Marshalling. The individual channels can be defined for any combination of field signal type, as required by the safety equipment.

DeltaV SIS Process Safety System Product Data Sheet November 27 CTO CSLS CHARM Cabinets Delivers “Electronic Marshalling” enabled by CHARMs technology Reduce system footprint Eliminate I/O home run cables Significantly reduce cabinet design engineering Fully documented package Introduction The DeltaV SIS™ Configure-To-Order (CTO) CHARMs Smart

Tags:

  Cabinets, March, Csls, Cto csls charm cabinets

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of CTO CSLS CHARM Cabinets - Emerson

1 DeltaV SIS Process Safety SystemProduct Data SheetNovember 2017 CTO csls CHARM Cabinets Delivers Electronic Marshalling enabled by CHARMs technology Reduce system footprint Eliminate I/O home run cables Significantly reduce cabinet design engineering Fully documented packageIntroductionThe DeltaV SIS Configure-To-Order (CTO) CHARMs Smart Logic Solver ( csls ) Cabinets provide an off-the-shelf solution for faster project execution and reduced installation costs. CTO csls Cabinets are factory tested and ready for installation in technical rooms. Electronic Marshalling eliminates traditional I/O design tasks and allows field wiring to start long before safety strategies are csls CHARM ViewRear csls CHARM Cabinets November 2017 BenefitsDelivers Electronic Marshalling enabled by CHARMs technology: The CTO csls Cabinets offer the full benefits of Electronic Marshalling. The individual channels can be defined for any combination of field signal type, as required by the safety equipment.

2 This allows for 100 % utilization of channels, regardless of the I/O signal mix. Late changes are easily accommodated with minimal re-engineering and no system footprint: Equipment room footprint is reduced by eliminating the traditional marshalling Cabinets with cross wiring to traditional I/O reduce cabinet design engineering: The CTO csls Cabinets are pre-engineered and factory tested. The I/O flexibility allows the same design to serve a wide variety of I/O signals, conditioned individually by the CHARM . Field wiring design is complete at the terminal documented package: Each cabinet is supplied with full documentation and engineering drawings showing internal lay- out, bill of materials and internal wiring. They are designed to meet local building code and industry best practices in order to deliver proven functionality with minimal DescriptionThe CTO csls Cabinets offering comprises a range of pre- engineered solutions based on industry standard, preinstalled with CHARM I/O and related equipment, ready to be installed in an equipment room and connected to safety instrumentation or Cabinets are typical, free standing enclosures intended for floor mounting in equipment room areas, where temperature and humidity are controlled within the requirements for computer/electronic equipment.

3 They come ready to receive incoming plant AC power. All internal wiring to power distribution components and grounding conductors has been tested at the delivery, each cabinet undergoes a full in-house inspection, to assure that it is fully operational before shipping directly to site. Electronic Marshalling eliminates the need for any internal cross wiring and I/O rationalization there is typically no need for FAT at a staging Cabinets can be ordered and delivered directly together with the DeltaV SIS electronic marshalling equipment and LS CHARM I/O to site to begin field wiring (FAT may be optional).The CTO csls Cabinets are configured by selecting a base enclosure model and required options to meet specific project enclosure models are available: For different cabinet sizes / entry (Front Access or Front and Rear access). For different power distribution needs: DC powered or AC powered.

4 For different world area design standards and regulations: EUR (Europe) and NA (US/Canada).Configurable options examples: the type of LS CHARMS ( or non ), side panels, cabinet light, nameplate engraving and injected CTO csls Cabinets come with following equipment installed. Primary and secondary 24 VDC power distribution for LS CHARM I/O Cards and field instrumentation. Wire ducts or wire basket. Grounding bars. Wiring plan pocket. Emerson Name Plate Holder and blank name plate insert. DeltaV LS CHARM I/O equipment based on your configuration (and priced seperately): including csls carriers, CHARM base plates, standard terminal blocks, address plugs and csls cards and LS CHARMs are not included and are to be ordered required number of (redundant) LS CHARM I/O cards and csls cards depends on the actual number and types of I/O that will be wired into the following sections provide a more detailed specification for the CTO csls Cabinets and available csls CHARM Cabinets November 2017 Base Model numberDescription# LS CHARM IOPower Requirements (Pri and Sec)Permitted Location / World AreaEU-CAB-800F-192-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 192 LS CHARM I/O; 800mm W x600mm D; Front Access SafeArea VACSafe Area EUREU-CAB-800FR-480-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 480 LS CHARM I/O; 800mm Wx 800mm D; Front and RearAccess.

5 Safe Area VACSafe Area EURNA-CAB-800F-192-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 192 LS CHARM I/O; 800mm W x600mm D; Front Access SafeArea VACSafe Area US/CANADANA-CAB-800F-252-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 252 LS CHARM I/O; 800mm W x600mm D; Front Access SafeArea VACSafe Area US/CANADANA-CAB-800FR-480-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 480 LS CHARM I/O; 800mm Wx 800mm D; Front and RearAccess; Safe Area VACSafe Area US/CANADANA-CAB-800FR-504-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 504 LS CHARM I/O; 800mm Wx 800mm D; Front and RearAccess; Safe Area VACSafe Area US/CANADAO verview of CTO csls Cabinets Base ModelsThe CTO base model reference for Cabinets uses the following naming convention: EUR or NA-CAB-XXXYY-ZZZIO-IP-DDDD , where EUR : Europe Design Standards and Regulations / NA : US/Canada Design Standards and Regulations.

6 XXX = cabinet width (mm), 800 , 1200 . YY = F for Front only access (600 mm deep), FR for Front and Rear access (800 mm deep). ZZZ= maximum I/O s count in this CTO. IP= Incoming Power, DC=24V DC or AC=120/230V AC. DDDD= short description of content and purpose. csls CHARM Cabinets November 2017 Base ModelNA-CAB-800F-252-AC-CSLSNA-CAB-800FR -504-AC-CSLSNA-CAB-800F-192-AC-CSLSNA-CA B-800FR-480-AC-CSLSEU-CAB-800F-192-AC-CS LSEU-CAB-800FR-480-AC-CSLSW orld AreaUS/CANUS/CANUS/CANUS/CANEUREURP ower Input (DC: 24 VDC, AC:120/230 VAC)ACACACACACACE nclosure Access (F: Front, FR: Front-Rear)FF/RFF/RFF/R# CHARMI/O252504192480192480 Enclosure OptionsNameplate EngravingG0No 1 Yes Type of CHARMS(to be specified for each row of CHARMS)C1 Non Cabinet LightL1No 2 LED light with motion sensor Temperature MonitoringT0No 1 Thermostat Door FansF1 Continuous Run 2 Thermostat Controlled PlinthD1100mmN/A 2200mm Side PanelsS0No 1 Yes Door HingH1 Left HingedN/A 2 Right Hinged Cable RoutingB1 Cable DuctN/A 2 Wire Basket Baying KitB0No 1 Yes Cable Clamps RailR0No 1 Yes Utility Socket SelectionU0 NoN/A 1 Yes 24 VDC for Injected PowerV1 Front side No 2 Front side Yes 3 Rear side NoN/A N/A N/A 4 Rear side Yes CertificationZ0No 1 CEN/A 2 CSA N/AFollowing more detailed options can be specified upon order (if applicable).

7 Disconnect switches for DC power feeds can be configured separately for csls power and for injected power inputs Type of utility socket : German-Russia / France-Poland / Switzerland / UK-Ireland / USA-Canada / Italy Power supply configuration : Power for csls and/or injected power (with diode), Front and Rear position in cabinet 24 VDC for injected power : optionally prewired (according specification to be provided) Wiring color scheme different from default : US (L- Black, N- White) / EUR (L- Brown, N- Blue) Input Voltage different from default : US (120 VAC) / EUR (230 VAC)Overview of CTO csls Cabinets models and Options : Default option settingo : Configure To Order option setting, different from default blank : option setting not possible for the base enclosure: Intentionally left blank to fill in your configuration choices csls CHARM Cabinets November 2017NA-CAB-800F-252-AC-CSLSD imensions800mm (W) x 600mm (D) x 2000mm (H) + 100mm PlinthAccessFront Access single door, right hand hinged, latch type lock and 2 sets of keys (key N 3524E)Protection CategoryIP54 NEMA 12 Approximate Weight~200 kgColorCabinet RAL7035, Plinth RAL7022 Door FansConfigurable: Continuous run or with thermostat control Temperature MonitoringConfigurable: Thermostat OtherLouvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plateEnvironmental SpecificationsEquipment/rack room installation (HVAC controlled), 30 C in Safe Area locations; Default Certification: CE (Europe).

8 Optional: NoneInput PowerPrimary and Secondary 110 VACP ower Supply RatingFixed 2 x 40 AInternal Power DistributionAC Distribution subassembly (mounted in left side) Fully redundant 24 VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).Local Safety NetworkRedundant 100 BASE-FX, RJ45 connectors, to be connected to each csls carrier. Primary and Secondary Local Safety Network to 3 csls carriers is BOM: Power Supply LS CHARM IO rails, for total of 252 LS I/O, 3 x csls Carrier with redundant Copper Ethernet connectors 21 x CHARM Base Plate 21 x CHARM Address Plug 252 x CHARM terminal blocks - Screw type 3 x CHARM I/O bus termination Base Plate and Channel Identifier LabelsNo DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting ViewSize of Wire Baskets: 150mm H x 54mm DFront ViewExample Layout and Installed csls CHARM Cabinets November 2017NA-CAB-800F-252-AC-CSLSF ront ViewTop ViewExternal Layout Drawing for NA-CAB-800F-252-AC- csls : Front and Top csls CHARM Cabinets November 2017NA-CAB-800FR-504-AC-CSLSD imensions800mm (W) x 800mm (D) x 2000mm (H) + 100mm PlinthAccessFront Access single door, right hand hinged, latch type lock and 2 sets of keys (key N 3524E)Protection CategoryIP54 NEMA 12 Approximate Weight~300 kgColorCabinet RAL7035, Plinth RAL7022 Door FansConfigurable: Continuous run or with thermostat control Temperature MonitoringConfigurable.

9 Thermostat OtherLouvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plateEnvironmental SpecificationsEquipment/rack room installation (HVAC controlled), 30 C in Safe Area locations; Default Certification: CE (Europe); Optional: NoneInput PowerPrimary and Secondary 110 VACP ower Supply RatingFixed 2 x 40 AInternal Power DistributionAC Distribution subassembly (mounted in left side). Fully redundant 24 VDC distribution for CHARM I/O cards and bussed field power through switches and fused terminals (mounted in right side).Local Safety NetworkRedundant 100 BASE-FX, RJ45 connectors, to be connected to each csls carrier. Primary and Secondary Local Safety Network to 3 csls carriers is BOM: Power Supply LS CHARM IO rails, for total of 504 LS I/O, 6 x csls Carrier with redundant Copper Ethernet connectors 42 x CHARM Base Plate 42 x CHARM Address Plug 504 x CHARM terminal blocks - Screw type 6 x CHARM I/O bus termination Base Plate and Channel Identifier LabelsNo DeltaV equipment is included in the base model.

10 All DeltaV equipment is to be configured separately through the Emerson quoting ViewSize of Wire Baskets: 150mm H x 54mm DFront ViewExample Layout and Installed csls CHARM Cabinets November 2017NA-CAB-800FR-504-AC-CSLSTop ViewFront ViewRear ViewExternal Layout Drawing for NA-CAB-800FR-504-AC- csls : Front/Rear and Top csls CHARM Cabinets November 2017NA-CAB-800F-192-AC-CSLSD imensions800mm (W) x 600mm (D) x 2000mm (H) + 100mm PlinthAccessFront Access single door, right hand hinged, latch type lock and 2 sets of keys (key N 3524E)Protection CategoryIP54 NEMA 12 Approximate Weight~200 kgColorCabinet RAL7035, Plinth RAL7022 Door FansConfigurable: Continuous run or with thermostat controlTemperature MonitoringConfigurable: ThermostatOtherLouvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plateEnvironmental SpecificationsEquipment/rack room installation (HVAC controlled), 30 C in Safe Area locations; Default Certification: CE (Europe); Optional: NoneInput PowerPrimary and Secondary 110 VACP ower Supply RatingFixed 2 x 40 AInternal Power DistributionAC Distribution subassembly (mounted in left side).