DataSheet Panel Mount - Crydom

DataSheetPanel MountDo not forget to visit us at: 2017 Crydom Inc. Specifications subject to change without Series IP00 Three-phase solid-state relay; Ratings 25 A, 50 A per phase @ 48-530 VAC 2 package styles IP00 or IP20 (See IP20 spec sheet for more information) SCR output for heavy industrial loads Transient protection built in AC or DC control Zero-crossing (resistive loads) or random-fire (inductive loads) output LED input status indicator UL Recognized, CE Compliant to EN60950-1 PRODUCT SELECTIONC ontrol Voltage 50 A90-280 VACA53TP50D4-32 VDCD53TP50 DAVAILABLE OPTIONSOUTPUT SPECIFICATIONS AC Output (1)Description 50 AOperating Voltage (47-63Hz) [Vrms]48-530 Transient Overvoltage [Vpk] (2)

Title: Panel Mount SSR: 53TP Series IP00 Author: Crydom Inc. Subject: This three-phase SSR features built-in transient protection and SCR output for heavy industrial loads.

Tags:

  Datasheet, Mount, Panels, Datasheet panel mount

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of DataSheet Panel Mount - Crydom

1 DataSheetPanel MountDo not forget to visit us at: 2017 Crydom Inc. Specifications subject to change without Series IP00 Three-phase solid-state relay; Ratings 25 A, 50 A per phase @ 48-530 VAC 2 package styles IP00 or IP20 (See IP20 spec sheet for more information) SCR output for heavy industrial loads Transient protection built in AC or DC control Zero-crossing (resistive loads) or random-fire (inductive loads) output LED input status indicator UL Recognized, CE Compliant to EN60950-1 PRODUCT SELECTIONC ontrol Voltage 50 A90-280 VACA53TP50D4-32 VDCD53TP50 DAVAILABLE OPTIONSOUTPUT SPECIFICATIONS AC Output (1)Description 50 AOperating Voltage (47-63Hz) [Vrms]48-530 Transient Overvoltage [Vpk] (2)

2 1200 Maximum Off-State Leakage Current @ Rated Voltage [mArms]10 Minimum Off-State dv/dt @ Maximum Rated Voltage [V/ sec] (3)500 Maximum Load Current [Arms] (4)50 Minimum Load Current [Arms] Surge Current 50-60 Hz ( ) [Apk]597/625 Maximum On-State Voltage Drop @ Rated Current [Vpk] Resistance Junction to Case (Rjc) [ C/W] I t for Fusing 50-60 Hz ( msec) [A sec]1779/1620 Minimum Power Factor (with Maximum Load) 25 AA53TP25DD53TP25D 25 ModeBlank: Zero Voltage Turn-On-10: Random Turn-OnLoad Current25: 25 Amps50: 50 AmpsControl VoltageD: DC (4-32V)A: AC (90-280V)A53TP25 DThermal PadBlank: Not IncludedH: IncludedH-10 Required for valid part numberFor options only and not required for valid part numberDataSheetPanel MountDo not forget to visit us at: 2017 Crydom Inc.

3 Specifications subject to change without SPECIFICATIONS (1)A53D53 DescriptionControl Voltage Range 4-32 VDC90-280 VrmsMinimum Turn-On VDC90 VrmsMinimum Turn-Off VDC10 VrmsMinimum Input Current (for on-state)19 mA @ mA @ 120 VMaximum Input Current25 mA @ 32V10mA @ 240 VNominal Input ImpedanceCurrent LimiterCurrent LimiterMaximum Turn-On Time [msec] (5)1/2 Cycle501/2 Cycle50 GENERAL SPECIFICATIONS (1)DescriptionDielectric Strength, Input/Output/Base (50/60Hz)Minimum Insulation Resistance (@ 500 V DC)Maximum Capacitance, Input/OutputAmbient Operating Temperature RangeAmbient Storage Temperature RangeWeight (typical)EncapsulationTerminalsScrews and Saddle clampsInput Terminal Screw Torque Range:[in lbs/Nm]Output Terminal Screw Torque Range:[in lbs/Nm]Parameters4000 Vrms109 Ohms 8 pF -40 C to 80 C-40 C to 125 oz (315g)Thermally conductive EpoxyNickel plated BrassZinc plated Steel8-10 / / NOTES1) All parameters at 25 C unless otherwise specified.

4 2) Relay will self trigger between 900-1200 Vpk. 3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph ) Heat sinking required, see page 4 for derating ) Turn-on time for Random turn-on versions is msec (DC Control Models)Maximum Turn-Off Time [msec] DataSheetPanel MountDo not forget to visit us at: 2017 Crydom Inc. Specifications subject to change without DIAGRAM++--LOAD CAN BE WIRED IN EITHER POSITIONACA1 LOADACA2 LOADLOAD CAN BE WIRED IN EITHER POSITIONACB1 LOADACB2 LOADLOAD CAN BE WIRED IN EITHER POSITIONACC1 LOADACC2 LOADTHERMAL DERATE INFORMATIOND53TP50D, D53TP50D60804020510152025204060800 Load Currect [Arms] Max Ambient Temp.

5 [ C]Power DissipationBase Plate Temp [ C]105100110120115A53TP25D, C/W1 C/W1201801506090301020304050204060800 Load Currect [Arms] Max Ambient Temp. [ C]Power DissipationBase Plate Temp [ C] C/W1 C/WDataSheetPanel MountDo not forget to visit us at: 2017 Crydom Inc. Specifications subject to change without APPROVALSI nput:Output:EN61000-4-2, Level 3 ESDEN61000-4-4, Level 3 Burst EN61000-4-2, Level 4 ESDLR Nr. 5941EN61000-4-4, Level 4 BurstEN61000-4-5, Level 4 SurgeEN60950: Meets the requirements of sections : 1,7 : : : : : :Rev. 120811 MECHANICAL SPECIFICATIONST olerances: in / mmAll dimensions are in: inches [millimeters]Agency ApprovalsDataSheetPanel MountDo not forget to visit us at: 2017 Crydom Inc.

6 Specifications subject to change without / PELIGRO / DANGER /GEFAHR / PERICOLO / HAZARD OF ELECTRIC SHOCK, EXPLOSIO N, OR ARC FLASH. Di sconnect all power b efore insta lling or working with th is equipment. Verify all connecti ons and r eplace a ll covers b efore tu rning o n t o f ollow these in structio ns will result in d eath or s erio us inju ry. RIESGO DE DESCARGA ELECTRICA O EXPLOSIO N. Desconecta r to dos los suministr os d e energia a e ste equipo antes de tr abajar con e ste equipo. Verificar todas las conexiones y colocar todas las tapas antes de energizer el in cumplimie nto de e stas in struccio nes puede p rovocar la muerte o le sio nes s eria DE DESCHARGE ELECTRIQUE OU EXPLOSION Ete indre to ute s les sources d' nergie de cet a ppareil avant de tr availler dessus d e c et appareil V rifier tousconnections, etremettre tous couverts enolace avant demettre sousDe n on-suiv i de ces instructio ns provoquera la mort o u d es l sio ns s rieuses s EIN ES ELEKTRISCHEN SCHLAGES ODER EINER EXPLOSIO N.

7 Ste llen Sie jeglichen Str om a b, d er dieses G er t versorgt, bevor S ie an dem Ger t Arbeiten durchf hren Vor d em Dr ehen auf Energie alle Anschl sse berpr fen und alle Abdeckungen ssung die ser Anweisungen k nnen z um Tode o der z u schwerenVerle tzungen f hren. WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE The product's side panels may be hot, allow the product to cool before touching. Follow proper mounting instructions including torque values.

8 Do not allow liquids or foreign objects to enter this to follow these instructions can result in serious injury, or equipment DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER Les panneaux lat raux du produit peuvent tre chauds. Laisser le produit refroidir avant de le toucher. Respecter les consignes de montage, et notamment les couples de serrage. Ne pas laisser p n trer de liquide ni de corps trangers l'int rieur du non-respect de cette directive peut entra ner,des l sions corporelles graves ou des dommages mat Nichtbeachtung dieser Anweisung kannK rperverletzung oder Materialsch den zur Folge VON MATERIALSCH DEN UND GEH USEERHITZUNG Die Seitenw nde k nnen hei sein.

9 Lassen Sie das Produkt abk hlen, bevor Sie es ber hren. Beachten Sie die Montageanweisungen, F hren Sie keine Fl ssigkeiten oder Fremdk rper in das Produkt no se respetan estas precauciones pueden producirse graves lesiones, da os DE DA OS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfr e antes de tocarlo. Respetar las instrucciones de montaje, y en particular los pares de apretado. No dejar que penetren l quidos o cuerpos extra os en el producto. RISCHIO DI SCOSSA ELETTRICA O DELL E SPLOSIONE.

10 Spenga tu tt a l'alimenta zioneche f ornisce questa apparecchiaturaprima d i lavorarea questa apparecchiatura Verificare t utti i c ollegamenti e s osti tu ire tu tte le coperture prima dell accensioneL'omis sio ne d i queste istruzioni provocher l a morte ole sio ni serieLa mancata osservanza di questa precauzione pu causare gravi rischi per l'incolumit personale o danni alle DI DANNI MATERIALI E D'INVOLUCRO CALDO I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo. Seguire le istruzioni di montaggio corrette.