Transcription of DCC Commercial - daikinac.com
1 2/18* Complete warranty details available from your local dealer or at Standard Features R-410A chlorine-free refrigerant High-efficiency scroll compressors Two-stage cooling Copper tube / aluminum fin coils (7 - 10 Ton) Micro-Channel indoor & outdoor coils (12 Ton) Power block for field wiring High- and low-pressure switches High-capacity, steel-cased filter drier Heater kits with single-point entry Cabinet Features Heavy-gauge, galvanized- steel cabinet with UV-resistant powder-paint finish Built-in filter rack with standard 2 filters Convertible airflow orientation Easy to service Full perimeter rail Sloped drain pan 24-volt terminal strip Units meet the performance outlined in Table of ASHRAE Standard AHRI Certified; ETL ListedDCC Commercial7 - 12 Ton Packaged Air ConditionersUp to EERC ooling Capacity: 88,000 146,000 BTU/h ContentsNomenclature.
2 2 Product Specifications ..4 Expanded Cooling Data ..8 Airflow Data ..16 Crankcase Heater ..20 Electrical Data / Heat Kit Data ..21 Dimensions ..29 Wiring Diagrams ..34 for Models with DDC Controls ..42 Accessories .. DCC0900453V**A*1234,5,67,8,9101112131415 16 Revision LevelsMajor & MinorBrandFactory-Installed OptionsDDaikinXNo OptionsANon-powered convenience outletConfigurationBPowered convenience outletCStandard Efficiency (6 - 25 Tons)CLow-ambient kitSStandard Efficiency (3 - 5 Tons)DReturn air smoke detectorTHigh Efficiency (3 - 5 Tons)ESupply air smoke detectorFNon-powered convenience outlet; ApplicationLow-ambient kitCCooling1 GNon-powered convenience outlet; GGas HeatReturn air smoke detectorHHeat Pump1 HNon-powered convenience outlet;Supply air smoke detectorNominal Cooling Capacity JNon-powered convenience outlet.
3 0363 Tons1028 Tons30025 TonsReturn & Supply air smoke detectors0484 Tons12010 TonsKNon-powered convenience outlet;0605 Tons15012 tonsLow-ambient kit; Supply air smoke detector0726 Tons18015 TonsLNon-powered convenience outlet; 0907 Tons24020 TonsLow-ambient kitReturn & Supply air smoke detectorsNominal Heating CapacityMPowered convenience outlet;Gas/Electric A/C H/P Factory-Installed Electric HeatLow-ambient kit045 45,000 BTU/hXXXNo HeatNPowered convenience outlet;090 90,000 BTU/h01010 kW03030 kWReturn air smoke detector115115,000 BTU/h01515 kW03130 kWOPowered convenience outlet;140140,000 BTU/h01615 kW04545 kWReturn & Supply air smoke detectors210210,000 BTU/h01818 kW04645 kWPPowered convenience outlet;350350,000 BTU/h02020 kW06060 kWSupply air smoke detector400400,000 BTU/h02525 kWQPowered convenience outlet; Low-ambientSee product specifications for heat size(s) available for each ; Return air smoke detectorRPowered convenience outlet; Low-ambientVoltagekit; Supply air smoke detector1208-230/1/60 (DS* & DT* 3-5 Tons models only)4460/3/60 TPowered convenience outlet; Low-ambient3208-230/3/607575/3/60kit; Return & Supply air smoke detectorsUNon-powered convenience outlet.
4 Supply Fan/Drive Type/MotorLow-ambient kit; Return air smoke detectorBBelt Drive (3-5 Tons single speed models only) VTwo-Speed Belt Drive VLow-ambient kit; Return air smoke detectorDDirect Drive (3-5 Tons single speed models only)(6-25 Tons only)WLow-ambient kit; Supply air smoke detectorHHigh Static (3-5 Tons single-speed BeltWHigh Static (6-25 TonsYLow-ambient kit; Return & SupplyDrive models only)two-speed Belt Driveair smoke detectorsmodels only)ZReturn & Supply air smoke detectorsFactory-Installed OptionsAUltra Low-Leak Downflow EconomizerRUltra Low-Leak Downflow Economizer;BDDC-BACnet protocol DDC-BACnet protocol; FUltra Low-Leak Downflow Economizer; Disconnect Switch (non-fused)Factory-Installed OptionsDDC-BACnet protocolVLow-Leak Downflow EconomizerXStandard Aluminized Heat ExchangerHDisconnect Switch (non-fused)WLow-Leak Downflow EconomizerSStainless-Steel Heat ExchangerJUltra Low-Leak Downflow Economizer;Disconnect Switch (non-fused)DHinged PanelsDisconnect Switch (non-fused)XNo OptionsKStainless-Steel Heat Exchanger; MDisconnect Switch (non-fused); DDC-BACnet protocolHinged PanelsBPhase MonitorNote: Not all options available for all Steel Heat Exchanger; Phase Monitor1 X= No Options in character 13thMHinged Panel.
5 Phase MonitorLStainless-Steel Heat Exchanger; Hinged Panels; Phase Options Stainless-Steel Heat Exchanger (Gas units only): A tubular heat exchanger made of 409-type stainless steel is installed in the unit. Low-Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3- to 6-ton units, cooling operation is extended from 60 F ambient temperature to 35 F outside air temperature. On 7 -20 ton units, cooling operation is extended from 35 F ambient temperature to 0 F outside air temperature. For 25 ton units, cooling operation is extended from 24 F ambient temperature to 0 F outside air temperature. Economizers (Downflow): Based on air conditions, can provide outside air to cool the space.
6 Electric Heat Kits (AC and heat pump units only): Available in all voltage options. Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs power to the outlet. Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit. When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by for 208/230V units, increase by for 460V units, and by for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly. Disconnect Switch (non-fused; 3-phase units only): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the unit.
7 Please note that for air conditioning (DSC units) and heat pump models (DSH units), the appropriate electric heat kit must be ordered to be factory-installed along with the disconnect switch (non-fused) when it is ordered. Please note that for models with a powered convenience outlet option and a disconnect switch (non-fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-fused) is in the off position. Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit. Hinged Access Panels: Allows access to unit s major components.
8 Combined with latches for easy access to control box, compressor, filters and blower motor. Available on all units. Phase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series models. Phase monitor shall provide protection for motors and compressors against problems caused by phase loss, phase reversal and phase unbalance. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. DDC Controller: DDC communicating controller, available for 3 - 25 ton DS, DC and DT series models with on-board BACnet communication interface. High static belt drive assembly, factory Specifications 7 TonsDCC090**3V**B*DCC090**4V**B*DCC090** 7V**B*Cooling CapacityTotal BTU/h88,00088,00088,000 Sensible BTU/h65,10065,10065,100 EER / / / / Reference #s704191070419107041910 Evaporator Motor / CoilMotor Type2-speed Belt Drive2-speed Belt Drive2-speed Belt DriveIndoor Nominal CFM3,0003,0003,000 Indoor Motor FLA (Cooling) / RPM2 / 1740-11602 / 1740-11602 / 1745-1170 Piston Size (Cooling) Size (Qty)(4) 16 x 20 x 2(4) 16 x 20 x 2(4) 16 x 20 x 2 Drain Size (NPT) " " "R-410A Refrigerant Charge Cir #1 & #2100 Coil Face Area (ft )
9 Deep / Fins per Inch4/164/164/16 Belt Drive Evap Fan Data# of Wheels (D x W)1 (15" x 12")1 (15" x 12")1 (15" x 12")Motor Sheave / Blower SheaveVL40 / AK74VL40 / AK74VL40 / AK74 Belt AX51AX51AX51 Condenser Fan / CoilQuantity of Condenser Fan Motors222 Horsepower - RPM - 1075 - 1075 - 1,075 Fan Diameter / # Fan Blades22 / 422 / 422 / 4 Outdoor Nominal CFM7,2007,2007,200 Face Area (ft ) Deep / Fins per Inch2 X2 / 27 1'2 X2 / 27 1'2 X2 / 27 1 CompressorQuantity / Type / Stage2 / Scroll / 12 / Scroll / 12 / Scroll / 1 Compressor RLA / LRA / / / DataVoltage-Phase-Frequency208/230-3-604 60-3-60575-3-60 Standard Motor Max. External " " "Outdoor Fan HP / RLA(2) / (2) / (2) / Circuit Ampacity / Overcurrent Protection (amps) 50 / 502015 Entrance Power SupplyLocatingDimpleLocatingDimpleLocati ngDimpleEntrance Control VoltageOperating Weight (lbs)101010101010 Ship Weight (lbs)108510851085 Wire size should be determined in accordance with National Electrical Codes.
10 Extensive wire runs will require larger wire sizes. May use fuses or HACR-type circuit breakers of the same size as : Always check the S&R plate for electrical data on the unit being Specifications 8 TonsDCC102**3V**B*DCC102**4V**B*DCC102** 7V**B*Cooling CapacityTotal BTU/h100,000100,000100,000 Sensible BTU/h69,00069,00069,000 EER / Reference #s737092373709237370923 Evaporator Motor / CoilMotor Type2-speed Belt Drive2-speed Belt Drive2-speed Belt DriveIndoor Nominal CFM3,2003,2003,200 Indoor motor FLA (Cooling) - RPM2 / 1740-11602 / 1740-11602 / 1745-1170 Piston Size (Cooling) Size (Qty)(4) 16 x 20 x 2(4) 16 x 20 x 2(4) 16 x 20 x 2 Drain Size (NPT)