Transcription of Disconnect Switches
1 5-11 Siemens Industry, Inc. SPEEDFAX 2011 Product Catalog5 Disconnect SWITCHESP roduct Category HDSSS iemens / Speedfax Previous folio:4-11 Updated by S Spencer 10-20-10 Featuresb 30, 60, 100 and 200 Ampere Switchesb UL Recognized (file # E121152 vol. 1 & 2) and CSA Certifiedb Simple Mounting with an integral switch and over center mechanismb Horsepower & load break ratedb Compact Sizeb Visible Blade Contactsb Rugged Construction with a short circuit current rating of 10,000 amps with Class H or 200,000 amps at 600V maximum AC, when fused with Class R or Class J fusesb Available with three operator handle options, allowing flexible placement of switchb Field Installable Auxiliary Contactsb Flexible Fuse Class Configurationsb Flange mounted handles meet NFPA79 requirementsOrdering Information1.
2 Select the basic switch size you need (30, 60, 100 or 200 ampere).2. Check the switch selected against the maximum horsepower rating required for our application. L or R suffix on switch catalog numbers denotes left or right-handed mechanism Choose either fuse or no fuse kit from chart below. Information4. Check Minimum Dimensions on page 5-12 for installation space Select from the list of handle operators, the type which best suits your application. Handle operators can be selected from the next Built to order. Allow 6 8 weeks for For copper only connectors, order as follows:Fusible order standard switch, standard fuse kit and cop-per only no fuse kit.
3 Non-Fusible order standard switch and copper only no fuse Includes both line and load For Class R fuses order Class H kit from this table and the Class R conversion kit from the next HP ratings for time delay fuses and for 250V DC also apply to Non-fusible MCS Disconnect Switch with Max-Flex handle operatorType MCS Disconnect Switch with rotary handleType MCS Disconnect Switch with fixed-depth, flange-mounted handleBasic Switches Maximum Horsepower Rating, 3 Phased Catalog Catalog 240 Volts AC 480 Volts AC 600 Volts AC 250 Switch Maximum Number Number Time Time Time Volts Ampere Voltage Right Left Standard Delay Standard Delay Standard Delay DC Rating Rating Hand Hand Fuse Fuse Fuse Fuse Fuse Fuse (max)d 130 600 MCS603R MCS603L 13 171 2 15 115 171 2 120 15 160 600 MCS606R MCS606L 171 2 15 15 130 15 150 10 100 600 MCS610R MCS610Ls 15 30 25 160 30 175 20 200 600 MCS620R MCS620Ls 25 60 50 125 60 150 40 Fuse And No Fuse Kits (Includes load base plus line and load fuse clips)
4 ABasicSwitchAmpereRatingSwitchCatalogNum berKitDescriptionNo Fuse KitsFor Class HFor Class JFor Class RLugWireSizeStandardCu OnlybCatalog Number aCatalog Number aCatalog Number aCatalog NumberCatalog Number130 MCS603 Ror MCS603 LNo FuseTMK606 30A, 250V FCK203s FCRK203#14 to30A, 600V FCK206 FCJK603 FCRK206#4 AWG60A, 250V FCK206 FCRK206Cu/AI60A, 600V FCK606 FCJK606 FCRK606160 MCS606 RorMCS606 LNo FuseTMK606 60A, 250V FCK206 FCRK206#14 to60A, 600V FCK606 FCJK606 FCRK606#4 AWG100A, 250V OFCK661sOFCK661scCu/AI100A, 600V OFCK661sOFCK661sc100 MCS610 RorMCS610 LNo FuseTMK610 TMK610C 100A, 250V FCK610 FCK610c#14 to100A, 600V FCK610 FCK610c#2/0 AWG200A, 250V OFCK620 OFCK620cCu/AI200A, 600V OFCK620 OFCK620c200 MCS620 RorMCS620 LNo FuseTMK620 TMK620Cs #6 to200A, 250V FCK620 FCK620c300 kcmil200A, 600V FCK620 FCK620cCu/AIDisconnect SwitchesType MCS (30-200A) Switches , Fuse and No Fuse Kits Selection Siemens Industry, Inc.
5 SPEEDFAX 2011 Product Catalog5-125 Disconnect SWITCHESP roduct Category HDSS & MCCBs Built to order. Allow 6 8 weeks for For Type 4 and 4X applications, order handle onlyCatalog Number 100A - FDH104 200A - FDH204b For Type 4 and 4X applications, order handle onlyCatalog Number FHOHS4c Standard cable length is 36 inches. Alternate lengths are available as follows: Length Amps Cat. No. 48" 30 100 FHOEC048 60" 30 100 FHOEC060 48" 200 FHOJC048 60" 200 FHOJC060d For Type 4 and 4X applications, order handle onlyCatalog Number RHOH4e For Type 3 and 3R applications, order handle onlyCatalog Number RHOHf Min. enclosure depth from mounting pan to handle mount-ing surfaces: 30-100A Inches 200A Inches*For millimeters multiply inches by Space RequirementsMinimum Dimensions (inches*) Switch Catalog Fuse Number Size A B C Class 30A/240V H, K, R MCS603 30A/600V H, K, R 30A/600V J 60A/240V H, K, R MCS606 60A/600V H, K, R 60A/600V J 100A/240V H, K, R MCS610 100A/600V H, K, R 100A/600V J 200A/240V H, K, R MCS620 200A/600V H, K, R 200A/600V J A Dimension is measured from each cross bail pin.
6 B Dimension is measured from line side barrier to load side barrier. C Dimension is measured from line side terminal of switch to load side terminal of fuse load Disconnect Switch Panel Space RequirementsSiemens / Speedfax Previous folio: 4-12 Updated by S Spencer 10-20-10 Auxiliary Switch KitsSwitchCatalog NumberContact Arrangement1 NO/1 NCCatalog Number2 NO/2 NCCatalog NumberMCS603 RMCSAKR136 MCSAKR236 MCS603 LMCSAKL136 MCSAKL236sMCS606 RMCSAKR136 MCSAKR236 MCS606 LMCSAKL136 MCSAKL236sMCS610 RMCSAK116 MCSAK216 MCS610 LMCSAK116 MCSAK216 MCS620 RMCSAK126 MCSAK226 MCS620 LMCSAK126 MCSAK226 Class R Fuse Conversion KitsFuse Clip RatingCatalog Number100A, 600 VSSRK33200A, 600 VSSRK34 Fuse Ejector KitsSwitchCatalog NumberFuse Ejector KitCatalog NumberMCS610FE100sMCS620FE200sHandle OperatorsFixed Depth, Flange Mounted, Types 1, 3, 3R.
7 12afSwitchCatalog NumberComplete Handle MechanismHandle OnlySwitch Operator OnlyCatalog NumberCatalog NumberCatalog NumberMCS603 RFDFS06 RFDH10 FDS06 RMCS603 LFDFS06 LFDH10 FDS06 LMCS606 RFDFS06 RFDH10 FDS06 RMCS606 LFDFS06 LFDH10 FDS06 LMCS610 RFDFS06 RFDH10 FDS06 RMCS610 LFDFS06 LFDH10 FDS06 LMCS620 RFDFS20 RFDH20 FDS20 RMCS620 LFDFS20 LFDH20 FDS20 LVariable Depth, Flange Mounted Max-Flex , Types 1, 3, 3R, 12bSwitchCatalog NumberComplete Handle MechanismHandle OnlySwitch Operator OnlyCable OnlycCatalog NumberCatalog NumberCatalog NumberCatalog NumberMCS603 RFHOS06036 RFHOHSFHOS06 RFHOEC036 MCS603 LFHOS06036 LFHOHSFHOS06 LFHOEC036 MCS606 RFHOS06036 RFHOHSFHOS06 RFHOEC036 MCS606 LFHOS06036 LFHOHSFHOS06 LFHOEC036 MCS610 RFHOS06036 RFHOHSFHOS06 RFHOEC036 MCS610 LFHOS06036 LFHOHSFHOS06 LFHOEC036 MCS620 RFHOS20036 RFHOHSFHOS20 RFHOJC036 MCS620 LFHOS20036 LFHOHSFHOS20 LFHOJC036 Variable Depth Rotary, Through-The-Door-Mounted, Types 1.
8 12deVariable DepthShaft Only Variable DepthMCS603 RCRHOS06 VDCRHOHRHOS06 RHOSVDMCS606 RCRHOS06 VDCRHOHRHOS06 RHOSVDMCS610 RCRHOS06 VDCRHOHRHOS06 RHOSVDMCS620 RCRHOS20 VDRHOHRHOS20 RHOSVDD isconnect SwitchesType MCS (30-200A) Accessories 5-13 Siemens Industry, Inc. SPEEDFAX 2011 Product Catalog5 Disconnect SWITCHESS iemens / Speedfax Previous folio:ICP 2010 18-27 Updated by S Spencer 10-20-10 Revised 04/30/15 Featuresn 30 - 800A ratingsn UL Listed under file #E121152 & CSA Certified under file #222227n Door mounted rotary handles with defeatable cover interlockn Meets UL requirements for both main and branch circuit applicationsn Compact sizen 100kA with Class CC fuses or up to 200kA with Class J fusesn Load break and horsepower ratedn Quick make and break operationn All handles are padlockable with up to (3) padlocks with 5/16 hasps in the OFF positionOrdering information1.
9 Select the panel mounted switch required based on Ampere, HP and AIC requirements. Switches with a right hand mechanism are standard, 30-100A Switches with a left hand mechanism are Select handle based on environmental rating Select operating shaft (200 or 400mm in length). For enclosure depths of or less from panel mounting surface to inside of door use 200mm long shafts. For deeper enclosures use 400mm long shafts. 30A 100kA Switches can be used in 10 deep enclosures (panel to inside of door) with 200mm shaft and CFSH5N : Be sure to check shaft and handle compatibility with the switch selected by using information provided in the selection Line & load lugs are provided as standard on 30-100A Switches .
10 Terminal kits are available for 200-800A Switches if Auxiliary contact are available if needed as 30A switch CFS361C5 and non-fusible 30A switch CNFS361 will accept up to (4) aux contactsB. 30A switch CFS361J5 will accept up to (2) aux con-tacts without an aux contact holder. If more than (2) aux contacts are required order aux contacts PLUS aux contact holder kit CFSAUXH1. All other Switches will accept up to (4) aux If non-fusible switch is required order a shorting bar for 60-600A Switches or catalog number CNFS361 for 30-100A Switches are designed to prevent inadvertent contact with live parts and shields are not required.