Example: barber

ENVIROTEMP FR3™ FLUID - nttworldwide.com

DESCRIPTIONE nvirotemp FR3 FLUID is a Fire ResistantNatural Ester based dielectric coolant specifically for-mulated for use in distribution transformers where itsunique environmental, fire safety, chemical, and elec-trical properties are FR3 FLUID is formulated from edibleseed oils and food grade performance enhancingadditives. It does not contain any petroleum, halo-gens, silicones or any other questionable material. Itquickly and thoroughly biodegrades in both soil andaquatic environments. The FLUID tested non-toxic inaquatic toxicity tests. It is tinted green to reflect itsfavorable environmental profile. ENVIROTEMP FR3 FLUID has an exceptionally highfire point of 360 C and flash point of 330 C.

DESCRIPTION Envirotemp® FR3™ fluid is a Fire Resistant Natural Ester based dielectric coolant specifically for-mulated for use in distribution transformers where its ...

Tags:

  Fluid, Envirotemp fr3 fluid, Envirotemp, Fr3 fluid

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of ENVIROTEMP FR3™ FLUID - nttworldwide.com

1 DESCRIPTIONE nvirotemp FR3 FLUID is a Fire ResistantNatural Ester based dielectric coolant specifically for-mulated for use in distribution transformers where itsunique environmental, fire safety, chemical, and elec-trical properties are FR3 FLUID is formulated from edibleseed oils and food grade performance enhancingadditives. It does not contain any petroleum, halo-gens, silicones or any other questionable material. Itquickly and thoroughly biodegrades in both soil andaquatic environments. The FLUID tested non-toxic inaquatic toxicity tests. It is tinted green to reflect itsfavorable environmental profile. ENVIROTEMP FR3 FLUID has an exceptionally highfire point of 360 C and flash point of 330 C.

2 It has thehighest ignition resistance of less-flammable fluidscurrently available. It is referred to as a High FirePoint or "Less-Flammable" FLUID , and is Listed as aLess-Flammable Dielectric Liquid by Factory Mutualand Underwriters Laboratories for use in complyingwith the National Electric Code (NEC ) and insur-ance FR3 FLUID is compatible with standardtransformer insulating materials, components and withfluid processing equipment and procedures. It demon-strates improved thermal characteristics with a vis-cosity closer to conventional transformer oil, superiordielectric strength in new and continued service appli-cations, and excellent chemical stability over time.

3 Because of it excellent environmental, fire safetyand performance characteristics applications forEnvirotemp FR3 FLUID have expanded into a variety ofother equipment, including sectionalizing switches,transformer rectifiers, electromagnets, and voltagesupply circuits for luminaries. Other potential applica-tions under study include voltage regulators, high volt-age cables, and power substations. The FLUID is alsoused in retrofill applications for other FLUID filled distri-bution equipment. ENVIROTEMP FR3 FLUIDB ulletin 00092 Product InformationJune, 2001(Supersedes May, 2001)TYPICAL INITIAL ENVIROTEMP FR3 FLUID PROPERTIESP ropertyValueTest MethodElectricalDielectric Strength56 kV @ 25 C ( gap)ASTM D181647 kV @ 25 CASTM D877 Relative @ 25 CASTM D924[Dielectric Constant]Dissipation @ 25 CASTM D924[Power Factor]Volume Resistivity30 X1012 -cm @ 25 CASTM D1169 Impulse Strength 226 kV @ gapASTM D3300(Sphere to Sphere)Gassing Tendency-79 ( L/min.)

4 ASTM D2300 Physical and ChemicalSpecific @ 25 CASTM D1298 Interfacial Tension27 mN/m @ 25 CASTM 9045 CNeutralization (Acid) mg KOH/gASTM D974 NumberKinematic Viscosity33 cSt @ 40 CASTM D4458 cSt @ 100 CMoisture Content20 mg/kgASTM 1533 BPercent Saturation of1 - 2%CPS MethodMoistureAir Solubility16% @ 25 C @ 1 D2779 AppearanceClear, Light GreenASTM D1524 ColorL D1500 ThermalFlash Point (Closed Cup)316 CASTM D93 Flash Point (Open Cup)330 CASTM D92 Fire Point (Open Cup)360 CASTM D92 Pour Point-21 CASTM D97 Thermal X 10-4 CPS Methodcal/(cm sec C) @ 25 CSpecific (cal/gm/ C) @ 25 CASTM D2766 Coefficient of x 10-4/ C @ 25 CCPS MethodHeat @ 50 CASTM @ 100 CEnvironmental PropertiesBOD/COD Ratio45%APHASM5210 BAquatic Biodegradation100%EPA OPPTS Toxicity to Trout FryZero Mortality to OECD Test End Point203 The typical properties shown above are for new FLUID prior to factoryshipment.

5 These properties are subject to change without CPS Dielectric Fluids Products for recommended accep-tance values. Ask for ENVIROTEMP FR3 FLUID Specification Guideline,Bulletin unique chemical structure of EnvirotempFR3 FLUID provides superior performance characteris-tics. The FLUID maintains its dielectric strength muchbetter than other dielectric fluids when used as aload-break switch medium, and has the lowestgassing tendencies under electrical stress. Its cool-ing performance is superior to other less-flammablefluids. It has lower viscosity at operating tempera-tures than other less-flammable fluids. The fluidexhibited no measurable change in viscosity overexhaustive testing cycles.

6 It has superior resistanceto coke and sludge formation when compared toconventional transformer oil. Under the same accel-erated coking tests, ENVIROTEMP FR3 FLUID producedless than 1/20 of carbonaceous coke than that pro-duced in mineral oil. Doble Laboratories sludge-freelife test resulted in no measurable Stability TestEnvirotemp FR3 FLUID has an exceptional abilityto draw out retained moisture and absorb water driv-en off by aging paper. It also chemically helps pre-vent the paper molecules from severing whenexposed to heat. These attributes enable the fluidto significantly minimize the rate of aging of trans-former insulating paper. Tests have shown thatpaper aged in ENVIROTEMP FR3 FLUID takes 5-8 timeslonger to reach the same end-of-life points as paperaged in conventional transformer following chart shows a comparison of thetime to reach insulation end-of-life for thermallyupgraded Kraft paper aged in conventional trans-former oil and ENVIROTEMP FR3 FLUID .

7 Time to insula-tion end-of-life using IEEE transformer load-ing guide calculation included for Insulating Paper End-of-Life (Hours)150 C170 CEnd-of-LifeMineralEnvirotempIEEEM ineralEnvirotempIEEEB asisOilFR3 FluidBasisOilFR3 FluidBasisRetained TensileStrength50%3100>4000*160224013003 2325%4000>4000*33274904000671 Degree of Polymerization2003200>4000*3697480340074 6* Paper did not reach end-of-life over the duration of the test. Tobe conservative, extrapolation was not SAFETYE nvirotemp FR3 FLUID has a fire point of 360 C,well above the NEC minimum of 300 C. Its flash point(330 C) is higher than the fire point of most other cur-rently available less-flammable fluids.

8 EnvirotempFR3 FLUID is certified as a less-flammable dielectriccoolant by Factory Mutual and UnderwritersLaboratories in compliance with the listing require-ments of the NEC. The National Fire ProtectionAssociation has no reports of fires or explosionsinvolv-ing transformers filled with ENVIROTEMP FR3 & Fire Point of Dielectric Fluids ( C)In large and small-scale tests, ENVIROTEMP FR3fluid has demonstrated greater fire resistance thanother askarel substitutes. Based on large-scale test-ing, Factory Mutual Research concluded that theprobability of a pool fire evolving the FLUID was so low,that it does not require heat release rate to be deter-147276300330165312343360 ConventionalTransformer OilR-Temp FluidSilicone OilEnvirotemp FR3 FluidFlash PointFire PointLeft to right: ENVIROTEMP FR3 FLUID , R-Temp FLUID and ConventionalTransformer Oil after 120 hours at 165 of 8mined nor applied in determining the installationrequirements of the FLUID .

9 Factory Mutual acceptsEnvirotemp FR3 FLUID for transformers Approved perFM Standard 3990. OSHA has recognized this FMstandard as fitting the definition of a Listed andLabeled product per NEC Section 110-3(b). The stan-dard permits ENVIROTEMP FR3 FLUID -filled transformersto be installed indoors, typically without sprinklers orvaults, with minimum clearance to walls of just Laboratories developed Standard340 to compare the fire hazard rating of different flu-ids. The following graph demonstrates the favorablerating assigned to ENVIROTEMP FR3 FLUID . Fire Hazard Rating UL Standard 340 MEETING THE CODESLess-Flammable fluids are recognized as a firesafeguard by Section 15 of the National ElectricalSafety Code (Accredited Standards Committee C2).

10 ENVIROTEMP FR3 FLUID meets the National ElectricalCode Section 450-23 requirements as alisted less-flammable liquid. It is covered by OSHA Article , Section 5(v). ENVIROTEMP FR3 FLUID is Factory Mutual Approvedand UL Classified "Less-Flammable" per NEC Article450-23, fitting the definition of a Listed Product perNEC. For additional information, request the NECR equirement Guidelines, Bulletin & HEALTHE nvirotemp FR3 FLUID is specifically formulated tominimizehealth and environmental risk. It is made offood grade seed-oils and food grade performanceenhancing additives. The base oils come from renew-able resources - commodity seeds - and are easilyrecyclable and reusable.


Related search queries