1 Installation InstructionsEthernet-to- devicenet Linking DeviceCatalog Number 1788-EN2 DNThis publication tells you how to install the 1788-EN2DN Ethernet-to-DeviceNet Linking Device and use RSNetWorx for devicenet software to configure User Information2 About the Linking Device6 System Requirements7 Installing and Configuring the Linking Device8 Using Diagnostic Web Pages44 Dimensions49 devicenet Connector Pinouts50 ethernet /IP RJ45 Connector Pinouts50 Specifications51 Additional Resources552 Ethernet-to-DeviceNet Linking Device rockwell automation Publication 1788-IN055C-EN-P - September 2011 Important User InformationSolid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication available from your local rockwell automation sales office or online at ) describes some important differences between solid-state equipment and hard-wired electromechanical devices .
2 Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is no event will rockwell automation , Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular Installation , rockwell automation , Inc. cannot assume responsibility or liability for actual use based on the examples and patent liability is assumed by rockwell automation , Inc. with respect to use of information, circuits, equipment, or software described in this of the contents of this manual, in whole or in part, without written permission of rockwell automation , Inc.
3 , is this manual, when necessary, we use notes to make you aware of safety : Identifies information about practices or circumstances that can cause an explosion in a hazardous environment , which may lead to personal injury or death, property damage, or economic : Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous information that is critical for successful application and understanding of the Linking Device 3 rockwell automation Publication 1788-IN055C-EN-P - September 2011 North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous sur l utilisation de cet quipement en environnements marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
4 Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of produits marqu s "CL I, DIV 2, GP A, B, C, D" ne conviennent qu' une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livr avec des marquages sur sa plaque d'identification qui indiquent le code de temp rature pour les environnements dangereux. Lorsque plusieurs produits sont combin s dans un syst me, le code de temp rature le plus d favorable (code de temp rature le plus faible) peut tre utilis pour d terminer le code de temp rature global du syst me.
5 Les combinaisons d' quipements dans le syst me sont sujettes inspection par les autorit s locales qualifi es au moment de l' :Explosion Hazard - Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. Substitution of components may impair suitability for Class I, Division 2. If this product contains batteries, they must only be changed in an area known to be :Risque d Explosion Couper le courant ou s'assurer que l'environnement est class non dangereux avant de d brancher l' quipement. Couper le courant ou s'assurer que l'environnement est class non dangereux avant de d brancher les connecteurs.
6 Fixer tous les connecteurs externes reli s cet quipement l'aide de vis, loquets coulissants, connecteurs filet s ou autres moyens fournis avec ce produit. La substitution de composants peut rendre cet quipement inadapt une utilisation en environnement de Classe I, Division 2. S'assurer que l'environnement est class non dangereux avant de changer les Ethernet-to-DeviceNet Linking Device rockwell automation Publication 1788-IN055C-EN-P - September 2011 European Hazardous Location ApprovalThe following applies when the product bears the Ex equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN.
7 This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 equipment shall be used within its specified ratings defined by rockwell shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this not disconnect equipment unless power has been removed or the area is known to be : This equipment is not resistant to sunlight or other sources of UV Linking Device 5 rockwell automation Publication 1788-IN055C-EN-P - September 2011 environment and EnclosureATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment , in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
8 Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety addition to this publication, see the following: Industrial automation Wiring and Grounding Guidelines, publication , for additional Installation requirements NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosuresATTENTION: Prevent Electrostatic DischargeThis equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation.
9 Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. Use a static-safe workstation, if available. Store the equipment in appropriate static-safe packaging when not in Ethernet-to-DeviceNet Linking Device rockwell automation Publication 1788-IN055C-EN-P - September 2011 About the Linking DeviceThe 1788-EN2DN Ethernet-to-DeviceNet Linking Device lets you seamlessly connect your information- or control-level networks with your Device -level Linking Device provides full devicenet master functionality, so you can connect up to 63 devicenet slave devices to an ethernet TCP/IP interface that supports the ethernet /IP network and an HTTP web server. As examples, you could use the Linking Device : as a gateway to connect information- or control-level networks to Device -level networks for programming, configuration, control, or data collection.
10 As a router/bridge to connect the ethernet /IP network to the devicenet Linking Device provides centralized data storage, or I/O tables, for data shared between the devicenet and ethernet /IP networks. Data is placed into the I/O tables by one network interface, allowing the data to be read through the other network Linking Device appears as a single Device on either network by using standard protocol mechanisms. No special, or extended, protocol features are required for the devices on either network to read or write the data flowing through the I/O tables; all cross-network activity is transparent to the devices on either connections, whether power or fieldbus, to the Linking Device are made on one end of the module. Phoenix connectors are provided for power and devicenet connections. A RJ45 style connector is provided for ethernet /IP connection. The Linking Device can be mounted to a DIN Linking Device 7 rockwell automation Publication 1788-IN055C-EN-P - September 2011 System RequirementsThe following hardware and software components are required to use the Linking Hardware 1788-EN2DN Linking Device devicenet cabling , power, and devices forming a devicenet network ethernet cabling and power Computer with access to the ethernet network Computer running devicenet configuration softwareThe devicenet slave devices with which the Linking Device communicates are specified using a devicenet Configuration Software tool such as RSNetWorx for devicenet software.