Exit Discharge Application Guide - Acuity Brands

exit Discharge Application Guide for Normally-off Fixtures Traditional emergency lighting and exit signs were primarily focused on guiding occupants to the exterior of a building. Today, an additional focus is being placed on getting occupants to an exit safely and down a path of safety once they are out of the building. This Guide will help define the exit Discharge , reference code requirements for the exit Discharge , and identify products that can be applied to meet exit Discharge requirements. Either normally-on or normally- off fixtures can provide exit Discharge illumination. However, this Guide will only cover normally-off remote fixtures. Interior - Exterior- Normal or conditioned space Damp or wet location Path o Path off egress egress exit Discharge exit Discharge exit Discharge Description The exit Discharge is the portion of the Since the nature of the exit Discharge is means of egress between the building exit outdoor applications , standard luminaires and the public way.

Exit Discharge The exit discharge is the portion of the means of egress between the building exit and the public way. According to the 2009 Life Safety Code, section 3.3.175, a public

Tags:

  Guide, Applications, Discharge, Exit, Exit discharge application guide

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Exit Discharge Application Guide - Acuity Brands

1 exit Discharge Application Guide for Normally-off Fixtures Traditional emergency lighting and exit signs were primarily focused on guiding occupants to the exterior of a building. Today, an additional focus is being placed on getting occupants to an exit safely and down a path of safety once they are out of the building. This Guide will help define the exit Discharge , reference code requirements for the exit Discharge , and identify products that can be applied to meet exit Discharge requirements. Either normally-on or normally- off fixtures can provide exit Discharge illumination. However, this Guide will only cover normally-off remote fixtures. Interior - Exterior- Normal or conditioned space Damp or wet location Path o Path off egress egress exit Discharge exit Discharge exit Discharge Description The exit Discharge is the portion of the Since the nature of the exit Discharge is means of egress between the building exit outdoor applications , standard luminaires and the public way.

2 According to the 2009 may not be suitable. Outdoor applications Life Safety Code, section , a public fall into two categories: damp location or wet way is defined as "A street, alley or other location. According to chapter one, article similar parcel of land essentially open to the 100, of the 2008 National Electrical Code, outside air deeded, dedicated, or otherwise damp locations include "..partially protected permanently appropriated to the public for locations under canopies, marquees, roofed public use and having a clear width and open porches, and like locations.." Wet height of not less than 30ft (50mm) (120in)." location is partially defined as "..locations subject to saturation with water or other See page 4 for Code information. liquids, such as vehicle washing areas;. and in unprotected locations exposed to weather.". Sheet #: RAUE - 420.

3 Remote Fixtures In general, remote fixtures offer In many instances, the battery unit can advantages such as lower initial cost, lower be installed in a normal or conditioned maintenance costs, and better aesthetics environment with the remote heads located over typical emergency battery units. in the areas that require special ratings. These advantages are more prevalent in environments that require special ratings The following chart lists normally-off remote such as wet location and NEMA 4X, or fixtures that may be used in damp or in areas where ambient temperatures can wet locations. Please consult the Lithonia diminish battery capacity or life. Both Lighting Product Selection Guide for lamp occurances are common with the exit type, voltage, and wattage. Discharge . Wall Ceiling Cold Fixture Description Lamp Mount Mount Wet Damp Weather AFN Architectural die-cast Xenon x x x x -40oC to 60oC.

4 PAR36. ELA RG Recessed gimbal Halogen x x incandescent Recessed 3 adjustable ELA LV3 OC specular open cone MR16 halogen x x 6V, 12V. Recessed 6 adjustable PAR36. ELA OC specular, open clear Halogen x x 6V, 12V incandescent Recessed 3 . ELA LV3 SB baffled reflector MR16 Halogen x x white, 6V, 12V. Recessed 6 PAR36. ELA SB baffled reflector Halogen x x white, 6V, 12V incandescent Recessed 3 . ELA LV3 EB baffled eyeball MR16 Halogen x x white, 6V, 12V. Recessed 6 PAR36. ELA EB baffled eyeball Halogen x x white, 6V, 12V incandescent Recessed ELA OSL outdoor step light Halogen x x x Die-cast aluminum, 12V (not MR11 or MR16). Recessed round, outdoor core light, MR16 Halogen ELA Core Light die-cast aluminum, x x x 6V, 12V. Surface-mount outdoor mini cylinder MR11 Halogen ELA OMC die-cast aluminum x x x x 6V, 12V. Surface-mount ELA WP weatherproof 35W, PAR46 x x x aluminum, 12V incandescent Surface-mount wet location PAR36.

5 ELA NX* sealed glass Halogen x x x x gray, white, black incandescent 6V, 12V. Surface-mount Class 1, Div. 2 PAR36. ELA Z haz. location, Halogen x x x x sealed glass, gray incandescent 6V, 12V. * These remote fixtures are offered in single and twin head versions. Page 2. Power Sources Once the classification of an environment is determined and the remote fixtures have been chosen, the next step is to determine which power sources will operate the remote fixtures from a normal or controlled environment. If a facility utilizes unit equipment for its emergency lighting, the option of running the exit Discharge remote(s) off of those units should be considered. By utilizing the chart below, select which unit(s) will work best for the Application . Application Unit Volts Total Capacity Commercial / Light Industrial ELM627 6 27W. Commercial / Light Industrial ELM1254 12 54W.

6 Commercial / Light Industrial ELM1272 12 72W. Industrial / Commercial IND6 6 16 -100W. Industrial / Commercial IND12 12 36 - 450W. Industrial / Commercial IND24 24 100 - 450W. TM. ELM618 IND6, IND12, IND24. If the facility is not utilizing unit equipment for its emergency lighting, the exit Discharge remote(s) can be powered by special exit signs that are placed above any door leading to the exit Discharge . The exit /unit combination, LHQM, provides 6 to watts of remote capacity depending on the unit and option(s) selected (see chart below). The ELA LEHO is a canopy accessory that provides 11 watts of remote capacity after it has been field-installed on a Signature LED emergency exit sign. Remote Application Unit Volts Capacity (Watts). Commercial / Light Industrial LHQM with HO 6 Commercial / Light Industrial LHQM with R0 6 Commercial / Light Industrial LHQM with HO & R0 6 Commercial / Light Industrial ELA LEHO 6 11.

7 ELA LEHO LHQM. Page 3. Codes Life Safety Code (NFPA 101). Section Means of Egress: A continuous and unobstructed way of travel from any point in a building or structure to a public way consisting of three separate and distinct parts: (1) the exit access, (2) the exit , and (3) the exit Discharge . Section Accessible Means of Egress Section Emergency Lighting: .. exit Discharge shall include only designated stairs, ramps, aisles, walkways, and escalators leading to a public way.. Section Performance of System: Emergency illumination shall be provided for not less than 1- hours in the event of failure of normal lighting. Emergency lighting facilities shall be arranged to provide initial illumination that is not less than an average of 1 ft-candle ( lux) and, at any point, not less than ft-candle ( lux), measured along the path of egress at floor level.

8 Illumination levels shall be permitted to decline to not less than an average of ft-candle ( lux) and, at any point, not less than ft-candle ( lux) at the end of the 1- . hours. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded.. Since exit Discharge is one of the three components defined as the "means of egress" per of the Life Safety Code and since also includes exit Discharge , many authorities having jurisdiction have concluded that the lighting levels of apply in full. Note: Variations may exist depending upon the interpretation of codes in your area. Reprinted with permission from NFPA 101 Life Safety Code , 2009 Edition. National Fire Protection Association, Quincy, Massachusetts 02269. This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.

9 Lithonia Lighting Emergency Lighting Systems One Lithonia Way, Conyers, GA 30012. Phone 800 334-8694, Fax 770 981-8141. 2002-2011 Acuity Brands Lighting, Inc. All rights reserved. Rev. 4/25/11 Form No.