Failure Modes, Effects and Diagnostic Analysis Project: 3144P SIS Temperature Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: ROS 04/08-19 Report No.: ROS 04/08-19 R003 Version V2, Revision R1, July 26, 2006 John C. Grebe Rachel Amkreutz The document was prepared using best effort. The authors make no warranty of any kind and shall not be liable in any event for incidental or consequential damages in connection with the application of the document. All rights reserved. ros 04-08-19 r003 v2 r1 3144p sis , 7/26/2006 John C. Grebe Rachel Amkreutz Page 2 of 28 Management summary This report summarizes the results of the Failure Modes, Effects , and Diagnostic Analysis (FMEDA) of the 3144P SIS Temperature Transmitter with Hardware version 1 and Software version A Failure Modes, Effects , and Diagnostic Analysis is one of the steps to be taken to achieve functional safety certification per IEC 61508 of a device.

Failure Modes, Effects and Diagnostic Analysis Project: 3144P SIS Temperature Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: ROS 04/08-19

Tags:

  Analysis, Dome, Failure, Effect, Diagnostics, Failure mode, Effects and diagnostic analysis

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Failure Modes, Effects and Diagnostic Analysis - …

1 Failure Modes, Effects and Diagnostic Analysis Project: 3144P SIS Temperature Transmitter Customer: Rosemount Inc. Chanhassen, MN USA Contract No.: ROS 04/08-19 Report No.: ROS 04/08-19 R003 Version V2, Revision R1, July 26, 2006 John C. Grebe Rachel Amkreutz The document was prepared using best effort. The authors make no warranty of any kind and shall not be liable in any event for incidental or consequential damages in connection with the application of the document. All rights reserved. ros 04-08-19 r003 v2 r1 3144p sis , 7/26/2006 John C. Grebe Rachel Amkreutz Page 2 of 28 Management summary This report summarizes the results of the Failure Modes, Effects , and Diagnostic Analysis (FMEDA) of the 3144P SIS Temperature Transmitter with Hardware version 1 and Software version A Failure Modes, Effects , and Diagnostic Analysis is one of the steps to be taken to achieve functional safety certification per IEC 61508 of a device.

2 From the FMEDA, Failure rates and Safe Failure Fraction are determined. The FMEDA that is described in this report concerns only the hardware of the 3144P SIS Temperature Transmitter, electronic and mechanical. For full functional safety certification purposes all requirements of IEC 61508 must be considered. The 3144P SIS Temperature Transmitter is a two wire, 4 20 mA smart device. For safety instrumented systems usage it is assumed that the 4 20 mA output is used as the primary safety variable. The transmitter can be equipped with or without display. The 3144P SIS Temperature Transmitter is classified as a Type B1 device according to IEC61508, having a hardware fault tolerance of 0. The 3144P SIS Temperature Transmitter together with a temperature-sensing element becomes a temperature sensor assembly. When using the results of this FMEDA in a SIL verification assessment, the Failure rates and Failure modes of the temperature sensing element must be considered.

3 This is discussed in detail in Section and Appendix B. Failure rates for the 3144P SIS Temperature Assembly when using thermocouples in a low stress environment are listed in Table 1. The dual sensing element mode assumes PV is S1, S2 or first good and drift alert is set to alarm. Table 1 Failure rates 3144P SIS Temperature Assembly with T/C Failure rate (in FIT) Failure category Single TC mode Dual TC mode Drift Alert = Alarm Fail High (detected by the logic solver) 28 28 Fail Low (detected by the logic solver) 5089 5347 Fail detected (int. diag.)* 5064 5322 Fail low (inherently) 25 25 Fail Dangerous Undetected 291 44No effect 103 107 Annunciation Undetected 5 5 Safe Failure Fraction * These failures follow the setting of the Alarm switch and result in either a High or Low output of the transmitter. It is assumed that upon the detection of a Failure the output will be sent downscale, therefore all detected failures are listed as a sub-category of the Fail Low Failure category.

4 If the Alarm switch is set to High, these failures would need to be added to the Fail High Failure category. 1 Type B component: Complex component (using micro controllers or programmable logic); for details see of IEC 61508-2. ros 04-08-19 r003 v2 r1 3144p sis , 7/26/2006 John C. Grebe Rachel Amkreutz Page 3 of 28 Failure rates for the 3144P SIS Temperature Assembly when using RTDs in a low stress environment are listed in Table 1. The dual sensing element mode assumes PV is S1, S2 or first good and drift alert is set to alarm. Table 2 Failure rates 3144P SIS Temperature Assembly using RTDs Failure rate (in FIT) Failure category Single 4-wire RTD mode Dual 3-wire RTD mode, Drift Alert = Alarm Fail High (detected by the logic solver) 28 28 Fail Low (detected by the logic solver) 2311 2338 Fail detected (int. diag.)* 2286 2313 Fail low (inherently) 25 25 Fail Dangerous Undetected 59 42No effect 107 111 Annunciation Undetected 5 5 Safe Failure Fraction * These failures follow the setting of the Alarm switch and result in either a High or Low output of the transmitter.

5 It is assumed that upon the detection of a Failure the output will be sent downscale, therefore all detected failures are listed as a sub-category of the Fail Low Failure category. If the Alarm switch is set to High, these failures would need to be added to the Fail High Failure category. The Failure rates are valid for the useful lifetime of the transmitter, see Appendix A. A user of the 3144P SIS Temperature Transmitter can utilize these Failure rates in a probabilistic model of a safety instrumented function (SIF) to determine suitability in part for safety instrumented system (SIS) usage in a particular safety integrity level (SIL). A full table of Failure rates is presented in section along with all assumptions. ros 04-08-19 r003 v2 r1 3144p sis , 7/26/2006 John C. Grebe Rachel Amkreutz Page 4 of 28 Table of Contents Management summary .. 2 1 Purpose and Scope .. 5 2 Project 6 Roles of the parties involved.

6 6 Standards / Literature Reference Documentation provided by the Documentation generated by 3 Product 8 4 Failure Modes, Effects , and diagnostics Analysis .. 9 Description of the Failure Methodology FMEDA, Failure rates ..10 Failure rates ..10 Assumptions ..10 Behavior of the safety logic solver ..11 Results ..12 5 Using the FMEDA 14 Temperature sensing elements ..14 3144P SIS Temperature Transmitter with single 3144P SIS Temperature Transmitter with RTD ..15 Converting Failure rates to IEC 61508 PFDAVG calculation 3144P SIS Temperature Transmitter ..17 6 Terms and Definitions .. 18 7 Status of the document .. 19 Liability ..19 Releases ..19 Future Release Appendix A: Lifetime of critical components .. 20 Appendix B: Failure rates for various transmitter modes .. 21 Appendix C: Proof tests to reveal dangerous undetected faults .. 24 Proof test Proof test Appendix D: Common Cause for redundant transmitter 26 ros 04-08-19 r003 v2 r1 3144p sis , 7/26/2006 John C.

7 Grebe Rachel Amkreutz Page 5 of 28 1 Purpose and Scope Generally three options exist when doing an assessment of sensors, interfaces and/or final elements. Option 1: Hardware assessment according to IEC 61508 Option 1 is a hardware assessment by exida according to the relevant functional safety standard(s) like IEC 61508 or EN 954-1. The hardware assessment consists of a FMEDA to determine the fault behavior and the Failure rates of the device, which are then used to calculate the Safe Failure Fraction (SFF) and the average Probability of Failure on Demand (PFDAVG). When appropriate, fault injection testing will be used to confirm the effectiveness of any self- diagnostics . This option for pre-existing hardware devices shall provide the safety instrumentation engineer with the required Failure data as per IEC 61508 / IEC 61511 and does not include an assessment of the development process Option 2: Hardware assessment with proven-in-use consideration according to IEC 61508 / IEC 61511 Option 2 is an assessment by exida according to the relevant functional safety standard(s) like IEC 61508 or EN 954-1.

8 The hardware assessment consists of a FMEDA to determine the fault behavior and the Failure rates of the device, which are then used to calculate the Safe Failure Fraction (SFF) and the average Probability of Failure on Demand (PFDAVG). When appropriate, fault injection testing will be used to confirm the effectiveness of any self- diagnostics . In addition, this option includes an assessment of the proven-in-use documentation of the device including the modification process. This option for pre-existing programmable electronic devices shall provide the safety instrumentation engineer with the required Failure data as per IEC 61508 / IEC 61511 and may help justify the reduced fault tolerance requirements of IEC 61511 for sensors, final elements and other PE field devices when combined with plant specific proven-in-use records. Option 3: Full assessment according to IEC 61508 Option 3 is a full assessment by exida according to the relevant application standard(s) like IEC 61511 or EN 298 and the necessary functional safety standard(s) like IEC 61508 or EN 954-1.

9 The full assessment extends option 1 by an assessment of all fault avoidance and fault control measures during hardware and software development. This assessment shall be done according to option 1. This document shall describe the results of the hardware assessment in the form of the Failure Modes, Effects and Diagnostic Analysis carried out on the 3144P SIS Temperature Transmitter. From this, Failure rates, Safe Failure Fraction (SFF) and example PFDAVG values are calculated. The information in this report can be used to evaluate whether a sensor (or logic / final element subsystem) meets the average Probability of Failure on Demand (PFDAVG) requirements and the architectural constraints / minimum hardware fault tolerance requirements per IEC 61508. ros 04-08-19 r003 v2 r1 3144p sis , 7/26/2006 John C. Grebe Rachel Amkreutz Page 6 of 28 2 Project management is one of the world s leading knowledge companies specializing in automation system safety and availability with over 200 years of cumulative experience in functional safety.

10 Founded by several of the world s top reliability and safety experts from assessment organizations like T V and manufacturers, is a partnership with offices around the world. offers training, coaching, project oriented consulting services, internet based safety engineering tools, detail product assurance and certification Analysis and a collection of on-line safety and reliability resources. maintains a comprehensive Failure rate and Failure mode database on process equipment. Roles of the parties involved Rosemount Inc. Manufacturer of the 3144P SIS Temperature Transmitter Project leader of the FMEDA Rosemount Inc. contracted in August 2004 with the FMEDA and PFDAVG calculation of the above mentioned device. Standards / Literature used The services delivered by were performed based on the following standards / literature. [N1] IEC 61508-2: 2000 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems [N2] FMD-91 & FMD-97, RAC 1991, 1997 Failure Mode / Mechanism Distributions, Reliability Analysis Center.