Fisher LCP100 Local Control Panel - Emerson

LCP100 Local Control of Area Classifications and SpecialInstructions for Safe Use and Installationin Hazardous Setup of 1. Fisher LCP100 Local Control Panel , withFIELDVUE DVC6200 SIS Digital Valve Controllerand Bettis ActuatorX0247 IntroductionScope of ManualThis instruction manual includes installation and maintenance information for the Fisher LCP100 Local Control Panel (figure 1). This device is used with Fisher FIELDVUE instruments in Safety Instrumented Systems (SIS). Refer to theDVC6200 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions instruction manual(D103557X012) or the DVC6000 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutionsinstruction manual (D103230X012) for additional otherwise noted, the information in this instruction manual applies to both DVC6200 SIS and DVC6000 SISdigital valve controllers.

Instruction Manual D103272X012 LCP100 Local Control Panel June 2018 2 Do not install, operate, or maintain an LCP100 local control panel without being fully trained and qualified in valve,

Tags:

  Control, Panels, Local, Lcp100 local control panel, Lcp100

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Fisher LCP100 Local Control Panel - Emerson

1 LCP100 Local Control of Area Classifications and SpecialInstructions for Safe Use and Installationin Hazardous Setup of 1. Fisher LCP100 Local Control Panel , withFIELDVUE DVC6200 SIS Digital Valve Controllerand Bettis ActuatorX0247 IntroductionScope of ManualThis instruction manual includes installation and maintenance information for the Fisher LCP100 Local Control Panel (figure 1). This device is used with Fisher FIELDVUE instruments in Safety Instrumented Systems (SIS). Refer to theDVC6200 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions instruction manual(D103557X012) or the DVC6000 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutionsinstruction manual (D103230X012) for additional otherwise noted, the information in this instruction manual applies to both DVC6200 SIS and DVC6000 SISdigital valve controllers.

2 For simplicity, the DVC6200 SIS model name will be used ManualD103272X012 LCP100 Local Control PanelOctober 2018 Instruction ManualD103272X012 LCP100 Local Control PanelOctober 20182Do not install, operate, or maintain an LCP100 Local Control Panel without being fully trained and qualified in valve,actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it isimportant to carefully read, understand, and follow all of the contents of this manual, includingall safety cautions andwarnings. If you have any questions about these instructions, contact your Emerson sales LCP100 Local Control Panel is used with the HARTr communicating DVC6200 SIS digital valve controller.

3 This panelis used to manually open and close a safety shutdown valve. The LCP100 also provides a manual reset feature as well asa button for initiating a partial stroke specifications for the LCP100 Local Control Panel are shown in table ServicesFor information on available courses contact: Emerson Automation SolutionsEducational Services - RegistrationPhone: +1-641-754-3771 or +1-800-338-8158e mail: ManualD103272X012 LCP100 Local Control PanelOctober 20183 Table 1. SpecificationsPower Options (switch selectable)JExternal: 24 VDC +/- 10% @ 50 mA maximumcontinuous current (100 mA maximum inrush)JLoop: 8 20 mA ( LCP100 and DVC6200 SIScombined)Power ConsumptionExternal: W max continuousLoop (Point-to-Point): W max continuousLoop (Multi-Drop): W max continuous Temperature Limits(1)-40 to 65_C (-40 to 149_F)Maximum distance between LCP100 and DVC6200 SIS digital valve controllerCable length is limited by maximum cablecapacitance of 100,000 pF(2).

4 Typical 314 meters(1030 feet) with 18 AWG shielded Audio, Control andInstrumentation ClassificationCSA (C/US)AEx ia IIB T4 Ga(3) Zone 0, 1, 2 AEx e mb [ib] IIC T4 Gb Zone 1, 2 AEx ic IIC T4 Gc Zone 2 Class I Division 2 Groups ABCD T4 ATEXEx ia IIB T4 Ga(3) Zone 0, 1, 2Ex e mb [ib] IIC T4 Gb Zone 1, 2Ex ic IIC T4 Gc Zone 2 IECExEx ia IIB T4 Ga(3) Zone 0, 1, 2Ex e mb [ib] IIC T4 Gb Zone 1, 2Ex ic IIC T4 Gc Zone 2Ex tb IIIC T71 C Db Zone 21, 22 CUTREx em[ib] IIC Zone 1, 2Ex ic IIC Zone 2 Electrical HousingIP66 Electromagnetic Interference (EMI)Meets EN 61326-1:2013 Immunity Industrial locations per Table 2 of EN 61326-1 Standard.

5 Performance is shown in table 2 below. Emissions Class A ISM equipment rating: Group 1, Class AConnectionsConduit: 3/4 NPT or M20 Wiring14 to 26 AWGT orque SpecificationsWiring terminals: NSm ( inSlbs)Electrical InstallationWire connections are polarity sensitiveCompatibilityDVC6200 SIS with Firmware revision 3 or laterDVC6000 SIS with Firmware revision 7 or laterInstallation OrientationWiring entrance must be facing mm (10 inches) long by mm ( inches)wide by mm 5 inches) deep. See figure MaterialsHousing material: filled polyesterApproximate kg ( lb)1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be DVC6000 SIS: Cable length is limited by maximum cable capacitance of 18000 LOOP Powered ManualD103272X012 LCP100 Local Control PanelOctober 20184 Table 2.

6 Electromagnetic Immunity Performance CriteriaPortPhenomenonBasic StandardTest LevelPerformanceCriteria(1)EnclosureElec trostatic discharge (ESD)IEC 61000 4 2$4 kV contact$8 kV airARadiated EM fieldIEC 61000 4 380 to 1000 MHz @ 10V/m with 1 kHz AM at 80%1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%AI/O signal/controlBurst (fast transients)IEC 61000 4 4$1 kV, I/O lines$2 kV, DC power linesASurgeIEC 61000 4 5$1 kV, I/O lines$2 kV, DC power lines)AConducted RFIEC 61000 4 6150 kHz to 80 MHz at 3 Vrms with 1 kHz AM at 80%ASpecification limit = 1% of span1. A = No degradation during testing. B = Temporary degradation during testing, but is self 2.

7 Fisher LCP100 Local Control Panel Dimensions129( )94( )110( )194( )257( )mm(INCH)E1077 1 Instruction ManualD103272X012 LCP100 Local Control PanelOctober 20185 Installation WARNINGE lectrostatic charge hazard. Do not rub or clean the LCP100 with solvents if a flammable vapor is present. To do so couldresult in an all wiring to the left side inside the LCP100 compartment, away from the Area Classifications and Special Instructions for Safe Use andInstallation in Hazardous LocationsRefer to the following instruction manual supplements for approval CSA (C/US) Hazardous Area Approvals - LCP100 Local Control Panel (D104236X012)D ATEX Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104237X012)D IECEx Hazardous Area Approvals - DVC2000 Digital Valve Controllers (D104238X012)

8 All documents are available from your Emerson sales office or Contact your Emerson sales office for allother approval/certification to figure 2 for dimensional information. The LCP100 Local Control Panel has four (4) mounting holes for on sitemounting of the device. The LCP100 must be installed so that the wiring connections are on the bottom to preventaccumulation of moisture inside the Connections WARNINGS elect wiring and/or cable glands that are rated for the environment of use (such as hazardous location, ingress protection,and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damagefrom fire or connections must be in accordance with Local , regional, and national codes for any given hazardous area to follow the Local , regional, and national codes could result in personal injury or property damage from fire to the appropriate wiring diagram, as defined in table 3, based on your protection method and installationrequirements.

9 Also refer to figure 4 for LCP100 switch setting, terminal connections, and label details and information,as well as DVC6200 SIS terminal box ManualD103272X012 LCP100 Local Control PanelOctober 20186 Table 3. Wiring Configurations with DVC6200 SIS Digital Valve ControllerLCP100 Protection MethodLCP100 Power SourceWiring Order fromLogic SolverDVC6200 SIS Mode(Current or Voltage)Refer to figureEx e mb [ib] IICEx tb IIICLOOPDVC6200 SIS then LCP100 Point-to-Point5 Multi-Drop6 LCP100 then DVC6200 SISP oint-to-Point7 Multi-Drop824 VDCDVC6200 SIS then LCP100 Point-to-Point9 Multi-Drop10Ex ic IICEx tb IIICLOOPDVC6200 SIS then LCP100 Point-to-Point11 Multi-Drop12 LCP100 then DVC6200 SISP oint-to-Point13 Multi-Drop1424 VDCDVC6200 SIS then LCP100 Point-to-Point15 Multi-Drop16Ex ia IIBEx tb IIICLOOPDVC6200 SIS then LCP100 Point-to-Point17 Multi-Drop18 LCP100 then DVC6200 SISP oint-to-Point19 Multi-Drop20 NoteFor intrinsically safe applications.

10 The LCP100 forms an intrinsically safe explosion protection system when used with intrinsicallysafe associated apparatus (a barrier) or with any other intrinsically safe following requirements must be met: Uo Ui , Io Ii, Po Pi , Co Ci + Cc, Lo Li + installing the cover, tighten the screws evenly in a criss cross pattern such as the one indicated in figure 3, to atorque of N m (25 lbf in), to help ensure the cover is properly 3. Proper Cover InstallationNOTE: TIGHTEN THE SCREWS IN A CRISS CROSS PATTERNTO HELP ENSURE PROPER COVER ManualD103272X012 LCP100 Local Control PanelOctober 20187 POWER SELECTORSWITCH (FACTORYDEFAULT IS 24 VDC)Figure 4.