Transcription of Floatless Level Switch (Compact, Plug-in Type) 61F-GP-N
1 Floatless Level Switch ( compact , Plug-in Type). 61F-GP-N @ Space-saving Design Ideal for Control Panel Downsizing. Easy Maintenance. compact : 38 84 mm (H W D). Easy identification of operating status with LED operation indicator. Independent DPDT contacts on 11-Pin Models. CE marking and UL/CSA compliance. Refer to Safety Precautions for Floatless Level Controllers. Model Number Legend Position of LED indicator 1. No. of Pins 2. Type 61F-GP-@ 1 2 N: 11 pins Blank: General-purpose N8: 8 pins L 2KM: Long-distance (for 2 km). L 4KM: Long-distance (for 4 km). H: High-sensitivity D: Low-sensitivity R: Two-wire T: High-temperature Ordering Information Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km). Model Model Model 11-pin 61F-GP-N 61F-GP-NL 2KM 61F-GP-NL 4KM.
2 Type High-sensitivity Low-sensitivity Two-wire Model Model Model 11-pin 61F-GP-NH 61F-GP-ND 61F-GP-NR. Type Tropical environments High-temperature Model Model 11-pin 61F-GP-N -TDL 61F-GP-NT. Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km). Model Model Model 8-pin 61F-GP-N8 61F-GP-N8L 2KM 61F-GP-N8L 4KM. Type High-sensitivity Low-sensitivity Two-wire Model Model Model 8-pin 61F-GP-N8H 61F-GP-N8D 61F-GP-N8R. 61F-GP-N8HY. Note: When ordering, specify the desired operating voltage at the end of the model number. Example: 61F-GP-N [220 VAC]. Desired supply voltage 1. compact Plug-in Models (11-pin Type). Specifications Item General-purpose High- Long-distance High-sensitivity Low-sensitivity Two-wire Controller temperature Controllers Controller Controller Controller Controller 61F-GP-N 61F-GP-NL 2KM 61F-GP-NH 61F-GP-ND 61F-GP-NR.
3 61F-GP-NT (for 2 km) (see note 4). 61F-GP-NL 4KM. (for 4 km). Controlling materials For control of ordi- For control of ordi- For control of ordi- For control of liq- For control of liq- For control of ordi- and operating condi- nary purified water nary purified water nary purified water uids with high spe- uids with low spe- nary purified water tions or sewage water or sewage where in cases where the cific resistance cific resistance or sewage water operating ambient distance between such as distilled such as salt water, used in combina- temperature is sewage pumps water sewage water, tion with Two-wire high. and water tanks or acid chemicals, al- Electrode Holder between receiver kali chemicals (incorporating a tanks and supply resistor of k ).
4 Tanks is long or where remote con- trol is required. Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz Operating voltage 85% to 110% of rated voltage range Interelectrode voltage 8 VAC. Interelectrode current Approx. 1 mA AC max. Approx. mA Approx. 1 mA AC max. AC max. Power consumption Approx. VA max. Interelectrode operate 0 to approx. 4 k 0 to approx. 4 k 0 to approx. k Approx. 10 k to 0 to approx. 0 to resistance (for 2 km) approx. 40 k k approx. 2 k . 0 to approx. k (see note 3). (for 4 km). Interelectrode release Approx. 15 k to Approx. 15 k to 4 k to (for 2 Approx. 100 k to Approx. 4 k to Approx. 15 k to resistance km) . k to (for 4. km). Response time Operate:80 ms max. Release:160 ms max. Cable length 1 km max.
5 600 m max. 2 km max. 50 m max. 1 km max. 800 m max. (see note 1) 4 km max. Control output 1 A, 250 VAC (Inductive load: cos = ). 3 A, 250 VAC (Resistive load). Ambient temperature Operating: 10 to 55 C ( 10 to 70 C for high-temperature controller). Ambient humidity Operating:45% to 85% RH. Insulation resistance 100 M min. (at 500 VDC). (see note 2). Dielectric strength 2000 VAC, 50/60 Hz for 1 min. (see note 2). Life expectancy Electrical: 100,000 operations min. Mechanical: 5,000,000 operations min. Weight Approx. 155 g Accessories Hold-down clip PFC-N8. Approved standards UL508, CSA , EN61010-1, EN61326-1 Industrial electromagnetic environment Note: 1. The length when using completely insulated, 600-V, 3-conductor ( mm2) cabtire cables.
6 Usable cable lengths will become shorter as the cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers. 2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power terminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions for Floatless Level Controllers. 3. Possible to use with 15 k or less, however, this may cause reset failure. 4. 61F-GP-NH High-sensitivity Controller uses advanced operation. When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter- nal relay will not operate.
7 When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal relay will operate. If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation. 2. Internal Circuit Diagrams 61F-GP-N /-NT/-NL/-ND 61F-GP-NH 61F-GP-NR. Power supply Power supply Power supply 24 V Control circuit 24 V Control circuit 24 V Control circuit 8V (See note.) 8V (See note.) 8V. U. U U U U U. 3 9 4 5 11 10 1 7 6 8 3 9 4 5 11 10 1 7 6 8 3 9 4 5 11 10 1. S0 S1 E3 E1 Ta1 Tc1 Tb1 Ta2 Tc2 Tb2 S0 S1 E3 E1 Ta1 Tc1 Tb1 Ta2 Tc2 Tb2 S0 S1 E3 E1 Ta1 Tc1 Tb1. Note: When applying a self-holding circuit, short between terminals 5 and 6 and use terminal 7 as E2.
8 3. Connections Automatic Water Supply and compact , Plug-in Type Drainage Control 61F-GP-N . Dimensions: page 14. Automatic Water Supply Control Automatic Drainage Control Connections Connections Commercial Voltage 61F-GP-N Commercial Voltage 61F-GP-N . R S T R S T. 8 7 6 5 8 7 6 5. U 4 U 4. MCCB MCCB. 0V Control U 0V Control U. 24 V circuit 24 V circuit Power 8V Power 8V. supply supply U U. 3 9 3 9. 10 11 1 2 10 11 1 2. Contac- Contac- tor (See note.) tor (See note.). PS-3S. Motor Stop Motor protection Water supply E1 protection PS-3S. Water relay source relay Waste- Start tank E2 Start E3 water E1. tank E2 Stop E3. M P M P. Reservoir Note: Be sure to ground the common Electrode E3 (the Note: Be sure to ground the common Electrode E3 (the longest Electrode).)
9 Longest Electrode). Connection Sockets Connection Sockets PF113A (Front-connecting) PF113A (Front-connecting). PL11 (Rear-connecting) PL11 (Rear-connecting). Connect terminal 1 to the contactor's coil terminal. Connect terminal 1 to the contactor's coil terminal. Note: The power supply depends on the specifications of the Note: The power supply depends on the specifications of the model. model. Principles of Operation Principles of Operation Water supply P. (Indicator ON) (Indicator ON). Pump OFF E1 Pump ON E1. Pump ON (Indicator OFF) Pump OFF (Indicator OFF). E2 E2. E3 E3 P. Water drainage The pump stops when the water Level reaches E1 (indicator ON) The pump starts when the water Level reaches E1 (indicator ON). and starts when the water Level drops below E2 (indicator OFF).
10 And stops when the water Level drops below E2 (indicator OFF). 4. Liquid Level Indication compact , Plug-in Type (Connection Example) 61F-GP-N . Dimensions: page 14. Liquid Level Indication Connections Lower limit Intermediate Upper limit Commercial Voltage 61F-GP-N 61F-GP-N 61F-GP-N . R S T. 8 7 6 5 8 7 6 5 8 7 6 5. U U U. 4 4 4. MCCB 0V 24 V Control U 0V 24 V Control U 0V 24 V Control circuit circuit circuit U. Power 8V Power 8V Power 8V. supply supply supply U U U. 3 9 3 9 3 9. 10 11 1 2 10 11 1 2 10 11 1 2. (See note.). PS-4S. Upper limit E1. Water Water supply tank Intermediate E2. source Lower limit E3. E4. M P. Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for the common Electrode (the longest Electrode, terminal 4).