<<Contents>> <<Index>>. General Model EJA430A . Specifications Gauge pressure transmitter GS 01C21E01-00E. The high performance Gauge pressure transmitter Model EJA430A can be used to measure liquid, gas, or steam pressure . It outputs a 4 to 20 mA DC signal corresponding to the measured Gauge pressure . Model EJA430A also features remote setup and monitoring through communications with the BRAIN . terminal and CENTUM CS or XL or HART 275. host. STANDARD Specifications . Refer to GS 01C22T02-00E for FOUNDATION Fieldbus communication type and GS 01C22T03-00E for PROFIBUS PA communication type marked with .. PERFORMANCE Specifications .

General Specifications <<Contents>> <<Index>> The high performance gauge pressure transmitter model EJA430A can be used to measure liquid, gas, or steam pressure.

Tags:

  Pressure, Transmitter, Gauge, Gauge pressure transmitters

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of General Model EJA430A Specifications Gauge …

1 <<Contents>> <<Index>>. General Model EJA430A . Specifications Gauge pressure transmitter GS 01C21E01-00E. The high performance Gauge pressure transmitter Model EJA430A can be used to measure liquid, gas, or steam pressure . It outputs a 4 to 20 mA DC signal corresponding to the measured Gauge pressure . Model EJA430A also features remote setup and monitoring through communications with the BRAIN . terminal and CENTUM CS or XL or HART 275. host. STANDARD Specifications . Refer to GS 01C22T02-00E for FOUNDATION Fieldbus communication type and GS 01C22T03-00E for PROFIBUS PA communication type marked with .. PERFORMANCE Specifications .

2 Zero-based calibrated span, linear output, wetted parts material code S' and silicone oil. Reference Accuracy of Calibrated Span (including the effects of zero-based linearity, hyster- esis, and repeatability). % of Span External Zero Adjustment . External zero is continuously adjustable with %. For spans below X, incremental resolution of span. Span may be adjusted locally using the digital indicator with range X switch. [ + ] % of Span Span Mounting Position Effect where X equals: Rotation in diaphragm plane has no effect. Tilting up to Capsule X MPa {psi} 90 will cause zero shift up to kPa { inH2O}. A {43} which can be corrected by the zero adjustment.

3 B {200} Output . Ambient Temperature Effects Two wire 4 to 20 mA DC output with digital communi- Total Effects per 28 C (50 F) Change cations. BRAIN or HART FSK protocol are superim- [ % Span + % URL] posed on the 4 to 20 mA signal. Stability Failure Alarm % of URL per 60 months Output status at CPU failure and hardware error;. Power Supply Effects Up-scale: 110%, mA DC or more(standard). % per Volt (from to 32 V DC, 350 ) Down-scale: -5%, mA DC or less , mA DC or less (Optional FUNCTIONAL Specifications code /F1). Note: Applicable for Output signal code D and E. Span & Range Limits Damping Time Constant (1st order).

4 The sum of the amplifier and capsule damping time Measurement Span and Range MPa psi (/D1) bar (/D3) kgf/cm2(/D4) constant must be used for the overall time constant. Span to 3 to 430 to 30 to 30. Amp damping time constant is adjustable from to A 64 seconds. Range to 3 -15 to 430 -1 to 30 -1 to 30. Span to 14 20 to 2000 to 140 to 140 Capsule (Silicone Oil) A B. B. Range to 14 -15 to 2000 -1 to 140 -1 to 140 Time Constant (approx. sec) URL is defined as the Upper Range Limit from the Ambient Temperature Limits table above. (approval codes may affect limits). -40 to 85 C (-40 to 185 F). Zero Adjustment Limits -30 to 80 C (-22 to 176 F) with LCD Display Zero can be fully elevated or suppressed, within the Lower and Upper Range Limits of the capsule.

5 Yokogawa Electric Corporation GS 01C21E01-00E. 2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright June 1997. Phone: 81-422-52-5690 Fax.: 81-422-52-2018 27th Edition April 2013. <<Contents>> <<Index>> 2. Process Temperature Limits Supply & Load Requirements (approval codes may affect limits) (Safety approvals can affect electrical requirements). -40 to 120 C (-40 to 248 F) With 24 V DC supply, up to a 570 load can be used. See Figure 2. Ambient Humidity Limits 5 to 100 % RH @ 40 C (104 F) Supply Voltage . to 42 V DC for General use and flameproof type Maximum Overpressure to 32 V DC for lightning protector (Optional Capsule pressure code /A).

6 To 30 V DC for intrinsically safe, Type n, A MPa {645 psig} nonincendive, or non-sparking type B 21 MPa {3000 psig}. Minimum voltage limited at V DC for digital Working pressure Limits (Silicone Oil) communications, BRAIN and HART. Maximum pressure Limit Load (Output signal code D and E). 0 to 1335 for operation Capsule pressure 250 to 600 for digital communication A 3 MPa {430 psig} EMC Conformity Standards , B 14 MPa {2000 psig} EN61326-1 Class A, Table2 (For use in industrial Minimum pressure Limit locations). See graph below EN61326-2-3. European pressure Equipment Directive 97/23/EC. Sound Engineering Practice 100{ } Atmospheric Safety Requirement Standards pressure EN61010-1.

7 Working Altitude of installation site: Max. 2,000 m above sea level pressure Installation category: I. kPa abs Pollution degree: 2. {psi abs}. Indoor/Outdoor use Applicable range Communication Requirements . 10{ }. BRAIN. Communication Distance Up to 2 km ( miles) when using CEV polyethyl- { }. ene-insulated PVC-sheathed cables. Communication distance varies depending on type of cable used. 1{ } Load Capacitance -40 0 40 80 120. F or less (see note). (-40) (32) (104) (176) (248). Process temperature C ( F) Load Inductance mH or less (see note). Spacing from power line Figure 1. Working pressure and Process Temperature 15 cm or more.

8 Input Impedance of communicating device 10 k or more at kHz. Note : For General -use and Flameproof type. For Intrinsically safe type, please refer to 600 OPTIONAL Specifications .'. R=. Digital External Communication load range resistance BRAIN and HART. 250. R ( ). 42. Power supply voltage E (V DC). Figure 2. Relationship Between Power Supply Voltage and External Load Resistance All Rights Reserved. Copyright 1997, Yokogawa Electric Corporation GS 01C21E01-00E April 01, 2013-00. <<Contents>> <<Index>> 3. PHYSICAL Specifications < Related Instruments > . Wetted Parts Materials Power Distributor: Refer to GS 01B04T01-02E or GS 01B04T02-02E.

9 Diaphragm, Cover flange, Process connector, BRAIN TERMINAL: Refer to GS 01C00A11-00E. and Vent/Drain Plug Refer to Model AND SUFFIX CODE.' < Reference >. Capsule Gasket 1. Teflon; Trademark of DuPont de Nemours & Co. For wetted parts material code S, Teflon-coated 2. Hastelloy; Trademark of Haynes International Inc. SUS316L. 3. Monel; Trademark of Inco Alloys International, Inc. For wetted parts material code other than S, 4. HART; Trademark of the HART Communication PTFE(Teflon). Foundation. Process Connector Gasket 5. FOUNDATION; Trademark of Fieldbus Foundation. 6. PROFIBUS; Registered trademark of Profibus PTFE Teflon Nutzerorganisation , Karlsruhe, Germany.

10 Fluorinated rubber for Optional code /N2 and /N3. Material Cross Reference Table Non-wetted Parts Materials SUS316L AISI 316L. Bolting SUS316 AISI 316. SCM435, SUS630, or SUH660. SUS304 AISI 304. Housing S25C AISI 1025. Low copper cast-aluminum alloy with polyurethane SCM435 AISI 4137. paint (Munsell ). SUS630 ASTM630. Degrees of Protection SCS14A ASTM CF-8M. IP67, NEMA4X. Cover O-rings Buna-N, fluoro-rubber (optional) 7. Other company names and product names used in Name plate and tag this material are registered trademarks or trademarks of their respective owners. SUS304 or SUS316 (option). Fill Fluid < Specification Conformance >.