Example: marketing

HIGH SPEED Dual Indication Fuse-Links HSDI

HIGH SPEED Dual Indication Fuse-LinksHSDI Square Body din 43620 - 690V (IEC/UL), Size 000 to 00, 10 to 315 AmpsForm No. HSDI 000/00 Page 1 of 5 Data sheet 720100 Standards/Approvals:CE, designed and tested to IEC 60269: part 4. UL recognised (Survival Only), CSAD escription:Square body din 43620 blade style, dual Indication High SPEED fuses Packaging:Size 000 are packed in 10 sSize 00 are packed in 6 sTechnical Data:Rated Voltage:690 VacAmps:10A to 315 ARated Breaking Capacity: 200kA RMS SymRoHS Compliant: YesCatalogue Symbol:170M1558D to 170M1572 DClass of Operation:gR (10 to 63A), aR (80 to 315A)Dimensional Data:DIN 000 Type T1mm = / 1 = 00 Type T1mm = / 1 = No.

HIGH SPEED Dual Indication Fuse-Links HSDI Square Body DIN 43620 - 690V (IEC/UL), Size 000 to 00, 10 to 315 Amps Form No. HSDI 000/00 Page 1 of 5

Tags:

  62304, Din 43620

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of HIGH SPEED Dual Indication Fuse-Links HSDI

1 HIGH SPEED Dual Indication Fuse-LinksHSDI Square Body din 43620 - 690V (IEC/UL), Size 000 to 00, 10 to 315 AmpsForm No. HSDI 000/00 Page 1 of 5 Data sheet 720100 Standards/Approvals:CE, designed and tested to IEC 60269: part 4. UL recognised (Survival Only), CSAD escription:Square body din 43620 blade style, dual Indication High SPEED fuses Packaging:Size 000 are packed in 10 sSize 00 are packed in 6 sTechnical Data:Rated Voltage:690 VacAmps:10A to 315 ARated Breaking Capacity: 200kA RMS SymRoHS Compliant: YesCatalogue Symbol:170M1558D to 170M1572 DClass of Operation:gR (10 to 63A), aR (80 to 315A)Dimensional Data:DIN 000 Type T1mm = / 1 = 00 Type T1mm = / 1 = No.

2 HSDI 000/00 Page 2 of 5 Data sheet 720100 Catalogue Numbers:Standard Approvals:CE, IEC 60269: part 4, UL recognised (Survival Only), CSAT echnical Data:10, 16, 20, 25, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 315* Amps* 315A is only available in size DIN00 The rated current of this fuse range has been given with copper conductors that have a high current density of (IEC 60269-4). For conductor cross sectionaccording to IEC 60269-1, the fuses with a rated current higher than 125A must be derated.

3 Please contact Cooper Bussmann for application NumbersSizeRated Current RMS AmpsI2t (A2sec)Watts LossMinimum Pre-ArcingClearing at *120008450045 HIGH SPEED Dual Indication Fuse-LinksHSDI Square Body din 43620 - 690V (IEC/UL), 10 to 315 AmpsForm No. HSDI 000/00 Page 3 of 5 Data sheet 720100 Total Clearing I2 TThe total clearing I2t at rated voltage and atpower factor of 15% are given in the electricalcharacteristics. For other voltages, theclearing I2t is found by multiplying by correction factor, K, given as a function ofapplied working voltage Eg (rms)Power LossesWatts loss at rated current is given in theelectrical characteristics.

4 The curve allowsthe calculation of the power losses at loadcurrents lower than the rated current. Thecorrection factor, Kp, is given as a functionof the RMS load current, lb, in % of the SPEED Dual Indication Fuse-LinksHSDI Square Body din 43620 - 690V (IEC/UL), 10 to 315 AmpsArc VoltageThis curve gives the peak arc voltage, UL,which may appear accross the fuse during itsoperation as a function of the applied workingvoltage, Egrection factor, K, given as a function of applied working voltage Eg (rms)at a power factor of 15%Form No.

5 DINPage 4 of 5 Data sheet 720100 Time Current CurvesHIGH SPEED Dual Indication Fuse-LinksHSDI Square Body din 43620 - 690V (IEC/UL), 10 to 315 AmpsForm No. HSDI 000/00 Page 5 of 5 Data sheet 720100 PeakLet-Through HIGH SPEED Dual Indication Fuse-LinksHSDI Square Body din 43620 - 690V (IEC/UL), 10 to 315 Amps


Related search queries