IG_EF-A1000-T_R1 AIG_EF-A1000-T_R1 AEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: measurable difference! Thermal Dispersion airflow Measurement TechnologyPart Number: 930-0195 Installation GuideEF-A1000 SeriesAnalog Output Electronic Low Flow (ELF) airflow /Temperature Measurement StationDocument: IG_EF-A1000-T_R1 AEF-A1000-T, EF-A1001-T ELFQ uick Installation GuideEB-Flow Electronic Low Flow ELF Analog Output Measurement StationIG_EF-A1000-T_R1Aa measurable difference! EB-FLOWEF-A1000, EF-A1001 ELFINSTALLATION Guide - ELECTRONIC LOW FLOW ELF ANALOG OUTPUTEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: INTRODUCTION AND SCOPE ..32. EF-A1000 , EF-A1001 Installation .

IG_EF-A1000-T_R1A EBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON(232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com a measurable difference! ® Thermal Dispersion Airflow Measurement Technology Part Number: 930-0195 Installation Guide EF …

Tags:

  Airflow

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Installation Guide EF-A1000 Series - ebtron.com

1 IG_EF-A1000-T_R1 AIG_EF-A1000-T_R1 AEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: measurable difference! Thermal Dispersion airflow Measurement TechnologyPart Number: 930-0195 Installation GuideEF-A1000 SeriesAnalog Output Electronic Low Flow (ELF) airflow /Temperature Measurement StationDocument: IG_EF-A1000-T_R1 AEF-A1000-T, EF-A1001-T ELFQ uick Installation GuideEB-Flow Electronic Low Flow ELF Analog Output Measurement StationIG_EF-A1000-T_R1Aa measurable difference! EB-FLOWEF-A1000, EF-A1001 ELFINSTALLATION Guide - ELECTRONIC LOW FLOW ELF ANALOG OUTPUTEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: INTRODUCTION AND SCOPE ..32. EF-A1000 , EF-A1001 Installation .

2 43. ELF PREPARATION FOR USE ..64. ELF INTERCONNECTIONS .. ELF 24 VAC Power Connections .. ELF Analog Output Connections .. Converting the ELF Analog Output for 4-wire Current Loops ..75. ELF ANALOG OUTPUT CONFIGURATION OPTIONS (CONFIG SW1 - SW4) ..76. ELF INITIAL START UP / NORMAL OPERATION .. Converting the Analog airflow Output Signal from Linear to Volumetric flow - FPM to CFM ..117. ELF ADDITIONAL INFORMATION ..11 Table of ContentsFigure 1. ELF Installation Applications and Orientation ..5 Figure 2. ELF Installation Dimensions ..6 Figure 3. ELF Main Circuit Board and Configuration Option Selector Detail ..8 Figure 4. EF-A1000 ELF Single Output Power and Signal Wiring Interconnections ..9 Figure 5. EF-A1001 ELF Dual Output Power and Signal Wiring Interconnections.

3 10 List of TablesTable 1. CONFIG Switch Settings ..7 List of FiguresCopyright EBTRON , brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject tochange without notice. Visit to view and/or download the most recent versions of this and other rights OF EFFECTIVE AND CHANGED PAGESI nsert latest changed pages (in bold text); remove and dispose of superseded number of pages in this manual is No Revision * Description of Change Date1 through 12 ..R1A ..Initial document release.

4 1/25/2016* R1A indicates an original page without changeIG_EF-A1000-T_R1Aa measurable difference! EB-FLOWEF-A1000, EF-A1001 ELFINSTALLATION Guide - ELECTRONIC LOW FLOW ELF ANALOG OUTPUTEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: INTRODUCTION AND SCOPEThis Quick Installation Guide provides basic Installation information for the instrument installer. Information includesphysical instrument Installation , power and output cable connections as well as initial setup of the instrument. The selfcontained electronic low flow instrument in this document is referred to as the ELF. Models covered in this document are as follows:Single Analog Output, Single Sensor (4" Probe)EF-A11100-10/2-10 VDC Single Analog Output with Flow Integration (4" Single Sensor)EF-A1110 /A10-5/1-5 VDC Single Analog Output with Flow Integration (4" Single Sensor)Dual Analog Output, Single Sensor (4" Probe)EF-A11110-10/2-10 VDC Dual Analog Output with Flow Integration (4" Single Sensor)EF-A1111 /A10-5/1-5 VDC Dual Analog Output with Flow Integration (4" Single Sensor)Single Analog Output, Two Sensors (>4" Probe)EF-A11200-10/2-10 VDC Single Analog Output with Flow Integration (>4" Two Sensors)EF-A1120 /A10-5/1-5 VDC Single Analog Output with Flow Integration (>4" Two Sensors)Dual Analog Output, Two Sensors (>4" Probe)

5 EF-A11210-10/2-10 VDC Dual Analog Output with Flow Integration (>4" Two Sensors)EF-A1121 /A10-5/1-5 VDC Dual Analog Output with Flow Integration (>4" Two Sensors)For complete and detailed specifications, operating instructions and technical information, refer to the separateInstallation, Operation and Maintenance Technical Manual TM_EF-A1000under separate measurable difference! EB-FLOWEF-A1000, EF-A1001 ELFINSTALLATION Guide - ELECTRONIC LOW FLOW ELF ANALOG OUTPUTEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: EF-A1000 , EF-A1001 INSTALLATIONThe ELF instruments are designed for use in small ducts and in VAV terminal box applications in an environment between-20 F to 120 F ( C to C) where it will not be exposed to rain or snow.

6 The ELF airflow measurement stationsensor probes are designed for insertion mounting through one side of the duct or VAV box sidewall. Mount the instru-ment in an accessible location to permit set up. Locate the instrument so that the attached instrument cable will reachthe customer provided BAS control installed location of the ELF is critical for proper performance. Refer to theMinimum Placement Guidelines in Technical Manual TM_EF-A1000 to determine theexact location recommended for the installed accuracy of the ELF is ensured in applications where the maximuminside duct dimension is 16 inches or less. Applications in larger duct sizes maydegrade accuracy. Consult factory for these that adequate clearance exists around the duct to permit insertion of theprobe, and to allow clearance for the instrument enclosure.

7 Insulation that interferes with probe mounting should be temporarily removed prior toinstallation. Mounting requires a inches ( mm) hole on the insertion side ofthe duct or VAV terminal Determine where the ELF airflow measuring station is to be located as indicated on the engineer's Carefully open the ELF package and inspect for damage. If damage is noted, immediately file a claim with Locate and mark the point on the duct or VAV box where the probe will be inserted, using the Minimum PlacementGuidelines section of Technical Manual TM_EF-A1000. Figures 1 and 2 show ELF Installation detail, probe orienta-tion and Using a inches ( mm) hole saw, drill the insertion side hole where Place the probe through the mounting hole, making sure that the gasket is seated firmly against the integral mount-ing bracket.

8 Ensure that the edge of the ELF mounting bracket is parallel to the edge of the duct or VAV terminalbox, and that the airflow arrow printed on it is oriented in the direction of actual airflow . Ensure that the gasket isfirmly seated against the bracket, and then fasten the mounting bracket at the four mounting holes using appropri-ate sheet metal Route the ELF instrument cable to the customer provided BAS interface. The following sections of this documentdescribe instrument set up and measurable difference! EB-FLOWEF-A1000, EF-A1001 ELFINSTALLATION Guide - ELECTRONIC LOW FLOW ELF ANALOG OUTPUTEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: 1. ELF Installation Applications and OrientationINSTALLING THE ELF IN DUCTED APPLICATIONSROUND DUCT PLACEMENTA cross major axisAcross minor axis1/2 X 1/2 XRECTANGULAR DUCT PLACEMENT1/2 X 1/2 X1/2 X1/2 XFLAT-OVAL DUCT PLACEMENTB oxes with pneumatic flow rings: Remove existing flow ring.

9 Locate ELF 3 inches (minimum) upstream of box, OR 3 inches (minimum) upstream of flow with no flow rings: Locate ELF 3 inches (minimum) upstream of (by others)VAV Box (by others)ELF PROBE VAV BOX INSTALLATIONA irflowELF DOWNSTREAM OF VAV BOX WITH H/W COILSA irflowAirflowVAV Terminal Box with H/W ReheatEBTRONELFD amper ActuatorNote:This application is not recommended for VAV boxes with electric ELF as close as 1 duct diameter downstreamOf VAV box transitionHot Water Reheat CoilTransition1 DSUPPLY AIR FROM AHUSPACE AIRT erminal Unit DDC ControllerEbtronELFHWRHWS2-Way or 3-Way HW Control ValveTEMP FLOWGND24 VEBTRON ELF24 VAC POWER INPUT24 VAC COM / SIGNAL COMANALOG airflow OUTREDBLACKWHITE4- CONDUCTORSHIELDED CABLEINCLUDED WITH ELFANALOG TEMPERATURE OUTGREENIG_EF-A1000-T_R1Aa measurable difference!

10 EB-FLOWEF-A1000, EF-A1001 ELFINSTALLATION Guide - ELECTRONIC LOW FLOW ELF ANALOG OUTPUTEBTRON, Inc. 1663 Hwy. 701 S., Loris SC 29569 Toll Free: ( ) Fax: Internet: 2. ELF Installation Dimensions3. ELF PREPARATION FOR USEDual output ELF models provide two separate linear analog outputs with one for measured airflow (or equivalent veloci-ty pressure) and the other for measured temperature. Single output ELF models provide a single analog output for air-flow. The airflow analog output can be set for either air flow or equivalent velocity pressure measurement with four fieldselectable full scale range options. On the dual output ELF, the temperature output is set for a full scale range of -20 to120 F ( to C).