LUTRONSG-4 SSG-4 SIRSG-4 BSG-4 NRL SG-4 PSSG-4 MSG-2B TMWallstationsfor use with 3000 Series and4000 Series systems Installation InstructionsOccupant CopyENGLISHDEUTSCHFRAN AISCHINESEPORTUGU SInstrucciones de Installaci nCopia Para el UsuarioFavor de leer antes de instalarInstallationshinweiseOccupant CopyInstallation InstructionsOccupant CopyInstallation InstructionsOccupant CopyInstru es de Instala oC pia do Usu rioESPA 11/1/01 1:36 PM Page 12 Installation InstructionsOccupant CopySG-2 BScene Select, StartSequencing,Panic, Zone Lock,Partition, or Raise buttonScene Select, Stop Sequencing,Lower, or Off buttonSG-4 MAll Scene 1 or OFF ButtonControl UnitStatus LEDsControl Unit StatusSelection ButtonsSG-4 SIRM aster Raise/LowerSceneIndicatorLEDs4S-IR

Installation Instructions 2 Occupant Copy SG-2B Scene Select, Start Sequencing,Panic, Zone Lock, Partition, or Raise button Scene Select, Stop Sequencing, Lower, or Off button

Tags:

  Installation, Instructions, Lutron, Installation instructions, Wallstation, Installation instructions wallstations

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Installation Instructions Wallstations - Lutron …

1 LUTRONSG-4 SSG-4 SIRSG-4 BSG-4 NRL SG-4 PSSG-4 MSG-2B TMWallstationsfor use with 3000 Series and4000 Series systems Installation InstructionsOccupant CopyENGLISHDEUTSCHFRAN AISCHINESEPORTUGU SInstrucciones de Installaci nCopia Para el UsuarioFavor de leer antes de instalarInstallationshinweiseOccupant CopyInstallation InstructionsOccupant CopyInstallation InstructionsOccupant CopyInstru es de Instala oC pia do Usu rioESPA 11/1/01 1:36 PM Page 12 Installation InstructionsOccupant CopySG-2 BScene Select, StartSequencing,Panic, Zone Lock,Partition, or Raise buttonScene Select, Stop Sequencing,Lower, or Off buttonSG-4 MAll Scene 1 or OFF ButtonControl UnitStatus LEDsControl Unit StatusSelection ButtonsSG-4 SIRM aster Raise/LowerSceneIndicatorLEDs4S-IR Infrared Receiver SceneSelection, OFF ButtonScene Selection ButtonsSG-4S, SG-4 NRL (No Raise/Lower)Master Raise/Lower IntensityControl (not available on SG-4 NRL)

2 SceneIndicatorLEDsScene Selection ButtonsOFF ButtonSG-4 PSPartitionStatusLEDsPartition StatusSelection ButtonsReset ButtonSG-4 BSceneIndicatorLEDsScene Selection 11/1/01 1:36 PM Page 23 Occupant CopyInstallation InstructionsWallstation circuits are classified as Class 2 circuits ( ) andPELV circuits (IEC). Unless otherwise specified, the voltages donot exceed 24 VAC or 15 VDC. As Class 2 circuits, they complywith the requirements of NFPA 70 National Electrical Code (NEC).As PELV circuits, they comply with the requirements of IEC60364-4-41, VDE 0100 Part 410, BS7671:1992 and otherequivalent standards.

3 When installing and wiring to theseWallstations, follow all applicable national and/or local wiringregulations. External circuits connected to input, output, RS232,DMX512, and other communication terminals of Wallstations ,must be supplied from a Listed Class 2 source or comply withthe requirements for PELV circuits, as applicable in your ! Lutron recommends that Wallstations be installed by aqualified electrician. Do not connect high-voltage power to low-voltage termi-nals. Improper wiring can result in personal injury ordamage to the control or to other equipment.

4 GRAFIK EyeWallstations must be connected to the GRAFIKEye Control Unit by using Class 2/PELV wiring methods perthe National Electrical Code. Check with your local electricalinspector for the local code requirements and wiringpractices allowed in your Notes System Maximums: 8 Unique GRAFIK Eyeaddresses per system. 16 Wallstations per system. GRAFIK Eye3000 Series Control Units can power amaximum of 3 Wallstations . 2000 ft. (600 m) wiring length. 0 C 40 C operating temperature. wallstation Wiring 3000 Series: Four #18 AWG ( mm2) Class 2/PELV wires (2 twisted, pair).

5 Lutron offers a one-cable, non-plenum, low-voltage solution (P/N GRX-CBL-346S-500), and a one-cable, plenum, low-voltage solution(P/N GRX-PCBL346S-500). Other suggested cables areBelden No. 9156, Alpha No. 1132, or equivalent, forGRAFIK Eye3000 Series Control Units. 4000 Series: Two #12 AWG ( mm2) Class 2/PELV wires and two shielded #18 AWG ( mm2) Class2/PELV wires (twisted, shielded pair). Lutron offers aone-cable (non-plenum), low-voltage solution (P/NGRX-CBL-46L). Power: wires 1 & 2, 12 VDC-24 VFW.

6 Data: wires 3 & 4, twisted, shielded pair. Terminal 2 (power) must not be connected between GRAFIKEye3000 Series Control 11/1/01 1:36 PM Page 341234123412345678910111213141516 Installation InstructionsOccupant CopyInstallationWarning:Always turn Off the circuitbreaker/MCB or remove the main fuse fromthe power line before doing any work. Failureto do so can result in serious personal wiring of Wallstations is dependent upon the GRAFIK EyeControl System that is providing power. GRAFIK Eye3000 Seriesand GRAFIK Eye4000 Series Control Units have different powerlimitations and wiring techniques.

7 Please confirm the type ofControl Unit to which the wallstation is being wired and use thecorresponding Instructions that Turn power Off. 2. Mount standard 1-gang wallbox, in. (70 mm) deep (available from Lutron P/N 241-519).3. Strip insulation from wires so that 3/8 in. (10 mm) of barewire is exposed for #18 AWG ( mm2) Remove the faceplate, adapter (if applicable), and buttonassembly from the wallstation to access DIP Address Wallstations . Each Wallstationin a system must be assigned a uniqueaddress.

8 Set DIP switches 1 4 of eachWallstation to one of the positions il-lustrated below and record its this addressSet switchesSet Switcheslike this:Location:like this:Location:6. Select function. Set DIP switches 5 and6 (and 7, if applicable) on theWallstation to select its function. DIPswitch settings and their correspondingfunction are shown in the chart on thenext Select Control type. Set DIP switches 7,8, and 9 or 8 and 9 (depending onControl type) on the wallstation toselect the Control type (refer to theSelect Control Type table on the Backlight Option.)

9 Your wallstation isfactory set for the backlight to be backlight can be switched on or offby setting DIP switch 234 SetAddress3/8 in. (10 mm) 11/1/01 1:36 PM Page 45 Occupant CopyInstallation InstructionsSG-4S, SG-4 SIRSG-4B, SG-4 NRLSG-4 PSSG-4 MWallstation5 6 Factory Set5 65 65 65 6 75 6 75 6 75 6 75 6 75 6 75 6 75 6 7 WallstationNote:If only one IR receiver is located in a room, the wallstation may be set to select any group of four scenes. However, if morethan one IR receiver is located in a room, all IR receivers in the room must be configured with the same scene , all IR Wallstations must be set to include scenes 1 4 if installed in the same room with a GRAFIK EyeControlUnit.

10 (GRAFIK EyeControl Unit scene buttons are always scenes 1 4.)Select Scenes 1 4 Not ApplicableFifth button turns ControlUnits On onlySelect Scenes 5 8 Not ApplicableNot ApplicableSelect Scenes 9 12 Not ApplicableNot ApplicableSelect Scenes 13 16 Not ApplicableFifth button turnsControl Units Off onlySG-2 BSelectScenes 1and OffSelectScenes 9and 10 SelectScenes 13and 14 PanicControlFineTuningControlPartitionSt atusControlZoneLockoutSequenceScenes5 16 DIP Switch Position7 8 9 ControlTypeSG-4S, SG-4B, SG-4 NRLSG-4 SIRSG-4 PSSG-4 MSG-2 BRefer to the Select Function table above forDip switch 7 FunctionSelect Control 11/1/01 1:36 PM Page 56 Installation InstructionsOccupant Copy432143219.