INSTALLATION INSTRUCTIONS62-0331-15 jade Economizer Module (MODEL W7220)This document describes wiring, power up, basic troubleshooting, and common installation issues for the jade Economizer Module (Model W7220). For further information on mounting and operation, refer to Honeywell document INSTALLATIONR eview the following before installing the The W7220:ElectricalRated Voltage: 20 to 30 Vac RMS; 50/60 HzTransformer: 100 VA maximum system inputRelay Digital Output Rating: 30 Vac IMPORTANTAll inputs and outputs must be Class 2 wiring. InputsA Mixed air (MA) analog sensor is required on all W7220 units; either an OA (Outdoor Air) sensor for dry bulb change over or an OA Sylkbus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Return Air (RA) Sylkbus sensor can be added to the system for differential enthalpy changeover.

JADE™ ECONOMIZER MODULE 62-0331—15 2 INSTALLATION AND SETUP The Economizer module may be mounted in any orientation. However, mounting in the orientation shown above permits proper viewing of the LCD display and use

Tags:

  Module, Economizers, Jade, Jade economizer module

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of JADE Economizer Module

1 INSTALLATION INSTRUCTIONS62-0331-15 jade Economizer Module (MODEL W7220)This document describes wiring, power up, basic troubleshooting, and common installation issues for the jade Economizer Module (Model W7220). For further information on mounting and operation, refer to Honeywell document INSTALLATIONR eview the following before installing the The W7220:ElectricalRated Voltage: 20 to 30 Vac RMS; 50/60 HzTransformer: 100 VA maximum system inputRelay Digital Output Rating: 30 Vac IMPORTANTAll inputs and outputs must be Class 2 wiring. InputsA Mixed air (MA) analog sensor is required on all W7220 units; either an OA (Outdoor Air) sensor for dry bulb change over or an OA Sylkbus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Return Air (RA) Sylkbus sensor can be added to the system for differential enthalpy changeover.

2 jade can be used with a CO2 indoor air sensor for Demand Control Ventilation and with a VFD for two speed fan (CO2) Sensor (C7232): 2-10 Vdc control signal; minimum impedance >50k signal: 2-10 Vdc; minimum actuator impedance is 2k ohm; Sylkbus two-wire output for Honeywell Sylk-bus communicating actuators. Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac)All Relay Outputs (at 30 Vac):Running: maximumInrush: maximumWhen Installing This these instructions carefully. Failure to follow them could damage the product or cause a hazard-ous ratings given in instructions and on the prod-uct to ensure the product is suitable for your must be a trained, experienced service installation is complete, check out product operation as provided in these additional detailed information on this product go to and download the product data sheet (lit no 63-2700) or scan QR code located on the label above MAT terminals with your smart phone.

3 Accessories50048926-001 2-pin edge connector for sensors (20 pieces per bag)50048926-002 6-pin edge connector for field wiring (20 pieces per bag) C7250 20k sensor for MA or OA (dry bulb changeover)C7400S Sylkbus sensor for enthalpy control in OA and/or RA and RA for differential dry bulb changeoverW7220 PCMOD interface tool for jade controller and Per-sonal Computer. Go to for the software50053060-001 Duct mounting kit for sensorsC7632 or C7232 CO2 sensors jade Economizer MODULE62-0331 152 INSTALLATION AND SETUPThe Economizer Module may be mounted in any orientation. However, mounting in the orientation shown above permits proper viewing of the LCD display and use of the : jade will be in the set up mode for the first 60 minutes after powered. If a sensor for OA air or Sylkbus device (sensor, actuator) is disconnected during the set up mode, the jade will not alarm that failure.

4 The MA sensor is a system critical sensor; if the MA sensor is removed during the set up mode, the jade will alarm. After 60 minutes the jade controller will change to operation mode and all components removed or failed will alarm in the operation mode. WIRINGAll wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Module wiring in the field is terminated to the four screw terminal blocks located on the left and right wiring at the OEM factory is terminated via the header pin terminals located on the left and right sides. The header terminal pins and the terminal blocks have common terminations for the appropriate input or output. The part number for the OEM female mating connector is Shock cause severe injury, death or property power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment Damage discharge can short equipment that you are properly grounded before handling the terminal can accommodate the following gauges of wire: Single wire from 18 AWG to 22 AWG solid or stranded Multiple wires up to two 22 AWG stranded For the 24 Vac connections: single wire from 14 to 18 AWG solid or strandedFor S-BUS wiring, the sensors may be mounted up to 200 ft.

5 (61 m) from the jade controller. When the length of wire is over 100 feet use twisted pair shielded :All wiring is polarity to Fig. 1 through Fig. 7 for common wiring configurations. Refer to Fig. 8 for use with the Smart VFD. Figure 8 shows how to make a single-speed blower operate with two speeds with jade . When the thermostat calls for first stage cooling or independent fan, the VFD will operate the fan at low speed. When the thermostat calls for first stage heat or second stage cooling, it will operate the fan at high speed. To achieve this, wire relays as shown, and configure the VFD to the minimum frequency for low speed fan, and for high speed fan configure Preset frequency 1, Wiring jade Economizer controller can only have one (1) communicating actuator connected to to four (4) non-communicating and (2) 2-posi-tion actuators (1 each on EXH1 and AUX1 O) (1) communicating and up to four (4) non-com-municating and (2) 2-position actuators (1 each on EXH1 and AUX1 O)When using a 2-position actuator on the AUX1 O the AUX1 O must be programmed for Exh2 and the % open is the % open of the outdoor damper when the 2-pos actuator opens.

6 Connect 24 V to Exh1 and/or AUX1 O and ground to the jade C the W7220 Economizer will not work with an old black motor M7415; replace the M7415 with a M7215 or MS3103 1. Economizer Module - Left hand terminal Lef t Terminal BlockMATMAT20k NTC and COMM ixed Air Temperature Sensor(polarity insensitive connection)OATOAT20k NTC and COMO utdoor Air Temperature Sensor(polarity insensitive connection)S-BUSS-BUSSYLK Bus Sylk Bus sensor (polarity insensitive connection)Bottom Left Terminal BlockIAQ 2-102-10 VdcAir Quality Sensor Input ( CO2 sensor)IAQ COMCOMAir Quality Sensor CommonIAQ 24V24 VacAir Quality Sensor 24 Vac SourceACT 2-102-10 VdcDamper Actuator Output (2-10 Vdc)ACT COM COMD amper Actuator Output CommonACT 24V24 VacDamper Actuator 24 Vac SourceTable 2. Economizer Module - Right hand terminal Right Terminal Blockn/aThe first terminal is not usedAUX2 I24 Vac INShut Down (SD) or Heat (W) Conventional only or Heat Pump Changeover (O/B) in Heat Pump Vac INOccupied / Unoccupied InputE-GNDEGNDE arth Ground - System RequiredEXH124 Vac OUT Exhaust Fan 1 OutputJADE Economizer MODULE362-0331 15 Fig.

7 1. Stand-alone dry bulb Economizer configuration with black motor M7215. AUX1 O24 Vac OUT Programmable: Exhaust fan 2 output or ERV or System Alarm output. Bottom Right Terminal BlockY2-I24 Vac INY2 in - Cooling Stage 2 Input from space thermostatY2-O24 Vac OUT Y2 out - Cooling Stage 2 Output to stage 2 mechanical coolingY1-I24 Vac INY1 in - Cooling Stage 1 Input from space thermostatY1-O24 Vac OUT Y1 out - Cooling Stage 1 Output to stage 1 mechanical coolingCCOM24 Vac CommonR24 Vac24 Vac Power (Hot)Table 2. Economizer Module - Right hand terminal blocks. (Continued)LabelTypeDescriptionROOF TOP UNITY1OY2OY1IY2 IOCC24 VAC1K11K1E-GNDY1GW2W1Y2O/BOCCW7220 Economizer CONTROLLER MODULETHERMOSTATCO2 SENSOR2-10 VDC(OPTIONAL)MAMAOATOATC RM28980 DIAQ (2-10V)IAQ COMIAQ 24 VACT (2-10V)ACT COMACT 24 VAUX1-0 AUX2-IOA TEMPSENSOR20K NTCM7215 NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND TEMPSENSOR20K NTC+-TR1 TRININ2R(+)C(-) jade Economizer MODULE62-0331 154 Fig.

8 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7503 Direct Coupled TOP UNITY1OY2OY1IY2 IOCC24 VACE-GNDY1GW2W1Y2O/BOCCW7220 Economizer CONTROLLER MODULETHERMOSTATCO2 SENSOR2-10 VDC(OPTIONAL)MATMATOATOATC RM32564 DIAQ (2-10V)IAQ COMIAQ 24 VACT (2-10V)ACT COMACT 24V3 OAT TEMPSENSOR20K NTCMS7503 OR MS7505 NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND TEMPSENSOR20K NTCR(+)C(-)AUX1-0 AUX2-I23231K11K1 jade Economizer MODULE562-0331 15 Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating TOP UNITY1OY2OY1IY2 IOCC24 VACE-GNDY1GW2W1Y2O/BOCCW7220 Economizer CONTROLLER MODULETHERMOSTATCO2 SENSOR2-10 VDC(OPTIONAL)MATMATOATOATC RR(+)C(-)M32650 DIAQ (2-10V)IAQ COMIAQ 24 VACT (2-10V)ACT COMACT 24V312 OAT TEMPSENSOR20K NTCMS3103J OR MS3105J11MA TEMPSENSOR20K NTCS-BUS45S-BUSAUX1-0 AUX2-INOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND Economizer MODULE62-0331 156 Fig.

9 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black AIRTEMP/HUMIDITY (ENTHALPY)SYLKBUS SENSORRETURN AIRTEMP/HUMIDITY (ENTHALPY)SYLKBUS SENSORROOF TOP UNITY1OY2OY1IY2 IOCCE-GNDY1GW2W1Y2O/BOCCW7220 Economizer CONTROLLER MODULETHERMOSTATMATMATC RR(+)C(-)M32565 DIN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND VDC(OPTIONAL)IAQ (2-10V)IAQ COMIAQ 24 VACT (2-10V)ACT COMACT 24V+-TR1 TRININM7215MA TEMPSENSOR20K NTCAUX1-0 AUX2-I32431K11K124 VACJADE Economizer MODULE762-0331 15 Fig.

10 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct Coupled AIRTEMP/HUMIDITY (ENTHALPY)SYLKBUS SENSORRETURN AIRTEMP/HUMIDITY (ENTHALPY)SYLKBUS SENSORROOF TOP UNITY1OY2OY1IY2 IOCCE-GNDY1GW2W1Y2O/BOCCW7220 Economizer CONTROLLER MODULETHERMOSTATC RR(+)C(-)M32566 DIN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND MS7503 OR MS75053S-BUSS-BUSMATMATCO2 SENSOR2-10 VDC(OPTIONAL)IAQ (2-10V)IAQ COMIAQ 24 VACT (2-10V)ACT COMACT 24 VMA TEMPSENSOR20K NTCAUX1-0 AUX2-I234341K11K124 VACJADE Economizer MODULE62-0331 158 Fig.