Instruction Manual D103151X012 67D Series April 2017. 67d series pressure reducing regulators Type 67D or 67DR Regulator Type 67DF or 67 DFR Filtered Regulator Figure 1. 67d series pressure reducing regulators Installation, operation and maintenance ! Warning procedures performed by unqualified personnel may result in improper Failure to follow these instructions or adjustment and unsafe operation. Either to properly install and maintain this condition may result in equipment equipment could result in an explosion, damage or personal injury. Use qualified fire and/or chemical contamination personnel when installing, operating causing property damage and personal and maintaining the 67D Series Pressure injury or death. Reducing Regulators . Fisher Regulators must be installed, operated and maintained Introduction in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Scope of the Manual Technologies, Inc.

67D Series Pressure Reducing Regulators TyPe 67D oR 67DR RegulaToR TyPe 67DF oR 67DFR FilTeReD RegulaToR Figure 1. 67D Series Pressure Reducing Regulators installation, operation and maintenance

Tags:

  Series, Pressure, Reducing, Regulators, 67d series pressure reducing regulators

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Manual: 67D Series Pressure Reducing Regulators

1 Instruction Manual D103151X012 67D Series April 2017. 67d series pressure reducing regulators Type 67D or 67DR Regulator Type 67DF or 67 DFR Filtered Regulator Figure 1. 67d series pressure reducing regulators Installation, operation and maintenance ! Warning procedures performed by unqualified personnel may result in improper Failure to follow these instructions or adjustment and unsafe operation. Either to properly install and maintain this condition may result in equipment equipment could result in an explosion, damage or personal injury. Use qualified fire and/or chemical contamination personnel when installing, operating causing property damage and personal and maintaining the 67D Series Pressure injury or death. Reducing Regulators . Fisher Regulators must be installed, operated and maintained Introduction in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Scope of the Manual Technologies, Inc.

2 Instructions. This manual provides instructions for the installation, If the regulator vents gas or a leak maintenance and parts ordering information for develops in the system, service to 67D Series Regulators . Instructions and parts lists for the unit may be required. Failure other equipment mentioned in this instruction manual, to correct trouble could result in a as well as for other 67 Series Regulators , are found in hazardous condition. separate manuals. 67D Series Specifications This section lists the specifications for the 67D Series Regulators . Factory specification such as type, maximum inlet Pressure and outlet Pressure are stamped on the nameplate fastened on the regulator at the factory. Available Configurations Temperature Capabilities(1) (continued). Type 67D: Direct-operated regulator with aluminum With Fluorocarbon (FKM): body and without internal relief Polyethylene Filter(4) (Standard): Type 67DR: Aluminum body with internal relief 0 to 180 F / -18 to 82 C.

3 Type 67DS: Stainless steel body without internal relief Polyvinylidene (PVDF), Stainless steel or Glass Type 67 DSR: Stainless steel body with internal relief Filter (Optional): 0 to 300 F / -18 to 149 C. Type 67DF: Aluminum body with filter and without With Silicone (VMQ)(2) Diaphragm, internal relief Low Temperature Nitrile (NBR) O-rings and Type 67 DFR: Aluminum body with filter and Low Temperature Bolting: internal relief -60 to 180 F / -51 to 82 C. Type 67 DFS: Stainless steel body with filter and With Gauges: -20 to 180 F / -29 to 82 C. without internal relief With Automatic Drain: 40 to 175 F / 4 to 79 C. Type 67 DFSR: Stainless steel body with filter and Types 67DF, 67 DFR, 67 DFS and 67 DFSR. internal relief Filter Capabilities Body Size, Inlet and Outlet Connection Style Micron Rating: 1/2 NPT Polyethylene Filter(4) (Standard): 5 microns Maximum Inlet Pressure (Body Rating)(1) Glass Fiber Filter (Optional): 5 microns All filtered models: 250 psig / bar PVDF or Stainless Steel Filter (Optional): 40 microns All unfiltered models: 400 psig / bar Spring Case Vent Location Outlet Pressure Ranges Aligned with inlet standard, other positions optional See Table 1 Drain Valve Location Maximum Emergency Outlet Pressure (1) Aligned in the center of the dripwell 150 psi / bar over outlet Pressure setting up Pressure Registration to a maximum of 250 psi / bar Internal Wide-Open Flow Coefficients Options Main Valve: Cg: ; Cv: ; C1: All Types Internal Relief Valve: Cg: ; Cv.

4 C1: Handwheel adjusting screw IEC Sizing Coefficient NACE International MR0175 or Xt: MR0103(3) construction Types 67DR, 67 DSR, 67 DFR and 67 DFSR Panel mount (includes spring case with 1/4 NPT. Internal Relief Performance vent, handwheel and panel mounting nut). Low capacity for minor seat leakage only; other Closing cap (available on spring case with overpressure protection must be provided if inlet 1/4 NPT vent). Pressure can exceed the maximum Pressure rating Fluorocarbon (FKM) elastomers for high of downstream equipment or exceeds maximum temperatures and/or corrosive chemicals outlet Pressure rating of the regulator. Silicone (VMQ) elastomers for cold temperatures Approximate Weights Fixed Bleed Restriction Types 67D and 67DR: lbs / kg Triple scale outlet Pressure gauge (brass or Types 67DF and 67 DFR: lbs / 1 kg stainless steel). Types 67DS and 67 DSR: lbs / 1 kg Stainless steel stem and valve plug Types 67 DFS and 67 DFSR: lbs / 2 kg Pipe plug in second outlet Smart Bleed Check Valve Setpoint Types 67 DFR and 67 DFSR.

5 6 psi / bar differential Smart Bleed internal check valve Temperature Capabilities(1) Types 67DF, 67 DFR, 67 DFS and 67 DFSR. With Nitrile (NBR): Stainless steel drain valve Standard Bolting: -20 to 180 F / -29 to 82 C. Stainless Steel Bolting: -40 to 180 F / -40 to 82 C. 1. The Pressure /temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded. 2. Silicone (VMQ) is not compatible with hydrocarbon gas. 3. Product complies with the material requirements of NACE International MR0175 or MR0103. Environmental limits may apply. 4. Do not use in high aromatic hydrocarbon service. 2. Type XXXX. 67D Series Type 67D or 67DS Type 67DF or 67 DFS. M1153 M1154. Smart Bleed Option For Type 67 DFR or 67 DFSR. Type 67DR or 67 DSR Type 67 DFR or 67 DFSR. INLET Pressure . OUTLET Pressure . ATMOSPHERIC Pressure . Figure 2. 67D Series Operational Schematics INLET Pressure .

6 OUTLET Pressure . Product Descriptions ATMOSPHERIC Pressure . Internal Relief (Types 67DR, 67 DSR, LOADING Pressure . The 67D Series direct-operated Regulators are typically 67 DFR and 67 DFSR). INTERMEDIATE Pressure . used to provide constantly controlled, reduced pressures. If for some reason, outside of normal operating PILOT SUPPLY Pressure . They are suitable for most air or gas applications. conditions, the downstream Pressure exceeds the The Types 67D and 67DS are the standard setpoint of the regulator, the force created by the instrument supply Regulators without a filter or downstream Pressure will lift the diaphragm until internal relief. the diaphragm is lifted off the relief seat. This allows flow through the token relief. The relief valve on The Types 67DF and 67 DFS are equipped with a the Type 67DR, 67 DSR, 67 DFR or 67 DFSR is an filter for removing particles from the supply gas. elastomer plug that prevents leakage of air from the The Types 67DR and 67 DSR have an internal relief downstream to atmosphere during normal operation, valve with a soft seat for reliable shutoff with no thereby conserving plant air.

7 Discernible leakage. The Types 67 DFR and 67 DFSR have a filter and Smart Bleed Airset internal relief valve with a soft seat for reliable In some cases, it is desired to exhaust downstream shutoff with no discernible leakage. Pressure if inlet Pressure is lost or drops below the setpoint of the regulator. For example, if the regulator Principle of Operation is installed on equipment that at times has no flow demand but is expected to backflow on loss of inlet Downstream Pressure is registered internally on the Pressure . The Type 67 DFR or 67 DFSR can be ordered lower side of the diaphragm. When the downstream with the Smart Bleed option which includes an internal Pressure is at or above the set Pressure , the valve plug check valve for this application. During operation, if is held against the orifice and there is no flow through inlet Pressure is lost, or decreases below the setpoint of the regulator. When demand increases, downstream the regulator, the downstream Pressure will back flow Pressure drops slightly allowing the spring to extend, upstream through the regulator and check valve.

8 This moving the stem down and the valve plug away from option eliminates the need for a fixed bleed downstream the orifice. This allows flow through the regulator. of the regulator, thereby conserving plant air. 3. 67D Series Table 1. Outlet Pressure Ranges and Control Spring Data OUTLET Pressure CONTROL SPRING DATA. Type RANGES Wire Diameter Free Length Part Number Color Material psig bar In. mm In. mm 0 to 20 0 to GE07809T012 Green stripe 0 to 35 0 to T14059T0012 Unpainted Music Wire 0 to 60 0 to T14058T0012 Blue stripe 67D, 67DR, 0 to 125 0 to T14060T0012 Red stripe 67DF and 67 DFR 0 to 35 0 to T14113T0012 Silver stripe 0 to 60 0 to T14114T0012 Blue Inconel 0 to 125 0 to T14115T0012 Red 0 to 20 0 to 10C1729X012 Green 67DS, 67 DSR, 0 to 35 0 to T14113T0012 Silver stripe 67 DFS and 0 to 60 0 to T14114T0012 Blue Inconel 67 DFSR 0 to 125 0 to T14115T0012 Red 0 to 150 0 to 10C1730X012 Black Installation A regulator may vent some gas to the atmosphere.

9 In hazardous or Note flammable gas service, vented gas may If the regulator is shipped mounted on accumulate and cause personal injury, another unit, install that unit according death or property damage due to fire or to the appropriate Instruction Manual. explosion. Vent a regulator in hazardous gas service to a remote, safe location away from air intakes or any hazardous ! Warning area. The vent line or stack opening must be protected against condensation Personal injury, property damage, or clogging. equipment damage or leakage Before installing a Type 67D, 67DR, 67DS, 67 DSR, due to escaping gas or bursting of 67DF, 67 DFR, 67 DFS or 67 DFSR regulator, be Pressure -containing parts may result sure the installation complies with the following if this regulator is overpressured or installation guidelines: is installed where service conditions could exceed the limits given in the 1. Regulator operation within ratings does not Specifications section, or where preclude the possibility of damage from debris conditions exceed any ratings of the in the lines or from external sources.

10 Regulators adjacent piping or piping connections. should be inspected for damage periodically and To avoid such injury or damage, provide after any overpressure condition. Pressure -relieving or Pressure -limiting devices (as required by the appropriate 2. Only personnel qualified through training and code, regulation or standard) to prevent experience should install, operate and maintain service conditions from exceeding the regulator. Make sure that there is no damage those limits. to or foreign material in the regulator. Also ensure that all tubing and piping is free of debris. The internal relief valve of the Type 67DR, 67 DSR, 67 DFR or 67 DFSR 3. Install the regulator so that flow is from the IN to the does not provide full overpressure OUT connection as marked on the regulator body. protection. The internal relief valve is 4. A clogged spring case vent hole may cause the designed for minor seat leakage only.