Manual: Rosemount Magnetic Flowmeter 8732EM …

Reference manual00809-0100-4444, Rev AFDecember 2017 Rosemount 8732EM Transmitter with HARTP rotocol Reference ManualContentsChapter 1 Safety messages .. 1 Chapter 2 Introduction .. description .. recycling/disposal ..7 Chapter 3 Sensor Installation .. and Lifting Safety .. and Position .. Installation .. reference connection ..20 Chapter 4 Remote Transmitter Installation .. symbols .. 29 Chapter 5 Basic Configuration .. jam screw .. Setup .. operator interface (LOI) .. Communicator interface .. units .. 47 Chapter 6 Advanced installation details .. switches .. loops .. housing configuration ..62 Chapter 7 Operation .. operator interface (LOI) .. Communicator interface .. 79 Chapter 8 Advanced Configuration Functionality .. outputs .. HART .. LOI .. parameters .. special units.

Reference manual 00809-0100-4444, Rev AF December 2017 Rosemount® 8732EM Transmitter with HART Protocol Reference Manual

Tags:

  Manual, Rosemount, Flowmeter, Magnetic, 8732em, Rosemount magnetic flowmeter 8732em

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Manual: Rosemount Magnetic Flowmeter 8732EM …

1 Reference manual00809-0100-4444, Rev AFDecember 2017 Rosemount 8732EM Transmitter with HARTP rotocol Reference ManualContentsChapter 1 Safety messages .. 1 Chapter 2 Introduction .. description .. recycling/disposal ..7 Chapter 3 Sensor Installation .. and Lifting Safety .. and Position .. Installation .. reference connection ..20 Chapter 4 Remote Transmitter Installation .. symbols .. 29 Chapter 5 Basic Configuration .. jam screw .. Setup .. operator interface (LOI) .. Communicator interface .. units .. 47 Chapter 6 Advanced installation details .. switches .. loops .. housing configuration ..62 Chapter 7 Operation .. operator interface (LOI) .. Communicator interface .. 79 Chapter 8 Advanced Configuration Functionality .. outputs .. HART .. LOI .. parameters .. special units.

2 109 Chapter 9 Advanced Diagnostics Configuration .. and enabling .. empty pipe detection .. temperature .. fault detection .. process noise detection .. electrode detection ..117 ContentsReference mA loop verification .. Meter Verification .. manual SMART Meter Verification .. SMART Meter Verification .. Meter Verification test results .. Meter Verification measurements .. the SMART Meter Verification .. 129 Chapter 10 Digital Signal Processing .. messages .. noise profiles .. process noise diagnostic .. flow reading in noisy applications .. of signal processing algorithm ..138 Chapter 11 Maintenance .. information .. a Local Operator Interface (LOI) .. 8732EM electronics stack .. a socket module/terminal block ..151 Chapter 12 Troubleshooting .. information .. check and guide.

3 Messages .. troubleshooting .. troubleshooting .. sensor tests .. sensor tests .. support ..178 Appendices and referenceAppendix AProduct Specifications .. 8700M Flowmeter Platform specifications .. specifications .. Flanged Sensor Specifications .. Wafer Sensor Specifications .. Hygienic (Sanitary) Sensor Specifications ..202 Appendix BProduct Certifications .. 207 Appendix CWiring Diagrams .. sensor to transmitter .. Smart Wireless THUM Adapter wiring diagrams .. Field Communicator wiring diagrams .. 214 Appendix DImplementing a Universal Transmitter ..217 ContentsiiRosemount 8732EM Transmitter with HART Protocol Reference messages .. capability .. step process .. the universal transmitter .. sensors .. sensors .. and Hauser sensors .. and Porter sensors .. sensors .. Veriflux VTC sensor.

4 Sensors .. sensors .. sensors .. Honeywell sensors .. sensors .. manufacturer sensor to 8732 Transmitter .. 246 ContentsReference manualiiiContentsivRosemount 8732EM Transmitter with HART Protocol Reference Manual1 Safety messagesWARNING!General hazards. Failure to follow these instructions could result in death or serious injury. Read this manual before working with the product. For personal and system safety, andfor optimum product performance, make sure you thoroughly understand the contentsbefore installing, using, or maintaining this product. Installation and servicing instructions are for use by qualified personnel only. Do notperform any servicing other than that contained in the operating instructions, unlessqualified. Verify the installation is completed safely and is consistent with the operatingenvironment.

5 Do not substitute factory components with non-factory compenents. Substitution ofcomponents may impair Intrinsic Safety. Do not perform any services other than those contained in this manual . Process leaks may result in death or serious injury. Mishandling products exposed to a hazardous substance may result in death or seriousinjury. The electrode compartment may contain line pressure; it must be depressurized beforethe cover is removed. If the product being returned was exposed to a hazardous substance as defined byOSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardoussubstance identified must be included with the returned goods. The products described in this document are NOT designed for nuclear-qualifiedapplications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.

6 For information onRosemount nuclear-qualified products, contact your local Emerson ProcessManagement Sales messagesReference manual1 WARNING!Explosion hazards. Failure to follow these instructions could cause an explosion, resulting indeath or serious injury. If installed in explosive atmospheres [hazardous areas, classified areas, or an Ex environment], it must be assured that the device certification and installationtechniques are suitable for that particular environment. Do not remove transmitter covers in explosive atmospheres when the circuit is transmitter covers must be fully engaged to meet explosion-proof requirements. Do not disconnect equipment when a flammable or combustible atmosphere is present. Before connecting a HART-based communicator in an explosive atmosphere, make surethe instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.

7 Do not connect a Rosemount transmitter to a non- Rosemount sensor that is located inan explosive atmosphere. The transmitter has not been evaluated for use with othermanufacturers' Magnetic Flowmeter sensors in hazardous (Ex or Classified) care should be taken by the end-user and installer to ensure the transmittermeets the safety and performance requirements of the other manufacturer sequipment. Follow national, local, and plant standards to properly earth ground the transmitter andsensor. The earth ground must be separate from the process reference ground. Rosemount Magnetic Flowmeters ordered with non-standard paint options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic chargebuild-up, do not rub the Flowmeter with a dry cloth or clean with !Electrical hazards.

8 Failure to follow these instructions could cause damaging and unsafedischarge of electricity, resulting in death or serious injury. Follow national, local, and plant standards to properly earth ground the transmitter andsensor. The earth ground must be separate from the process reference ground. Disconnect power before servicing circuits. Allow ten minutes for charge to dissipate prior to removing electronics compartmentcover. The electronics may store energy in this period immediately after power isremoved. Avoid contact with leads and terminals. High voltage that may be present on leads couldcause electrical shock. Rosemount Magnetic Flowmeters ordered with non-standard paint options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic chargebuild-up, do not rub the Flowmeter with a dry cloth or clean with messages2 Rosemount 8732EM Transmitter with HART Protocol Reference ManualNOTICED amage hazards.

9 Failure to follow these instructions could resulting damage or destruction ofequipment. The sensor liner is vulnerable to handling damage. Never place anything through thesensor for the purpose of lifting or gaining leverage. Liner damage may render thesensor inoperable. Metallic or spiral-wound gaskets should not be used as they will damage the liner face ofthe sensor. If spiral wound or metallic gaskets are required for the application, liningprotectors must be used. If frequent removal is anticipated, take precautions to protectthe liner ends. Short spool pieces attached to the sensor ends are often used forprotection. Correct flange bolt tightening is crucial for proper sensor operation and life. All boltsmust be tightened in the proper sequence to the specified torque specifications. Failureto observe these instructions could result in severe damage to the sensor lining andpossible sensor replacement.

10 In cases where high voltage/high current are present near the meter installation, ensureproper protection methods are followed to prevent stray electricity from passingthrough the meter. Failure to adequately protect the meter could result in damage tothe transmitter and lead to meter failure. Completely remove all electrical connections from both sensor and transmitter prior towelding on the pipe. For maximum protection of the sensor, consider removing it fromthe pipeline. Do not connect mains or line power to the Magnetic flowtube sensor or to thetransmitter coil excitation messagesReference manual3 Safety messages4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual2 IntroductionTopics covered in this chapter: System description Product descriptionThe 8700M Magnetic Flowmeter Platform consists of a sensor and a transmitter.