Medium Voltage Conductor Ampacities

Page 1 of 6 Energy | | GUIDELINEF ebruary, 2018TG84 Voltage Conductor AmpacitiesCOPPERC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105 CMV-105213014515016511551751701901/01802 001952152/02052252252553/02402702602904/ 0280305295330250315355330365350385430395 4405004755304805357506006655856551000690 770675755 Single Conductor 5kV - 35kVALUMINUMC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105 CMV-105210011511513011201351301501/01401 551501702/01601751752003/01902102002254/ 0215240230260250250280255290350305340310 3505003804253854307504905454855401000580 645565640 Based on NEC Table (C)(73) Ampacities of an Insulated Triplexed or Three Single Conductor Co

Single Copper Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)1. Based on NEC Table 310.60(C)(68) Ampacities of an Insulated Single Aluminum Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F)

Tags:

  Medium, Copper, Voltage, Conductor, Copper conductors, Ampacities, Medium voltage conductor ampacities

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Medium Voltage Conductor Ampacities

1 Page 1 of 6 Energy | | GUIDELINEF ebruary, 2018TG84 Voltage Conductor AmpacitiesCOPPERC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105 CMV-105213014515016511551751701901/01802 001952152/02052252252553/02402702602904/ 0280305295330250315355330365350385430395 4405004755304805357506006655856551000690 770675755 Single Conductor 5kV - 35kVALUMINUMC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105 CMV-105210011511513011201351301501/01401 551501702/01601751752003/01902102002254/ 0215240230260250250280255290350305340310 3505003804253854307504905454855401000580 645565640 Based on NEC Table (C)(73) Ampacities of an Insulated Triplexed or Three Single Conductor copper Cables in Isolated Conduit in Air Based on Conductor Temperatures of 90 C (194 F) and 105 C and (221 F) and Ambient Air Temperature of 40 C (104 C) on NEC Table (C)(74)

2 Ampacities of an Insulated Triplexed or Three Single Conductor Aluminum Cables in Isolated Conduit in Air Based on Conductor Temperatures of 90 C (194 F) and 105 C and (221 F) and Ambient Air Temperature of 40 C (104 C) NEC 2014. Always refer to latest NEC 2 of 6 Energy | | GUIDELINEF ebruary, 2018TG84 Voltage Conductor AmpacitiesCOPPERC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105 CMV-105216017517019511852051952251/02152 402252552/02502752602953/02903203003404/ 0335375345390250375415380430350465515470 5255005806455806507507508357308201000880 980850950 Single Conductor 5kV - 35kVALUMINUMC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105

3 CMV-105212513513015011451601501751/01701 851752002/01952152002303/02252502302654/ 0265290270305250295325300335350365405370 4155004605104605157506006655906601000715 800700780 Based on NEC Table (C)(67) Ampacities of Insulated Single copper Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90 C (194 F) and 105 C (221 F) and Ambient Air Temperature of 40 C (104 F) on NEC Table (C)(68) Ampacities of an Insulated Single Aluminum Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90 C (194 F) and 105 C (221 F) and Ambient Air Temperature of 40 C (104 F) NEC 2014.

4 Always refer to latest NEC 3 of 6 Energy | | GUIDELINEF ebruary, 2018TG84 Voltage Conductor AmpacitiesCOPPERC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105 CMV-105213514515016011551651701851/01751 901952102/02002202202353/02302502502704/ 0265285285305250290315310335350355380375 4005004304604504857505305705455851000600 645615660 Multiconductor Conductor 5kV - 35kVALUMINUMC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105

5 CMV-105210511011512511201301351451/01401 501501652/01601701701853/01801951952104/ 0205220220240250230245245265350280310295 3155003403653553857504254604404751000495 535510545 Based on NEC Table (C)(79) Ampacities of Three Insulated copper Conductors Cabled Within an Overall Covering (Three- Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct) Based on Ambient Earth Temperature of 20 C (68 F), Electrical Duct Arrangement in Accordance with Figure , 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90 C (194 F) and 105 C (221 F).

6 One Circuit (See Figure , Detail 1.) on NEC Table (C)(80) Ampacities of Three Insulated Aluminum Conductors Cabled Within an Overall Covering (Three- Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct) Based on Ambient Earth Temperature of 20 C (68 F), Electrical Duct Arrangement in Accordance with Figure , 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90 C (194 F) and 105 C (221 F). One Circuit (See Figure , Detail 1.)

7 NEC 2014. Always refer to latest NEC 4 of 6 Energy | | GUIDELINEF ebruary, 2018TG84 Voltage Conductor AmpacitiesCOPPERC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105 CMV-105218019018520012002152102251/02302 452402552/02602802702903/02953203053304/ 0335360350375250365395380410350440475460 4955005305705505907506507006657201000730 785750810 Multiconductor Conductor 5kV - 35kVALUMINUMC onductor Size AWG/kcmil2001 - 5000 V5001 - 35000 V90 CMV-90105 CMV-10590 CMV-90105

8 CMV-105214015014515511551701651751/01801 901852002/02052202102253/02302502402604/ 0260280270295250285310300320350345375360 3905004204504354707505205605405801000600 650620665 Based on NEC Table (C)(83) Ampacities of Three Insulated copper Conductors Cabled Within an Overall Covering (Three- Conductor Cable) Directly Buried in Earth Based on Ambient Earth Temperature of 20 C (68 F), Arrangement per Figure , 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90 C (194 F) and 105 C (221 F).

9 One Circuit (See Figure , Detail 5.)1 Based on NEC Table (C)(84) Ampacities of Three Insulated Aluminum Conductors Cabled Within an Overall Covering (Three- Conductor Cable) Directly Buried in Earth Based on Ambient Earth Temperature of 20 C (68 F), Arrangement per Figure , 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90 C (194 F) and 105 C (221 F). One Circuit (See Figure , Detail 5.)11 Per NEC 2014. Always refer to latest NEC 5 of 6 Energy | | GUIDELINEF ebruary, 2018TG84 Temperature Correction FactorsTemperature Rating of the ConductorAmbient Temperature ( C)90 C105 CAmbient Temperature ( F)10 or or on NEC Table (C)(4).

10 For ambient temperatures other than 40 C (104 F), multiply the allowable Ampacities specified in the ampacity tables by the appropriate factor shown NEC 2014. Always refer to latest NEC 6 of 6 Energy | | GUIDELINEF ebruary, 2018TG84 Voltage Cables (MV-105 and MV UD) Voltage RatingsVoltage RatingInsulation LevelNominal Thickness (mils)5kV100%905kV133%1158kV100%1158kV13 3%14015kV100%17515kV133%22025kV100%26028 kV100%28025kV133%32028kV133%34535kV100%3 4535kV133%420 Minimum Size (AWG) Voltage RatingMinimum Size (AWG )5kV88kV615kV225kV135kV1/0 Voltage and insulation level, per UL 1072, ICEA S 93-639 and ICEA S 97-682, section 4, table 4-7.