Micro Motion Compact Density Meters Installation …

Installation ManualMMI-20020974, Rev ADMay 2018 Micro Motion Compact Density MetersPeak performance precision Density meter installationSafety and approval informationThis Micro Motion product complies with all applicable European directives when properly installed in accordance with theinstructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration ofconformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available onthe internet at or through your local Micro Motion support affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not informationFull product specifications can be found in the product data sheet.

Installation Manual MMI-20020974, Rev AD May 2018 Micro Motion® Compact Density Meters Peak performance precision density meter installation

Tags:

  Density

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Micro Motion Compact Density Meters Installation …

1 Installation ManualMMI-20020974, Rev ADMay 2018 Micro Motion Compact Density MetersPeak performance precision Density meter installationSafety and approval informationThis Micro Motion product complies with all applicable European directives when properly installed in accordance with theinstructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration ofconformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available onthe internet at or through your local Micro Motion support affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not informationFull product specifications can be found in the product data sheet.

2 Troubleshooting information can be found in the configurationmanual. Product data sheets and manuals are available from the Micro Motion web site at policyFollow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with governmenttransportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not acceptyour returned equipment if you fail to follow Micro Motion procedures and forms are available on our web support site at , or by phoning the Micro Motion CustomerService Flow customer serviceEmail: Worldwide: Asia-Pacific: and South AmericaEurope and Middle EastAsia PacificUnited 240 1978 Australia800 158 727 Canada+1 303-527-5200 The Netherlands+31 (0) 704 136 666 New Zealand099 128 804 Mexico+41 (0) 41 7686 111 France0800 917 901 India800 440 1468 Argentina+54 11 4837 7000 Germany0800 182 5347 Pakistan888 550 2682 Brazil+55 15 3413 8000 Italy8008 77334 China+86 21 2892 9000 Central & Eastern+41 (0) 41 7686 111 Japan+81 3 5769 6803 Russia/CIS+7 495 981 9811 South Korea+82 2 3438 4600 Egypt0800 000 0015 Singapore+65 6 777 8211 Oman800 70101 Thailand001 800 441 6426 Qatar431 0044 Malaysia800 814 008 Kuwait663 299 01 South Africa800 991 390 Saudi Arabia800 844 9564 UAE800 0444 0684 ContentsChapter 1 Planning.

3 Checklist .. practices .. drop in the meter .. requirements .. a pre- Installation meter check ..11 Chapter 2 Mounting .. the meter .. the electronics on the meter (optional) .. the display on the transmitter (optional) ..15 Chapter 3 Wiring .. and wiring requirements .. or non-hazardous output wiring .. safe output wiring .. wiring for remote-mount 2700 FOUNDATION fieldbus option .. to external devices (HART multidrop) .. to signal converters and/or flow computers .. 40 Chapter 4 Grounding ..43 ContentsInstallation Manual iContentsiiMicro Motion Compact Density Meter1 PlanningTopics covered in this chapter: Installation checklist Best practices Pressure drop in the meter Power requirements Perform a pre- Installation meter checklist Make sure that the hazardous area specified on the approval tag is suitable for theenvironment in which the meter will be installed.

4 Verify that the local ambient and process temperatures are within the limits of themeter. If your meter will be wired to a remote-mount 2700 FOUNDATION fieldbustransmitter:- Refer to the instructions in this manual for preparing the 4-wire cable and wiringto the processor Refer to the instructions in the transmitter Installation manual for mounting andwiring the 2700 FOUNDATION fieldbus Consider the maximum cable length between the meter and transmitter. Themaximum recommended distance between the two devices is 1000 ft (300 m). Micro Motion recommends using Micro Motion cable. For optimal performance, install the meter in the preferred meter will work in any orientation as long as the vibrating tubes remain full ofthe process fluid.

5 However, you should validate the meter performance prior tooperation if you have installed it in a non-preferred meter orientationTable 1-1: Liquids and slurries Install the meter so that the flow direction arrow on the meter case matches theactual forward flow of the process. (Flow direction is also software-selectable.) For optimal performance, thermally insulate the meter and the inlet and bypass-loop pipeline to maintain stable Manual 1 Micro Motion offers a soft, weather-proof insulating jacket that is easily fitted to allCDM practicesThe following information can help you get the most from your meter. Handle the meter with care. Follow local practices for lifting or moving the meter. Perform a Known Density Verification (KDV) check of the meter prior to installingthe meter in your system.

6 Install the meter in the preferred orientation in a vertical pipeline with liquids andslurries flowing you do not install the meter in the preferred orientation, you may need to apply a fieldoffset to ensure optimal performance. Refer to your organizational standards for samplingand reference measurement to determine what the offset may be. Do not apply a compression force greater than 200 lbs ( kg) when installing themeter. Thermally insulate the meter and the inlet and bypass-loop pipeline to maintainstable temperatures. There are no pipe run requirements for Micro Motion Meters . Straight runs of pipeupstream or downstream are unnecessary. Keep the meter tubes full of process fluid. For halting flow through the meter with a single valve, install the valve downstreamfrom the meter.

7 Minimize bending and torsional stress on the meter. Do not use the meter to alignmisaligned piping. The meter does not require external supports. The flanges will support the meter inany orientation. Installing the meter in a bypass configuration allows you to remove the meter forservicing or calibration without affecting the main pipeline (Section ). For bypass configurations using a pump, install the pump downstream of the meterto avoid pump heat transfer. For bypass configurations, maintain a target flow through the meter to ensuresample integrity and consistent temperature with the main installations for bypass configurationsThe following figures illustrate typical bypass configurations for installing the Motion Compact Density MeterBypass Installation : S-BendFigure 1-1: Bypass Installation : Pressure bendFigure 1-2: Bypass Installation : Laminar flowFigure 1-3: ImportantThe laminar flow Installation is only recommended for processes using refined, clean fluids with Manual 3 Bypass Installation : Pitot tubeFigure 1-4: AA.

8 VentBypass Installation : Orifice plateFigure 1-5: AA. Orifice platePlanning4 Micro Motion Compact Density MeterBypass Installation : PumpFigure 1-6: ABCAA. VentB. Sample pointC. drop in the meterThe pressure drop in the meter depends on the process conditions. The following figuresillustrate the pressure drop for the meter at varying fluid Density and viscosity. In addition,these charts show how the meter compares to the Micro Motion 7835/7845 liquid the most accurate pressure drop calculations using your process variables, use the Micro Motionproduct selector available at Manual 5 Sample pressure drop calculations (fluid viscosity equals 2 cP)Figure 1-7: A. Pressure drop (bar)B. Flow rate (m3/hr)Note Density = 800 kg/m3 Viscosity = 2 cPPlanning6 Micro Motion Compact Density MeterSample pressure drop calculations (fluid viscosity equals 10 cP)Figure 1-8: A.

9 Pressure drop (bar)B. Flow rate (m3/hr)Note Density = 800 kg/m3 Viscosity = 10 requirementsFollowing are the DC power requirements to operate the meter: Explosion-proof/flameproof Meters :- 24 VDC, W typical, W maximum- Minimum recommended voltage: VDC with 1000 ft of 24 AWG (300 m mm2) power-supply cable- At startup, power source must provide a minimum of A of short-term currentat a minimum of V at the power-input terminals. Intrinsically safe Meters :- 24 VDC, W typical with 250 barrier, W maximum with 250 barrier- Minimum recommended voltage: VDC with 1000 ft of 22 AWG (300 m mm2) power-supply cablePlanningInstallation Manual 7 Power cable recommendations for explosion-proof/flameproof metersMinimum wire gauge (AWG per feet )Figure 1-9: 300ft600ft900ft1200ft1500ft1800ft2100ft2 400ft2700ft3000ftB2 1.

10 6V24 AWG maximumB. Distance of installationPlanning8 Micro Motion Compact Density MeterMinimum wire area (mm2 per meter)Figure 1-10: 0 . 00 0m20 0m 30 0m 40 0m 50 0m 60 0m 70 0m 80 0m 90 0m 100 0mB2 1 . 6V24 ft Minimum wire area (mm2)B. Distance of installationPlanningInstallation Manual 9 Power cable recommendations for intrinsically safe metersMinimum wire gauge (AWG per feet)Figure 1-11: 3 0 0 6 0 0 9 0 0 12 0 0 1 50 0 18 0 0 21 0 0 24 0 0 27 0 0 3 00 022 . 8 V24 V14151617181920212 223242526 ABA. AWGB. Distance of installationPlanning10 Micro Motion Compact Density MeterMinimum wire area (mm2 per meter)Figure 1-12: A. Minimum wire area (mm2)B. Distance of a pre- Installation meter checkCheck the meter prior to Installation to confirm that no damage occurred to the meterduring Remove the meter from the !