MITSUBISHI Electronic Multi-Measuring Instrument

This manual is a simple version. Please contact our Service Network for a detailed version of User's manual . MITSUBISHI Electronic Multi-Measuring Instrument Types ME110 SSR ME110 SSR-C. ME110 SSR-4AP ME110 SSR-CH. ME110 SSR-4 APH ME110 SSR-MB Before operating the Instrument , you should first read thoroughly this operation manual for safe operation and optimized performance ME110 SSR-4A2P. of the product. Deliver this user's manual to the end user. Safety precaution (Always read these instructions before using this equipment). Storage conditions For personnel and product safety please read the contents of these operating instructions carefully before using. Ambient temperature the :-20 to 60 C, average day temperature exceeds 35 C.

Types ME110SSR ME110SSR-4AP ME110SSR-4APH ME110SSR-4A2P ME110SSR-C ME110SSR-CH ME110SSR-MB Safety precaution Deliver this user’s manual

Tags:

  Manual

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of MITSUBISHI Electronic Multi-Measuring Instrument

1 This manual is a simple version. Please contact our Service Network for a detailed version of User's manual . MITSUBISHI Electronic Multi-Measuring Instrument Types ME110 SSR ME110 SSR-C. ME110 SSR-4AP ME110 SSR-CH. ME110 SSR-4 APH ME110 SSR-MB Before operating the Instrument , you should first read thoroughly this operation manual for safe operation and optimized performance ME110 SSR-4A2P. of the product. Deliver this user's manual to the end user. Safety precaution (Always read these instructions before using this equipment). Storage conditions For personnel and product safety please read the contents of these operating instructions carefully before using. Ambient temperature the :-20 to 60 C, average day temperature exceeds 35 C.

2 Please save this manual to make it accessible when required and always forward it to the end user. Humidity range 30~85%RH, non condensing. Atmosphere without corrosive gas, dust, salt, oil mist. Indicates that incorrect handling may cause hazardous conditions. A place without excessive shocks or vibration. Always follow the instructions because they are important to personal Do not expose to rain and water drips. safety. Otherwise, it could result in electric shock, fire, erroneous Do not expose to direct sunlight. operation, and damage of the Instrument . An area in where are pieces of metal and an inductive substance disperse. Normal service conditions Disposal When disposing of this product , treat it as industrial The battery is not used for this product.

3 Use the Instrument in an environment that meets the Normal service conditions as following points: Guarantee Ambient temperature :-5 to 50 C, average day temperature exceeds 35 C. The period of guarantee is for 1 year from the sale date, except in the case that the Humidity :30~85%RH, non condensing. failure has been caused by bad handling of the product, provided that it has been Altitude: 1000m or less installed according to the manufacture's instructions. Pollution Degree : 2. Atmosphere without corrosive gas, dust, salt, oil mist. A place without excessive shocks or vibration. EMC DIRECTIVE INSTRUCTION. Do not expose to rain and water drips. This section summarizes the precautions on conformance to the EMC Directive of the cabinet Do not expose to direct sunlight.

4 Constructed using this Instrument . An area in where are no pieces of metal and an inductive substance disperse. However, the method of conformance to the EMC Directive and the judgment on whether or not the Do not expose to strong electromagnetic field and ambient noises. cabinet conforms to the EMC Directive has to be determined finally by the manufacturer. 1. EMC Standards Installation instructions EN 61326-1:2006. EN 61000-3-2:2006/A1:2009/A2:2009. EN 61000-3-3:2008. This Instrument should be installed and used by a qualified electrician. The Instrument must not be powered and used until its definitive assembly on the cabinet's door. 1. 2. Installation (EMC directive). Verity the following points; The Instrument is to be mounted on panel of a cabinet.

5 Auxiliary power supply and Measuring ratings Therefore, the construction of a cabinet is important not only for safety but also for EMC. The Instrument is examined by the following conditions. Auxiliary power supply 100-240V AC+10-15%(50-60Hz) 10VA. Use a conductive cabinet. 100V DC+40-25% 6W. Six faces of a cabinet have to be ensured conductivity for each other. Voltage 277V AC phase to neutral / 480V AC phase to phase A cabinet has to be connected to earth by a thick wire of low impedance. Ratings Current 5A or 1A (via current transformer) Holes on faces of cabinet have to be 10 cm or less in diameter. Frequency 50/60Hz The terminals for protective earth and functional earth have to be connected to earth by a thick wire of low impedance.

6 Current circuits, C1, C2 and C3 are Measurement category . (A terminal for protective earth is important not only for safety but also for EMC.). Voltage circuits, P1, P2 and P3 are Measurement category . The Instrument is to be mounted on panel. All connections keep inside the cabinet. Protective earth: Maintains the safety of the Instrument and improves the noise resistance. Tighten the terminal screws with the specified torque and use the suitable pressure connectors Functional earth: Improves the noise resistance. andsuitable wire size. When wiring in the Instrument , be sure that it is done correctly by checking the Instrument s wiring diagrams. All connections should be kept inside the cabinet. Be sure there are no foreign substances such as sawdust or wiring debris inside the Instrument .

7 Wirings outside the cabinet have to be used with the shielded cable. Do not drop this Instrument from high place. If you drop it and the display is cracked, do not touch The following diagram shows how to provide good contact of the shielded cable. the liquid crystal and or get it in your mouth. When touch the liquid crystal, wash it away at once. Remove part of the outer cover. In order to prevent invasion of noise, do not bunch the control wires or communication cables with Remove part of the paint musk on the cabinet. the main circuit or power wire, or install them close to each other. Keep the distance between Connect those parts with the clamp. communicational signal lines, input signal lines and power lines, high voltage lines are shown below, when run parallel to each other.

8 Screw Conditions Length Shield section Clamp fitting Below 600V, or 600A power lines 30cm or more Other power lines 60cm or more Paint mask Operation instructions Shielded cable When the external terminals are connected to the external equipments, the Instrument and the external equipments must not be powered and used until its definitive assembly on the cabinet's door. The rating of the terminal of the external equipment should satisfy the rating of the external Check on your delivery terminal of this Instrument . (See Specifications.). Check the following point as soon as you receive MITSUBISHI Electronic Multi-Measureing Maintenance instructions Instrument : The package is in good condition. The product has not been damaged during transit.

9 Do not touch the terminals while all the circuits connected to this Instrument are alive. The product corresponds to your order specifications. Do not disassemble or modify the Instrument . This product had the following accessories. Do not contact a chemical dust cloth contact the Instrument for a long time, or do not wipe it with benzene, thinner, alcohol. Parts name Quantity Specifications Wipe dirt on surface with a soft dry cloth. User's manual Check the following points, 1 A3 size (this document). Condition of the apepearance Condition of the Display M5 belleville spring nuts Unusual sound, a smell, and generation of heat Attaching nuts 2 (contained in a bag). Condition of the wiring and the attachment 1. Mounting Wiring 1.

10 Dimensions of the panel 2. View angle The panel hole dimensions are as shown The contrast of the display changes Wirings of the terminals have to be fastened according to the following table. below. And it can be attached to a panel at view angles. Measurements inputs Protective erasing of thickness - Output terminal auxiliary power input terminal terminal 90 1 External Screw specification M4 screw M3 screw M4 screw View angle diameter Terminal For M4 screw of external For M3 screw of external For M4 screw of external diameter below diameter below diameter below 60 Fastening torque ~ ~ ~ 2. 4. 10. 90 1.. 60 . Do not fasten three wires or more to one terminal.. 60 Otherwise, it may generate heat or ignition. 60.. 2- 6.