Model: REOZJB - Kohler Power

model : 50 REOZJB . 190--600 V Diesel Standard Features D Kohler Co. provides one-source responsibility for the generating system and accessories. Ratings Range D The generator set and its components are 60 Hz 50 Hz prototype-tested, factory-built, and production-tested. Standby: kW 49--55 40--50 D The generator set accepts rated load in one step. kVA 49--69 40--56. D The 60 Hz generator set meets NFPA 110, Level 1, Prime: kW 45--50 35--45 when equipped with the necessary accessories and kVA 45--63 38--53 installed per NFPA standards. D A standard one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.

Diesel Kohler Co. provides one-source responsibility for the generating system and accessories. The generator set and its components are prototype-tested, factory-built, and production-tested.

Tags:

  System, Model, Reozjb

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Model: REOZJB - Kohler Power

1 model : 50 REOZJB . 190--600 V Diesel Standard Features D Kohler Co. provides one-source responsibility for the generating system and accessories. Ratings Range D The generator set and its components are 60 Hz 50 Hz prototype-tested, factory-built, and production-tested. Standby: kW 49--55 40--50 D The generator set accepts rated load in one step. kVA 49--69 40--56. D The 60 Hz generator set meets NFPA 110, Level 1, Prime: kW 45--50 35--45 when equipped with the necessary accessories and kVA 45--63 38--53 installed per NFPA standards. D A standard one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.

2 D Alternator features: d The unique Fast-Responset II excitation system delivers excellent voltage response and short-circuit capability using a permanent magnet (PM)-excited alternator. d The brushless, rotating-field alternator has broadrange reconnectability. D Other features: d Kohler designed controllers for guaranteed system integration and remote communication. See Controllers on page 3. d The low coolant level shutdown prevents overheating (standard on radiator models only). d Integral vibration isolation eliminates the need for under-unit vibration spring isolators. Generator Set Ratings 130_C Rise 105_C Rise Standby Rating Prime Rating Alternator Voltage Ph Hz kW/kVA Amps kW/kVA Amps 120/208 3 60 55/69 191 50/63 173.

3 127/220 3 60 55/69 180 50/63 164. 120/240 3 60 55/69 165 50/63 150. 120/240 1 60 49/49 204 45/45 188. 139/240 3 60 55/69 165 50/63 150. 220/380 3 60 55/69 104 50/63 95. 277/480 3 60 55/69 83 50/63 75. 347/600 3 60 50/63 60 45/56 54. 4P8. 110/190 3 50 45/56 170 42/53 161. 115/200 3 50 41/51 147 37/46 133. 120/208 3 50 40/50 139 35/44 122. 110/220 3 50 45/56 147 42/53 139. 110/220 1 50 40/40 182 38/38 173. 220/380 3 50 45/56 85 42/53 81. 230/400 3 50 41/51 74 37/46 66. 240/416 3 50 40/50 69 35/44 61. 120/240 1 60 55/55 229 50/50 208. 4Q10. 110/220 1 50 50/50 227 45/45 205. RATINGS: All three-phase units are rated at Power factor. All single-phase units are rated at Power factor.

4 Standby Ratings: The standby rating is applicable to varying loads for the duration of a Power outage. There is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. Obtain technical information bulletin (TIB-101) for ratings guidelines, complete ratings definitions, and site condition derates. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.

5 G5-205 (50 REOZJB ) 10/11m Alternator Specifications Specifications Alternator D NEMA MG1, IEEE, and ANSI standards compliance for Manufacturer Kohler temperature rise and motor starting. Type 4-Pole, Rotating-Field D Sustained short-circuit current of up to 300% of the rated Exciter type Brushless, current for up to 10 seconds. Permanent-Magnet D Sustained short-circuit current enabling downstream circuit Leads: quantity, type 12, Reconnectable breakers to trip without collapsing the alternator field. Voltage regulator Solid State, Volts/Hz Insulation: NEMA MG1 D Self-ventilated and dripproof construction. Material Class H D Vacuum-impregnated windings with fungus-resistant epoxy Temperature rise 130_C, Standby varnish for dependability and long life.

6 Bearing: quantity, type 1, Sealed Coupling Flexible Disc D Superior voltage waveform from a two-thirds pitch stator and Amortisseur windings Full skewed rotor. Voltage regulation, no-load to full-load D Fast-Responset II brushless alternator with brushless Permanent magnet (PM) alternator 2% Average exciter for excellent load response. 550 controller (with drift due to temperature variation) 3-Phase Sensing, One-step load acceptance 100% of Rating Unbalanced load capability 100% of Rated Standby Current Peak motor starting kVA: (35% dip for voltages below). 480 V, 380 V 4P8 (12 lead) 212 (60 Hz), 143 (50 Hz). 240 V, 220 V 4Q10 (4 lead) 155 (60 Hz), 133 (50 Hz).

7 Application Data Engine Engine Electrical Engine Specifications 60 Hz 50 Hz Engine Electrical system (12/24 Volt*) 60 Hz 50 Hz Manufacturer John Deere Battery charging alternator: 12 Volt/24 Volt Engine model 4045TF150 4045TF120 Ground (negative/positive) Negative Engine type 4-Cycle, Turbocharged Volts (DC) 12/24. Ampere rating 55/45. Cylinder arrangement 4 Inline Starter motor rated voltage (DC) 12/24. Displacement, L (cu. in.) (276). Battery, recommended cold cranking Bore and stroke, mm (in.) 106 x 127 ( x ). amps (CCA): 12 Volt/24 Volt Compression ratio :1 Quantity, CCA rating each One, 640/Two, 570. Piston speed, m/min. ( ) 457 (1500) 381 (1250) Battery voltage (DC) 12.

8 Main bearings: quantity, type 5, Replaceable Insert Rated rpm 1800 1500 *12-volt or 24-volt engine electrical systems are available. 82 (110) 70 (94). Max. Power at rated rpm, kWm (BHP) Fuel 4045TF150 4045TF120. Cylinder head material Cast Iron Fuel system 60 Hz 50 Hz Crankshaft material Forged Steel Fuel supply line, min. ID, mm (in.) ( ). Valve material: Fuel return line, min. ID, mm (in.) ( ). Intake Chromium-Silicon Steel Max. lift, fuel pump: type, m (ft.) Engine-Driven, ( ). Exhaust Stainless Steel Max. fuel flow, Lph (gph) 113 ( ) 109 ( ). Governor: type, make/ model Mechanical, Fuel prime pump Manual Stanadyne/DB4. Fuel filter Frequency regulation, no-load to full-load 3--5%.

9 Secondary 8 Microns @ 98% Efficiency Frequency regulation, steady state (mech. governor). (elect. isoch. gov.) Water Separator Yes Recommended fuel #2 Diesel Frequency Field-Convertible Air cleaner type, all models Dry Lubrication Exhaust Lubricating system 60 Hz 50 Hz Type Full Pressure Exhaust system 60 Hz 50 Hz Oil pan capacity, L (qt.) ( ). Exhaust manifold type Dry Oil pan capacity with filter, L (qt.) ( ). Exhaust flow at rated kW, m3/min. (cfm) (439) (360). Oil filter: quantity, type 1, Cartridge Exhaust temperature at rated kW, dry exhaust, _C (_F) 476 (889) 487 (909) Oil cooler Water-Cooled Maximum allowable back pressure, kPa (in.)

10 Hg) ( ). Exhaust outlet size at engine hookup, mm (in.) 98 ( ). G5-205 (50 REOZJB ) 10/11m Application Data Controllers Cooling Radiator system 60 Hz 50 Hz Ambient temperature, _C (_F) 50 (122). Engine jacket water capacity, L (gal.) ( ). Radiator system capacity, including Decision-Makerr 1 Controller engine, L (gal.) ( ) Single-light annunciation and basic controls with NFPA capability. Engine jacket water flow, Lpm (gpm) 125 (33) 106 (28) Relay logic, AC meters, and engine gauge features. Heat rejected to cooling water at rated 12-volt engine electrical system capability only. kW, dry exhaust, kW (Btu/min.) (2180) (1890) Remote or automatic start options.