Transcription of Multifunction Digital Timer H5CR - LIMASOFT
1 Timing functions9 selectable, including ON-delay, repeat cycle, OFF-delay, and one-shotContact typeSPDT relaySolid-state open collectorProduct typeEconomyStandardShort bodyEconomyStandardShort bodyUnit depth78 mm100 mm64 mm78 mm100 mm64 mm( in)( in)( in)( in)( in)( in)Panel mounting hardware Not providedProvidedProvidedNot providedProvidedProvidedSupplyAC24 V or 100 to 240 V; 50/60 Hz 24 V or 100 to 240 V; 50/60 Hz voltageDC12 to 24 V 12 to 24 V12 to 24 V 12 to 24 VPartBacklit display H5CR-BH5CR-S H5CR-BSH5CR-SSnumberUnlit displayH5CR-L H5CR-LS 1/16 DIN Timer withEasy-to-Use Functionsn Nine field-selectable output modes accommodate a wide variety of applicationsn All parameters set by scroll- through menus accessed from the front paneln Field-selectable time ranges from second to 9999 hoursn High-visibility alphanumeric LCD display has 8 mm high characters and built-in backlightn Precision control possible to secondn Four levels of key protection providedn 10-year battery back-upn Selectable elapsed time (UP) and time remaining (DOWN) displayn Short body model H5CR-S measures just 64 mm ( inches) deepAdd the supply voltage to the part number when you order.
2 For example, TIMERSO rdering InformationMultifunction Digital Timer H5 CRH5CR 1 DescriptionPart numberSoft cover with two mounting clips for front panel protectionY92A-48F1 Shock prevention terminal cover for Standard and Short body timers protects wiring connectionsY92A-48 TSockets forBottom surface or track mounting, top screw terminalsP2CF-08economy timersBack mounting, for use with Y92F-30 mounting adapter, bottom screw terminalsP3G-08n ACCESSORIESH5 CRH5CR2 DescriptionPart numberPanel mounting bracket (one supplied with H5CR-B and H5CR-S models)Y92F-30n REPLACEMENT PARTSPart numberH5CR-LH5CR-BH5CR-SClassificationEc onomy typeStandard typeShort body typeAC100 to 240 VAC, 50/60 Hz,100 to 240 VAC, 50/60 Hz, 24 VAC, 50/60 Hz24 VAC, 50/60 HzDC12 to 24 VDC, 20% max. 12 to 24 VDC, 20% ripplepermissible rippleOperating voltage85% to 110% of rated voltageAC3 VA at 60 Hz, 240 VAC DC1 W at 24 VDC 2 W at 24 VDCI nputsTypes availableReset and start signalReset, gate, start signal, and key protectSignal,TypeNo-voltage inputresetON impedance1 k max.
3 (Approx. 2 mA when 0 )and gate Residual voltage2 V max. in ON stateOFF impedance100 k minimumPulse width1 ms or 20 ms selectable for reset and signal20 ms for gateKeyTypeNo-voltage inputprotectON impedance100 k max. (Approx. 2 mA when 0 )Residual voltage1 V max. in ON stateOFF impedance100 k minimumResponse time1 secondTypeTime limitSPDT relay output or NPN open collector transistor output (H5CR-qS)Instantaneous RelayMax. load5 A, 250 VAC resistive load ( = 1)Min. load10 mA, 5 VDCS olid-Max. load100 mA, 30 VDCstateResidual voltage2 V max., 1 V typicalRepeat accuracyPower start , second start , second max. (rate for set value)Setting error Resetting systemPower reset (A, A-1, A-2, B, D and E modes)External, manual, automatic resets (may be internal depending on A-1, B, B-1, D and Eoperation modes)Resetting timePower second minimum (A, A-1, A-2, B, D and E modes)Indicators4-digit LCD alphanumeric4-digit LCD alphanumeric display with backlightingdisplay without backlighting8 mm ( in) H present value, 4 mm ( in) H set value8 mm ( in) H presentvalue, 4 mm ( in) Hset valueSpecificationsSupplyvoltagePowercon sumptionControloutput*One-shot time, seven choices sec, sec, 1 sec, 5 sec, 10 sec, 15 sec, 20 secRange selectionTime unitMaximum setting.
4 - - - seconds- - . - - seconds- - - . - seconds- - - - s1 second9999 seconds- - min - - s1 second99 minutes 59 seconds- - - . - minutes- - - - min1 minute9999 minutes- - hr - - min1 minute99 hours 59 minutes- - - . - hours- - - - hr1 hour9999 hoursn RANGE AND OPERATION MODE SELECTIONMode OperationOutput typeAON-delaySustained orA-1 Sustained start signal ON-delay one-shot*A-2 Power ON-delayA-3 Power ON-delay/non-powerresettableBRepeat cycleB-1 Repeat cycle/non-powerresettableDOFF-delaySusta inedEOne-shotFCumulative signal ON-delayH5 CRH5CR3 Memory functionRetains preset values for 10 years at 25 C (77 F)MaterialsPlastic caseMountingPanel or surface; Y92F-30 Panel, Y92F-30 mounting bracket includedmounting bracket includedConnections8-pin round socketScrew terminalsWeight105 g ( oz.)160 g ( oz.)120 g ( oz.)ApprovalsUL/CSA/SEVO perating ambient temperature-10 to 55 C (14 to 131 F) with no icingHumidity35% to 85% RHVibration Mechanical durability10 to 55 Hz with mm single amplitude in 3 directionsMalfunction durability10 to 55 Hz with mm single amplitude in 3 directionsShockMechanical durability30 G each in three directionsMalfunction durability10 G each in three directionsVariation due to voltage changeIncluded in "Repeat accuracy" specificationVariation due to temperature changeIncluded in "Repeat accuracy" specificationInsulation resistance100 M min.
5 At 500 VDC between current-carrying terminal and exposed non-current-carrying metal parts, and between non-continuous strength2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminal and exposednon-current-carrying metal parts for 100 to 240 VAC type1,000 VAC for both 24 VAC and 12 to 24 VDC typesService lifeMechanical10 million operations minimum(SPDT relay)Electrical100,000 operations minimum at 5 A, 240 VAC, resistive load ( = 1)SPECIFICATIONS continuedTiming Chartsn OPERATION MODESThe gate input is not included on "economy" models H5CR-L and mode A: Signal ON delay 1 ( Timer resets when power comes on.)Timing begins at the leading edge ofthe start signal. The control output willbe energized when the present valueequals the preset time. The output willbe sustained until a reset signal isapplied, until power is interrupted, orfor a programmable one-shot mode A1: Signal ON delay 2 ( Timer resets when power comes on.)
6 Timing begins at the leading edge of thestart signal. The control output will beenergized if the start signal is sustainedfor an amount of time equal to the presettime. The output will be sustained untilthe start signal is interrupted, until a resetsignal is applied, until power isinterrupted, or for a programmable one-shot time signalGateResetControl outputSet valueUP0 Set valueDOWN0 PowerStart signalSet valueUP0 GateResetControl outputSet valueDOWN0 TimingdiagramTimingdiagramSustained outputOne-shotOne-shot outputs can be set to s, s, 1 s, 5 s, 10 s, and 20 mode A-2: Power ON delay 1 ( Timer resets when power comes on.)Timing begins when power is signals act as a gate input,causing the present value to hold. Thecontrol output will be energized whenthe present value equals the presettime. The output will be sustained untila reset signal is applied, until power isinterrupted, or for a programmableone-shot time mode B: Repeat cycle 1 ( Timer resets when power comes on.)
7 The OFF/ON cycle is initiated at theleading edge of the start signal. Thecontrol output will be OFF for the firstcycle. In subsequent cycles the outputwill be ON for the programmable one-shot time period, then OFF for theremainder of the preset time. The cyclewill be repeated until a reset input isapplied or power is OFF/ON cycle is initiated at theleading edge of the start signal. Theoutput relay will be OFF for the presettime, then ON for the preset time. Thecycle will be repeated until a reset inputis applied or power is begins when power is signals act as a gate input, causingthe present value to hold. The controloutput will be energized when thepresent value equals the preset output will be sustained until a resetsignal is applied or for a programmableone-shot time period. If power to the unitis interrupted, the control output will bede-energized.
8 The output will re-energize once power is signalGateResetControl outputSet valueUP0 Set valueDOWN0 TimingdiagramPowerStart signalGateResetControl outputSet valueUP0 Set valueDOWN0 TimingdiagramPowerStart signalGateResetControl outputSet valueUP0 Set valueDOWN0 TimingdiagramPowerStart signalGateResetControl outputSet valueUP0 Set valueTimingdiagramSustained outputOne-shotOne-shot outputs can be set to s, s, 1 s, 5 s, 10 s,and 20 = one-shot time before power interruptiont-a = remaining one-shot time after power interruptionOutput mode A-3: Power ON delay 2 ( Timer does not reset when power comes on.)DOWN0H5 CRH5CR5 Output mode E: Interval ( Timer resets when power comes on.)Timing begins on the leading edge of thestart signal. The control output is onlyenergized during timing. The Timer isreset when power is interrupted or areset signal is OFF/ON cycle is initiated at theleading edge of the start signal.
9 Theoutput relay will be OFF for the presettime, then ON for the preset time. Thecycle will be repeated until a reset inputis applied. If power to the unit isinterrupted, the present value will cycle will continue from that pointonce power is OFF/ON cycle is initiated at theleading edge of the start signal. Thecontrol output will be OFF for the firstcycle. In subsequent cycles the outputwill be ON for the programmable one-shot time period, then OFF for theremainder of the preset time. The cyclewill be repeated until a reset input isapplied. If power to the unit isinterrupted, the present value will cycle will continue from that pointonce power is mode D: Signal OFF delay ( Timer resets when power comes on.)The control output is energized at theleading edge of the start signal. Timingbegins at the trailing edge of the startsignal. The control output is de-energized when the present value equalsthe preset signalGateResetControl outputSet valueUP0 DOWN0 Set valueTimingdiagramStart signalGatePowerResetDOWN0 Set valueUP0 Control outputSet valueTimingdiagramPowerStart signalGateResetDOWN0 Set valueUP0 TimingdiagramSet valueControl outputPowerStart signalGateResetControl outputSet valueUP0 Set valueDOWN0 TimingdiagramSustained outputOne-shotOne-shot outputs can be set to s, s, 1 s, 5 s, 10 s,and 20 = one-shot time before power interruptiont-a = remaining one-shot time after power interruptionOutput mode B-1: Repeat cycle 2 ( Timer does not reset when power comes on.)
10 H5 CRH5CR6 Timing begins on the leading edge of thestart signal. The control output isenergized when the cumulative elapsedtime of the start signal is equal to thepreset time. The output is sustained untilpower is interrupted or a reset signal mode F: Cumulative ( Timer does not reset when power comes on.)n TIMERSD imensionsUnit: mm (inch)PowerStart signalGateResetControl outputSet valueUP0 Set valueDOWN0 TimingdiagramEconomy Models H5CR-L, H5CR-LS48( )48( )Short Body Models H5CR-S, H5CR-SS48( )48( ) terminal screw,effective length: 6 mm ( in)Standard Models H5CR-B, H5CR-BS48( )48( )6( )100( ) ( ) ( )64( )6( ) terminal screw,effective length: 6 mm ( in) ( ) ( )6( ) ( ) ( ) ( )H5 CRH5CR7n PANEL MOUNTING ADAPTER Y92F-30 The diagram below shows the adapter on an H5CR-L Timer . The mounting depths for H5CR-B and H5CR-S are the same as shown inTimer ( ) ( )PanelY92F-30 Panel mountingadapterP3G-08 Rear surfaceconnection socket58( )48( )Panel CutoutsPanel cutouts shown at rightconform to DIN min.