Operating Instructions Proline Promag 10 HART

BA00082D/06/ Products Solutions Services 71315813. Valid as of software version V (device software). Operating Instructions Proline Promag 10. HART. Electromagnetic flowmeter 6. Products Solutions Services Promag 10. Table of contents 1 Safety Instructions .. 4 9 Troubleshooting .. 75. Designated use .. 4 Troubleshooting Instructions .. 75. Installation, commissioning and operation .. 4 System error messages .. 76. Operational safety .. 4 Process error messages .. 77. Return .. 5 Process errors without messages .. 78. Notes on safety conventions and icons .. 5 Response of outputs to errors .. 79. Spare parts .. 80. 2 Identification .. 6 Return.

BA00082D/06/EN/17.16 Products Solutions Services 71315813 Valid as of software version V 1.04.00 (device software) Operating Instructions Proline …

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Operating Instructions Proline Promag 10 HART

1 BA00082D/06/ Products Solutions Services 71315813. Valid as of software version V (device software). Operating Instructions Proline Promag 10. HART. Electromagnetic flowmeter 6. Products Solutions Services Promag 10. Table of contents 1 Safety Instructions .. 4 9 Troubleshooting .. 75. Designated use .. 4 Troubleshooting Instructions .. 75. Installation, commissioning and operation .. 4 System error messages .. 76. Operational safety .. 4 Process error messages .. 77. Return .. 5 Process errors without messages .. 78. Notes on safety conventions and icons .. 5 Response of outputs to errors .. 79. Spare parts .. 80. 2 Identification .. 6 Return.

2 84. Disposal .. 84. Device designation .. 6 Software history .. 84. Certificates and approvals .. 8. Registered trademarks .. 8. 10 Technical data .. 85. 3 Installation .. 9 Application .. 85. Function and system design .. 85. Incoming acceptance, transport and storage .. 9 Input .. 85. Mounting requirements .. 11 Output .. 85. Installation Instructions .. 20 Power supply .. 86. Post-installation check .. 43 Performance characteristics .. 87. Installation .. 87. 4 Wiring .. 44 Environment .. 87. Connecting the remote version .. 44 Process .. 88. Connecting the measuring unit .. 50 Mechanical construction .. 94. Potential equalization .. 52 Operability.

3 106. Degree of protection .. 55 Certificates and approvals .. 106. Post-connection check .. 56 Ordering information .. 108. Accessories .. 108. Documentation .. 108. 5 Operation.. 57. Display and Operating elements .. 57 11 Appendix .. 109. Brief Operating Instructions on the function matrix 58 Illustration of the function matrix .. 109. Displaying error messages .. 60 Group SYSTEM UNITS .. 110. Communication .. 61 Group OPERATION .. 112. USER INTERFACE .. 113. Group TOTALIZER .. 114. 6 Commissioning .. 68 Group CURRENT OUTPUT .. 115. Function check .. 68 Group PULSE/STATUS OUTPUT .. 117. Switching on the measuring device .. 68 Group COMMUNICATION.

4 122. Brief commissioning guide .. 68 Group PROCESS PARAMETER .. 123. Commissioning after installing a new electronics Group SYSTEM PARAMETER .. 125. board .. 69 Group SENSOR DATA .. 128. Empty-pipe/full-pipe adjustment .. 70 Group SUPERVISION .. 130. Group SIMULATION SYSTEM .. 132. 7 Maintenance .. 71 Group SENSOR VERSION .. 132. Group AMPLIFIER VERSION .. 132. Exterior cleaning .. 71 Factory settings .. 133. Seals .. 71. Index .. 136. 8 Accessories .. 72. Device-specific accessories .. 72. Measuring principle-specific accessories .. 72. Communication-specific accessories .. 73. Service-specific accessories .. 73. Endress+Hauser 3. Safety Instructions Promag 10.

5 1 Safety Instructions Designated use The measuring device described in this Operating Manual is to be used only for measuring the flow rate of conductive fluids in closed pipes. Most liquids can be measured as of a minimum conductivity of 50 S/cm. Examples: Acids, alkalis Drinking water, wastewater, sewage sludge Milk, beer, wine, mineral water, etc. Resulting from incorrect use or from use other than that designated the operational safety of the measuring devices can be suspended. The manufacturer accepts no liability for damages being produced from this. Installation, commissioning and operation Please note the following: Installation, connection to the electricity supply, commissioning and maintenance of the device must be carried out by trained, qualified specialists authorized to perform such work by the facility's owner-operator.

6 The specialist must have read and understood this Operating Manual and must follow the Instructions it contains. The device must be operated by persons authorized and trained by the facility's owner- operator. Strict compliance with the Instructions in the Operating Manual is mandatory. With regard to special fluids, including fluids used for cleaning, Endress+Hauser will be happy to assist in clarifying the corrosion-resistant properties of wetted materials. However, minor changes in temperature, concentration or in the degree of contamination in the process may result in variations in corrosion resistance. For this reason, Endress+Hauser does not accept any responsibility with regard to the corrosion resistance of wetted materials in a specific application.

7 The user is responsible for the choice of suitable wetted materials in the process. If welding work is performed on the piping system, do not ground the welding appliance through the Promag flowmeter. The installer must ensure that the measuring system is correctly wired in accordance with the wiring diagrams. The transmitter must be grounded apart from when special protective measures are taken ( galvanically isolated SELV or PELV power supply). Invariably, local regulations governing the opening and repair of electrical devices apply. Operational safety Please note the following: Measuring systems for use in hazardous environments are accompanied by separate Ex documentation, which is an integral part of this Operating Manual.

8 Strict compliance with the installation Instructions and ratings as stated in this supplementary documentation is mandatory. The symbol on the front of this Ex documentation indicates the approval and the certification body ( 0 Europe, 2 USA, 1 Canada). The measuring device complies with the general safety requirements in accordance with EN 61010-1, the EMC requirements of IEC/EN 61326 and NAMUR Recommendations NE 21 and NE 43. Depending on the application, the seals of the process connections of the Promag H sensor require periodic replacement. When hot fluid passes through the measuring tube, the surface temperature of the housing increases.

9 In the case of the sensor, in particular, users should expect temperatures that can be close to the fluid temperature. If the temperature of the fluid is high, implement sufficient measures to prevent burning or scalding. 4 Endress+Hauser Promag 10 Safety Instructions The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Operating Instructions . Return The measuring device must be returned if repairs or a factory calibration are required, or if the wrong measuring device has been ordered or delivered. According to legal regulations, Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when handling returned products that are in contact with medium.

10 To ensure swift, safe and professional device returns, please read the return procedures and conditions on the Endress+Hauser website at Notes on safety conventions and icons The devices are designed to meet state-of-the-art safety requirements, have been tested, and left the factory in a condition in which they are safe to operate. The devices comply with the applicable standards and regulations in accordance with EN 61010-1 "Safety requirements for electrical equipment for measurement, control and laboratory use". The devices can, however, be a source of danger if used incorrectly or for anything other than the designated use. Consequently, always pay particular attention to the safety Instructions indicated in this Operating Manual by the following icons: # Warning!