P70, P72, and P170 Series Controls for dual Pressure applications Part No. 24-8607-0, Rev. H. installation instructions Issued March 2016. Refer to the QuickLIT Web site for the most up-to-date version of this document. applications P72 models have a Double-Pole Single-Throw (DPST). switch with load-carrying contacts that can provide The P70, P72, and P170 Controls for dual Pressure direct control of 208/240 VAC, single-phase motors up applications provide combined high and low Pressure to 3 hp, 480, and 600 VAC single-phase control of compressors on commercial refrigeration and non-compressor motors and 208/220 VAC, 3-phase air conditioning applications . motors up to 5 hp.

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions 8 Piping P70, P72, and P170 dual pressure controls are typically …

Tags:

  Applications, Series, Installation, Instructions, Pressure, Dual, Dual pressure applications installation instructions

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of P70, P72, and P170 Series Controls for Dual Pressure ...

1 P70, P72, and P170 Series Controls for dual Pressure applications Part No. 24-8607-0, Rev. H. installation instructions Issued March 2016. Refer to the QuickLIT Web site for the most up-to-date version of this document. applications P72 models have a Double-Pole Single-Throw (DPST). switch with load-carrying contacts that can provide The P70, P72, and P170 Controls for dual Pressure direct control of 208/240 VAC, single-phase motors up applications provide combined high and low Pressure to 3 hp, 480, and 600 VAC single-phase control of compressors on commercial refrigeration and non-compressor motors and 208/220 VAC, 3-phase air conditioning applications . motors up to 5 hp.

2 See Table 3. IMPORTANT: Except for those models listed as These Controls are available in several Pressure refrigeration temperature limiting Controls , use this ranges and are compatible with most common P70, P72, and P170 Series Controls for dual refrigerants. Ammonia-compatible models are also Pressure applications only as an operating control. available (P70L and P70M only). See Table 2. Where failure or malfunction of the P70, P72, or P170 Pressure Control could lead to personal injury The MICRO-SET option provides fine adjustment of or property damage to the controlled equipment or the differential setting for precision Pressure control of other property, additional precautions must be low Pressure applications .

3 Designed into the control system. Incorporate and Some models feature Limited Knob Adjustment, which maintain other devices, such as supervisory or restricts adjustment of the Pressure settings and deters alarm systems or safety or limit Controls , intended to over-adjustment or tampering. See Low Pressure warn of or protect against failure or malfunction of Limited Knob Adjustment. the P70, P72, or P170 Pressure Control. A Manual Reset Lockout option does not allow the P70S and P170S models have independently operated Pressure control to reset automatically after CUT OUT. high and low Pressure Single-Pole Double-Throw is reached, and provides shutdown capability for (SPDT) switches that can be wired to satisfy a variety unmonitored equipment.

4 See Manual Reset Operation. of control requirements. These adaptable Controls have NEMA 1 enclosures are standard on most models. a high Pressure manual reset lockout mechanism that NEMA 3R enclosures are also available. is convertible to automatic reset. See Table 1. Table 1 through Table 2 list the standard models and P70L, M, N, and P170L, M, N models have a Single- features of P70, P72, and P170 Controls for dual Pole Single-Throw (SPST) switch. Models are Pressure applications . These standard models are available with automatic or manual reset lockout available through most authorized options. Models with manual reset are available with Johnson Controls /PENN distributors.

5 Either high-side-only manual reset, or low-side and high-side manual reset. (See Table 1 and Table 3.). Ammonia compatible models are available (P70L and P70M only). See Table 2. P70, P72, and P170 Series Controls for dual Pressure applications installation 1. instructions Table 1: Standard Model P70, P72, and P170 MICRO-SET dual Pressure Controls for Non-Corrosive Refrigerants Model Code Switch Low Pressure Side High Pressure Side Pressure Limited Number Action psig (kPa) psig (kPa) Connector Knob Range Differential Range Differential Adjustment (Non- Adjustable). P70LB-61 SPST 12 in. Hg to Min 5 (34) 100 to 500 Fixed 36 in. Capillary Low CUT OUT. 80 psig Max 35 (241) (690 to 3,447) Approximately with 1/4 in.

6 (-41 to 552) 65 (448) Flare Nut P70MA-181 Lockout None Requires Manual Reset P70SA-11 Two Fixed at Independent 65 (448) or SPDT Lockout Requires Manual Reset P170LB-61 SPST Fixed 1/4 in. Male Low CUT OUT. Approximately Flare 65 (448) Connector P170MA-181 Lockout None Requires Manual Reset P170SA-11 Two Fixed at Independent 65 (448) or SPDT Lockout Requires Manual Reset 1. Control models with high Pressure side (only) that are UL Listed as Refrigeration Pressure Limiting Controls . Table 2: Standard Model P70, P72, and P170 All Range dual Pressure Controls for Ammonia Model Code Switch Low Pressure Side High Pressure Side Pressure Limited Number Action psig (kPa) psig (kPa) Connector Knob Range Differential Range Differential Adjustment (Non- Adjustable).

7 P70LA-21 SPST 20 in. Hg to Min 7 (48) Max 100 to 500 Fixed 1/4 in. Female None 100 psig 50 (345) (690 to 3,447) Approximately NPT. (-68 to 690) 65 (448) Connector P70MA-21 Lockout Requires Manual Reset 1. Control models with high Pressure side (only) that are UL Listed as Refrigeration Pressure Limiting Controls . 2 P70, P72, and P170 Series Controls for dual Pressure applications installation instructions Table 3: Standard Model P70, P72, and P170 All Range dual Pressure Controls for Non-Corrosive Refrigerants Model Code Switch Low Pressure Side High Pressure Side Pressure Limited Number Action psig (kPa) psig (kPa) Connector Knob Range Differential Range Differential Adjustment (Non- Adjustable).

8 P70LB-11 SPST 20 in. Hg to Min 6 (41) 100 to 500 Fixed 36 in. Capillary Low CUT OUT. 100 psig Max 50 (345) (690 to 3,447) Approximately with 1/4 in. (-68 to 690) 65 (448) Flare Nut P70MA-11 Lockout None Requires P70NA-1 Fixed (Manual Manual Reset Reset). P72LA-11 DPST Min 7 (48) Fixed None Max 50 (345) Approximately 65 (448) Low CUT OUT. P72LB-11. P72MA-11 Lockout None Requires Fixed (Manual Manual Reset P72NA-11. Reset). P170LB-11 SPST Min 7 (48) Fixed 1/4 in. Male Low CUT OUT. Max 50 (345) Approximately Flare 65 (448) Connector P170MA-11 Lockout None Requires P170NA-1 Fixed (Manual Manual Reset Reset). 1. Control models with high Pressure side (only) that are UL Listed as Refrigeration Pressure Limiting Controls .

9 installation Dimensions See Figure 1 and Figure 2 for dimensional information. P70, P72, and P170 Series Controls for dual Pressure applications installation instructions 3. Figure 1: Dimensions for P70, P72, and P170 dual Pressure Controls with NEMA 1 Enclosure, in. (mm). Figure 2: Dimensions for P70, P72, and P170 dual Pressure Controls with NEMA 3R Enclosure, in. (mm). 4 P70, P72, and P170 Series Controls for dual Pressure applications installation instructions Mounting Use the two inner holes with the Universal Mounting Bracket (and screws supplied) when CAUTION: Risk of Property Damage. mounting the control to a flat horizontal Mount the Pressure control separately surface.

10 See Figure 3. ! from the electrical cabinet and seal all electrical piping to prevent ammonia from migrating to electrical components. Where there may be exposure to ammonia, use only ammonia-compatible control modules and Pressure connections. System shutdown due to improper adjustment may cause property damage. Figure 3: Mounting dual Pressure Controls with NEMA 1 Enclosures CAUTION: Risk of Property Damage. Mount the P70, P72, or P170 Pressure ! Control according to the instructions and Mount Controls with NEMA 3R enclosures in a level, upright position with the bellows and conduit guidelines included with the control. connection facing down. Ensure that all gaskets These instructions and guidelines are are in place.