FIELDVUE DLC3010 Digital LevelControllerThe FIELDVUE DLC3010 Digital Level Controller is usedwith Level sensors to measure liquid Level , the Level ofthe interface between two liquids, or liquid specificgravity (density). Changes in Level or specific gravityexert a buoyant force on a displacer, which rotates atorque tube shaft. The Digital Level Controller convertsthis rotational motion to an electronic DLC3010 is a communicating,microprocessor-based instrument that can beconfigured to sense the Level , interface Level , ordensity of liquids. In addition to the normal function ofproviding a 4 to 20 milliampere current signal, theDLC3010, using HART communications protocol,gives easy access to information critical to processoperation.

www.Fisher.com Fisher™ FIELDVUE™ DLC3010 Digital Level Controller The FIELDVUE DLC3010 digital level controller is used with level sensors to measure liquid level, the level of

Tags:

  Controller, Levels, Digital, Dlc3010, Dlc3010 digital level controller

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Product Bulletin DLC3010 Digital Level Controller …

1 FIELDVUE DLC3010 Digital LevelControllerThe FIELDVUE DLC3010 Digital Level Controller is usedwith Level sensors to measure liquid Level , the Level ofthe interface between two liquids, or liquid specificgravity (density). Changes in Level or specific gravityexert a buoyant force on a displacer, which rotates atorque tube shaft. The Digital Level Controller convertsthis rotational motion to an electronic DLC3010 is a communicating,microprocessor-based instrument that can beconfigured to sense the Level , interface Level , ordensity of liquids. In addition to the normal function ofproviding a 4 to 20 milliampere current signal, theDLC3010, using HART communications protocol,gives easy access to information critical to processoperation.

2 You can obtain information about theprocess, instrument, or sensor using the 475 or 375 Field Communicator. The DLC3010 can be used inanalog or HART Digital signaling mode with theEmerson Automation Solutions DeltaV connection for HART communication may bemade at any point in the field wiring that meets theHART impedance requirements. Configuration,calibration, diagnostics, parameter review, signalmonitoring and alert monitoring are all availableW7977-2through the HART protocol. Information from the fieldcan be integrated into control systems or be receivedon a single loop DLC3010 Digital Level Controller is designed todirectly replace standard pneumatic and electroniclevel transmitters.

3 It mounts on a wide variety of Fisher249 caged and cageless Level Digital Level ControllerD102727X012 Product : DLC3010 August 2017 DLC3010 Digital Level ControllerD102727X012 Product : DLC3010 August 2017 2 DLC3010 Digital Level Controller SpecificationsAvailable ConfigurationsDLC3010 Digital Level Controller :Mounts on caged and cageless 249 sensors. Seetables 4 and 5 and sensor : TransmitterCommunications Protocol: HARTI nput SignalLevel, Interface, or Density: Rotary motion of torquetube shaft proportional to changes in liquid Level ,interface Level , or density that change the buoyancyof a Temperature: Interface for 2- or 3-wire 100 ohm platinum RTD for sensing processtemperature, or optional user-entered targettemperature to permit compensating for changes inspecific gravityOutput SignalAnalog: 4 to 20 milliamperes DC (Jdirectaction increasing Level , interface, or densityincreases output.)

4 Or Jreverse action increasinglevel, interface, or density decreases output)High saturation: mALow saturation: mAHigh alarm: mALow Alarm: mAOnly one of the above high/low alarm definitions isavailable in a given configuration. NAMUR NE 43compliant when high alarm Level is : HART 1200 Baud FSK (frequency shift keyed)HART impedance requirements must be met toenable communication. Total shunt impedanceacross the master device connections (excluding themaster and transmitter impedance) must be between230 and 600 ohms. The transmitter HART receiveimpedance is defined as:Rx: 42K ohms and Cx: 14 nFIn point-to-point configuration, analog and digitalsignalling are available.

5 The instrument may bequeried digitally for information, or placed in Burstmode to regularly transmit unsolicited processinformation digitally. In multi-drop mode, the outputcurrent is fixed at 4 mA, and only digitalcommunication is LevelController(1)w/ 3-Inch249W, Usinga 14-inchDisplacerw/ All Other249 SensorsIndependentLinearity$ ofoutput span$ ofoutput span$ ofoutput spanHysteresis< ofoutput span- - -- - -Repeatability$ of fullscale output$ ofoutput span$ ofoutput spanDead Band< ofinput span- - -- - -Hysteresis plusDeadband- - -< ofoutput span< ofoutput spanNOTE: At full design span, reference To lever assembly rotation.

6 At effective proportional band (PB)<100%,linearity, dead band, repeatability, power supplyeffect, and ambient temperature influence arepotentially derated by the factor (100%/PB)Operating InfluencesPower Supply Effect: Output changes < of fullscale when supply varies between minimum andmaximum voltage specifications. -continued-Table of ContentsDLC3010 Specifications of Operation Level Sensor Specifications Level Sensors Information Insulator Digital Level Controller Digital Level ControllerD102727X012 Product : DLC3010 August 2017 3 DLC3010 Digital Level Controller Specifications (continued)Transient Voltage Protection: The loop terminals areprotected by a transient voltage suppressor.

7 Thespecifications are as follows:Pulse WaveformMax VCL(Clamping Voltage) (V)Max IPP(Pulse Peak@ Current) (A)Rise Time(ms)Decay to50% (ms) : s = microsecondAmbient Temperature: The combined temperatureeffect on zero and span without the 249 sensor is lessthan of full scale per degree Kelvin over theoperating range -40 to 80_C (-40 to 176_F)Process Temperature: The torque rate is affected bythe process temperature (see figure 1). The processdensity may also be affected by the Density: The sensitivity to error in knowledgeof process density is proportional to the differentialdensity of the calibration.

8 If the differential specificgravity is , an error of specific gravity units inknowledge of a process fluid density represents 10%of CompatibilityMeets EN 61326 1:2013 and EN 61326 2 3:2006 Immunity Industrial locations per Table 2 of EN 61326 1 and Table of EN 61326 2 3. Performance is shown in table 1 below. Emissions Class A ISM equipment rating: Group 1, Class ASupply Requirements (See figure 3)12 to 30 volts DC ; mAInstrument has reverse polarity minimum compliance voltage of is requiredto guarantee HART compensation: for ambient parameter compensation: for processtemperature (requires user-supplied tables).

9 Manual compensation: for torque tube rate at targetprocess temperature is MonitorsLinked to jumper-selected Hi (factory default) or Loanalog alarm signal:Torque tube position transducer: Drive monitor andsignal reasonableness monitorUser-configurable alarms: Hi-Hi and Lo-Lo Limitprocess alarmsHART-readable only:RTD signal reasonableness monitor: When RTDinstalledProcessor free-time in Non Volatile Memory alarms: Hi and Lo limit processalarms, Hi and Lo limit temperature alarms, Hi and Lolimit electronics temperature alarmsDiagnosticsOutput loop current meter specific gravity measurement in Level mode: usedto update specific gravity parameter to improveprocess measurementDigital signal-tracing capability: by review of troubleshooting variables , andBasic trending capability for PV, TV and Meter IndicationsLCD meter indicates analog output on a percent scalebar graph.

10 The meter also can be configured todisplay:Process variable in engineering units only. Percent range range alternating with process variable orProcess variable, alternating with process temperature(and degrees of pilot shaft rotation).Electrical ClassificationPollution Degree IV, Overvoltage Category II per IEC61010 clause dHazardous Area:CSA Intrinsically Safe, Explosion proof, Division 2,Dust Ignition proofFM Intrinsically Safe, Explosion proof,Non incendive, Dust Ignition proofATEX Intrinsically Safe, Type n, FlameproofIECEx Intrinsically Safe, Type n, FlameproofRefer to tables 8, 9, 10, and 11 for additional Housing:CSA Type 4 XFM NEMA 4 XATEX IP66 IECEx IP66-continued- DLC3010 Digital Level ControllerD102727X012 Product .